Plan Review Details - Permit 04081380
Plan Review Stops For Permit 04081380
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-07-06 Cont ID  
Sent By rmcdouga Date 2005-07-06 Time 12:26 Rev Time 0.00
Received By rmcdouga Date 2005-07-06 Time 12:26 Sent To  
Notes
2005-07-06 00:00:00REVISION TO CHANGE ROOF COVERING FROM
 ASPHALT SHINGLES TO CLAY TILE IS OK.
 ITEMS SUBMITTED: LETTER FROM DESIGNER OF
 RECORD, TRUSS LAYOUT AND DRAWINGS AND
 PRODUCT APPROVALS FOR CLAY TILE AND
 POLYFOAM ADHESIVE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-05-25 Cont ID  
Sent By jgomez Date 2005-05-25 Time 17:54 Rev Time 0.50
Received By jgomez Date 2005-05-25 Time 17:54 Sent To PC
Notes
2005-05-25 00:00:00REVISION CHECKLIST:
  
 1- PRODUCT APPROVAL SUBMITTED FOR ROOF
 TILE ADHESIVE IS NOT FOR THIS
 APPLICATION. NEED CORRECT POLYFOAM THAT
 IS TO BE USED FOR ROOF CLAY TILE.
  
 2- PROVIDE 2 COPIES OF TRUSS LAYOUT.
  
 3- TRUSS ENGINEER TO PROVIDE TRUSS
 LAYOUT WITH ORIGINAL SIGNATURE AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTES
 WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS.
  
 4- ENGINEER OF RECORD TO REVIEW AND
 APPROVE TRUSS LAYOUT AND TRUSS PACKAGE
 PRIOR TO SUBMITTAL TO THIS OFFICE.
 APPLY REVIEW STAMP AS VERIFICATION OF
 APPROVAL OF PACKAGE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-03-01 Cont ID  
Sent By jgomez Date 2005-03-01 Time 09:25 Rev Time 0.25
Received By jgomez Date 2005-03-01 Time 08:36 Sent To PC
Notes
2005-03-01 00:00:00REVISION CHECKLIST:
 1- ROOF STRUCTURE WAS DESIGNED TO CARRY
 SHINGLES. PRODUCT APPROVAL SUBMITTED IS
 FOR CLAY TILE. ENGINEER OF RECORD TO
 REVISE PLANS/SPECS TO REFLECT ADDITIONAL
 ROOF LOAD.
  
 2- ENGINEER OF RECORD TO SPECIFY ROOF
 TILE FASTENING AS REQUIRED BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-12-03 Cont ID  
Sent By jgomez Date 2004-12-03 Time 10:28 Rev Time 0.50
Received By jgomez Date 2004-12-03 Time 10:28 Sent To PC
Notes
2004-12-03 00:00:00BUILDING SUBMITTAL RESPONDING TO PROVISO
 DATED 11-16-04.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-11-16 Cont ID  
Sent By jgomez Date 2004-11-16 Time 15:49 Rev Time 0.00
Received By jgomez Date 2004-11-16 Time 15:49 Sent To PC
Notes
2004-11-16 00:00:00BUILDING REVIEW PROVISO:
 1-NEED TO SPECIFY CEILING FANS SIZE AS
 REQUIRED BY TABLE 6-6 OF CHAPTER 13 FBC
 2001 WHEN THE CEILING FAN CREDIT IS
 TAKEN ON THE ENERGY CALCULATIONS.
  
 2-GARAGE DOOR PRODUCT APPROVAL: PACKAGE
 SUBMITTED TO THE FLORIDA BUILDING
 COMMISSION FOR APPROVAL WAS AN
 ENGINEER'S REPORT NOT THE DADE COUNTY
 PRODUCT APPROVAL. SUBMIT ENGINEER
 PACKAGE.
  
 3-REVISE SOIL TEST REPORT. THIS IS THE
 CITY OF WEST PALM BEACH, NOT PALM BEACH
 COUNTY. REVISE NAME AND ADDRESS AS
 REQUIRED AND RESUBMIT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-21 Cont ID  
Sent By mmclean Date 2004-10-13 Time 15:58 Rev Time 2.50
Received By jgomez Date 2004-10-21 Time 08:31 Sent To PC
Notes
2004-10-20 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK STAMPED DRAWINGS & RECEIPT.
 2-SH24 EGRESS WINDOWS DON'T MEET THE
 REQUIREMENTS OF SEC. 1005.4.4 FBC 2001
 WHERE NET CLEAR HEIGHT DIMENSION SHALL
 BE 24". ALSO, SEE SEC. 1005.4.1 CITY
 AMENDMENTS FOR ADDITIONAL REQUIREMENTS
 **WINDOW SIZE SHOWN ON ELEVATIONS ARE NO
 TO SCALE ACCORDING TO SIZE CALLED ON
 FLOOR PLANS. REVISE AS REQUIRED.
 3-SPECIFY CONCRETE SLAB JOINTS OR
 SPECIFY WWM SUPPORTS AND SPACING AS
 REQ'D BY SEC. 1909.3 FBC 2001.
 4-SHEET 3/7 FOOTING F08.08(T.E) DOESN'T
 MATCH FOOTING SHOWN ON SCHEDULE.
 5-SHEET 4/7: SPECIFY ATTIC LIVE LOAD
 REQUIRED FOR TRUSSES DESIGN. SEE
 TABLE 1604.1 FBC 2001 (AND SPECIFY
 STORAGE OR NON STORAGE).
 6-CONTRACTOR TO UPDATE LICENSE. SEE
 PERMIT CLERK AT FRONT COUNTER.
 7-OWES $341.31 FOR UPDATED VALUATION.
 PAY ATTACHED RECEIPT.
 8-STORM SHUTTERS:A)INSTALLATION SCHEDULE
 SHOWS ENTRY DOOR BLOCKED WITH STORM
 PANELS. SPECIFY WHICH ONE IS THE MEANS
 OF ESCAPE REQUIRED BY SEC. 1005.4.5
 FBC 2001.
 B)PROVIDE CORRECT FL. PRODUCT APPROVAL
 THAT MATCHES DADE COUNTY REPORT.
 C)REVISE ANCHOR SCHEDULE. SEE APPROVED
 DRAWINGS AND SPECIFY ANCHOR TYPE AND
 SPACING ACCORDING TO THE DESIGN PRE-
 SSURES, EDGE DISTANCE, PANEL SPAN,
 CONNECTION TYPE AND STRUCTURE TO BE
 ATTACHED (CONCRETE BLOCK OR CONCRETE).
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC
 9-IF CEILING FAN CREDIT IS TAKEN ON THE
 ENERGY CALCS, THEN, NEED TO SPECIFY
 FANS SIZES ON PLANS AS PER TABLE 6-6
 OF CHAPTER 13 FBC 2001.
 10-PROVIDE STRUCTURAL BUCK DETAIL FOR
 ENTRY DOOR USING 2X BUCK AS REQUIRED
 BY DOOR PRODUCT APPROVAL.
 11-PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR: A)ENTRY DOOR THAT MATCH
 DOOR SHOWN ON PLANS. PRODUCT APPROVAL
 SUBMITTED IS FOR GLASS DOOR. REVISE
 PLANS AND PRODUCT APPROVAL TO MATCH.
 B)SLIDING GLASS DOORS WITH CORRECT FL.
 PRODUCT APPROVAL NUMBER.
 C)SINGLE HUNG WINDOWS WITH CORRECT FL.
 PRODUCT APPROVAL NUMBER.
 D)STRUCTURAL CONNECTORS SPECIFIED:
 SIMPSON AND USP CONNECTORS.
 E)GARAGE DOOR WITH LEGIBLE DRAWINGS.
  
 12-SHEET 4/7: A)SPECIFY FASTENERS FOR
 2X8 TOP PLATE. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 B)REVISE NUMBER OF FASTENERS SPECIFIED
 FOR SIMPSON SPH8. SEE 2004 SIMPSON
 CATALOGUE.
 **SEE PLANS FOR ADDITIONAL COMMENTS.
  
 13-PROVIDE SOIL TEST REPORT.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-09-15 Cont ID  
Sent By dpalmer Date 2004-09-15 Time 07:16 Rev Time 0.33
Received By dpalmer Date 2004-09-15 Time 07:16 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-06-23 Cont ID  
Sent By adarroug Date 2005-06-23 Time 14:26 Rev Time 0.00
Received By adarroug Date 2005-06-23 Time 14:26 Sent To B
Notes
2005-06-23 00:00:00TO "JGOMEZ" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-05-18 Cont ID  
Sent By adarroug Date 2005-05-18 Time 10:42 Rev Time 0.00
Received By adarroug Date 2005-05-18 Time 10:42 Sent To B
Notes
2005-05-18 00:00:00TO "JGOMEZ" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-02-11 Cont ID  
Sent By adarroug Date 2005-02-11 Time 11:16 Rev Time 0.00
Received By adarroug Date 2005-02-11 Time 11:15 Sent To B
Notes
2005-02-11 00:00:00TO JGOMEZ DESK/REVISON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-11-09 Cont ID  
Sent By csiegber Date 2004-11-09 Time 10:56 Rev Time 0.00
Received By csiegber Date 2004-11-09 Time 10:56 Sent To B
Notes
2004-11-09 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-09-22 Cont ID  
Sent By csiegber Date 2004-09-22 Time 14:52 Rev Time 0.00
Received By csiegber Date 2004-09-22 Time 14:52 Sent To Z
Notes
2004-09-22 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-21 Cont ID  
Sent By mmclean Date 2004-09-01 Time 11:14 Rev Time 0.00
Received By jgomez Date 2004-08-30 Time 14:26 Sent To PC
Notes
2004-09-14 00:00:00TO SFD RACK/E
2004-08-30 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-09-20 Cont ID  
Sent By dpalmer Date 2004-09-20 Time 07:16 Rev Time 0.30
Received By pkrauss Date 2004-09-20 Time 07:04 Sent To B
Notes
2004-09-20 00:00:00PROVISO:
 1.14" R/A JUMPER FROM THE MASTER
 BEDROOM SHALL COMPLY WITH 2001 FBC(M)
 601.4 EXCEPTION #1 & 3.
  
 2.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-09-15 Cont ID  
Sent By jleech Date 2004-09-15 Time 19:35 Rev Time 0.33
Received By jleech Date 2004-09-15 Time 19:35 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-10-13 Cont ID  
Sent By mmclean Date 2004-10-13 Time 15:58 Rev Time 0.00
Received By mmclean Date 2004-10-13 Time 15:58 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-09-01 Cont ID  
Sent By csiegber Date 2004-09-22 Time 14:52 Rev Time 0.00
Received By mmclean Date 2004-09-01 Time 11:12 Sent To I
Notes
2004-09-01 00:00:00DENIED, REAR SETBACK IS SCALE TO 15FT &
 SURVEY SHOWS 20FT.NEED TO PROVIDE
 SURVEY WITH CORRECT SETBACK.CALLED
 CONTR, LEFT MSG MM


Account Summary | Usage Policy | Privacy Policy