Plan Review Details - Permit 04081182
Plan Review Stops For Permit 04081182
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-02-16 Cont ID  
Sent By mjacobs Date 2005-02-16 Time 10:43 Rev Time 2.00
Received By mjacobs Date 2005-02-16 Time 10:43 Sent To PC
Notes
2005-02-16 00:00:00I SPOKE WITH MR. WINSTON BROWN AND HE
 INFORMED ME THAT HE WILL TERMINATE THE
 PERMIT APPLICATION.2-16-05 MJACOBS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-31 Cont ID  
Sent By csiegber Date 2004-08-24 Time 16:43 Rev Time 2.50
Received By pschmitz Date 2004-08-31 Time 14:34 Sent To Z
Notes
2004-08-31 00:00:00BUILDING PLAN REVIEW
 PERMIT:04081182
 ADD:1911 N TAMARIND AVE
 CONT:WINSTON BROWN
 TEL: (954)485-6901
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) ONLY THE ARCHITECT OR DESIGN
 PROFESSIONAL WHO HAS SIGN AND SEAL THE
 PLANS ARE ALLOWED TO MAKE CHANGES ON THE
 PLANS. SEE RED CIRCLE ON PLANS.
  
 3) FBC.104.2.1. ADDITIONAL INFORMATION
 REQUIRED, ON THE NEW 3'-6" OVERHANG
 SHOW ATTATCHMENT DETALIS AND PROVIDE
 PRODUCT APPROVALS FOR ALL COMPONENTS
 WHICH WILL BE USED.
  
 4) FBC.104.2.4 SITE DRAWWINGS. SHOW THE
 LOCATION OF THE PROPOSED BUILDING OR STR
 UCTURE AND OF EVERY EXISTION BUILDING
 OR STRUCTURE ON THE SITE OR LOT.
  
 5) PLEASE SHOW DOOR HEADER DETAILS OR
 PLANS. WINDOW DETAILS NEEDS TO SHOW
 NAILING OR STRAPPING SCHEDULE.
  
 6)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 7)2001 FL BLD CODE, 1005.4:
 PROVIDE EMERGENCY EGRESS WINDOWS IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGTH OF 24" AND NET CLEAR
 OPENING WIDTH OF 20" AND A NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH
 SHALL NOT BE MORE THAN 44 " ABOVE THE
 FINISH FLOOR.
  
 8 ) FBC 2405.2THE FOLLOWING GLAZING IS
 IN A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201):
 LOCATION OF GLAZING?
 SUBMIT DETAILS TO DEMONSTRATE COMPLIANCE
 WITH BATHROOM WINDOWS
  
 9) PRODUCT APPROVALS ARE REQUIRED FOR
 DOORS,WINDOWS,SIMPSON TIES AND SHUTTERS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10)2304.3.4 WOOD JOIST SHALL HAVE 18"
 CLEARENCE FROM THE BOTTOM OF JOIST TO
 EARTH OR ELSE BE PRESSURE TREATED WOOD
  
 11) THE PLANS INDICATE CONCRETE BLOCK
 STRUCTURE,BUT EXTERIOR WALL DETAILS
 SHOWS WIRE LATH AND STUCCO.IS THERE AN
 ADDITION ON THIS BUILDING? IF SO PLEASE
 SHOW IN DETAILS ON DRAWINGS.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 MYRON JACOBS
 BUILDING PLAN REVIEW
 TEL: (561)805-6726
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-02-03 Cont ID  
Sent By dpalmer Date 2005-02-03 Time 08:35 Rev Time 0.30
Received By dpalmer Date 2005-02-03 Time 08:25 Sent To Z
Notes
2005-02-03 00:00:00REDLINED NOTES.
  
 CIRCUITING FOR #21,#28 TO BE ARC FAULT.
  
 RECEPT SPACING FOR KIT COUNTERSPACE PER
  
 210.52C1

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-09-15 Cont ID  
Sent By mmclean Date 2004-09-14 Time 11:54 Rev Time 0.50
Received By dpalmer Date 2004-09-15 Time 12:47 Sent To P
Notes
2004-09-15 00:00:00******** UNSAT *******
  
 1)NOTE: PLEASE SEE TITLE BLOCK FOR ENGI-
 -NEER REQUIRED TO HAVE PRINTED LICENSE
 #. 61G15-23.002
 PLEASE ALSO SEE FS 471.023, A LEGAL
 SIGNATURE IS REQUIRED. APPEARS TO BE
 INITIALS??
  
 2)NOTE: PLEASE SEE TITLE BLOCK FOR
 DESIGN AND ASSC'S. FS 481.219, 61G1-16.-
 -.004. PLEASE INCLUDE ALL LICENSE INFOR-
 -MATION.
  
 3)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4.1.6.2
  
 4)NOTE: PLEASE CORRRLELATE SIZE OF HEAT/
 KW WITH MECHANICAL SPECS. PLEASE ALSO
 SEE 424.3B FOR REQUIRED MIN OCP OF 125%.
  
 5 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 NEC 210.12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-11 Cont ID  
Sent By adarroug Date 2005-02-11 Time 15:50 Rev Time 0.00
Received By adarroug Date 2005-02-11 Time 15:50 Sent To P
Notes
2005-02-11 00:00:00TO "P"BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-31 Cont ID  
Sent By mjacobs Date 2005-01-31 Time 15:57 Rev Time 0.00
Received By mjacobs Date 2005-01-31 Time 15:57 Sent To E
Notes
2005-01-31 00:00:00TO "DP" DESK/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-24 Cont ID  
Sent By csiegber Date 2004-08-24 Time 16:43 Rev Time 0.00
Received By csiegber Date 2004-08-24 Time 16:43 Sent To B
Notes
2004-08-24 00:00:00TO MISC BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-09-20 Cont ID  
Sent By jleech Date 2004-09-16 Time 18:09 Rev Time 0.35
Received By pkrauss Date 2004-09-20 Time 14:38 Sent To  
Notes
2004-09-20 00:00:00DENIED:
 PER FS 471.025 AND THE FAC 61G15-23.002,
 LICENSE NUMBER SHALL BE INCLUDED ON THE
 TITLE BLOCK AND PLANS ARE TO SIGNED NOT
 INITIALED BY THE ENGINEER.SEE ALSO
 COMMENT #2 BY BUILDING PLAN REVIEW.
  
 RETURN AIR JUMPERS ARE NOT SIZED
 PROPERLY.PER 2001 FBC(M) 601.4
 EXCEPTION #1, RETURN AIR JUMPERS SHALL
 BE 1 1/2 TIMES THE SQUARE INCHES OF THE
 SUPPLY.ALL AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED PER #3 OF 601.4.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE PER
 2001 FBC 1503.4.4.
  
 AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-02-15 Cont ID  
Sent By pschmitz Date 2005-02-12 Time 08:21 Rev Time 0.00
Received By pschmitz Date 2005-02-15 Time 14:28 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-09-16 Cont ID  
Sent By dpalmer Date 2004-09-15 Time 12:47 Rev Time 0.75
Received By jleech Date 2004-09-16 Time 18:09 Sent To M
Notes
2004-09-16 00:00:00DENIED;
 1.SEE ELECTRICAL PLAN REVIEW'S NOTES
 1 AND 2.
 2.MINIMUM SIZE OF SEWER IS 3" NOT 2".
 3.KITCHEN SINK TO DISCHARGE DOWN STREAM
 OF BATHROOM GROUP. SEC 909.1.
 4.DRAIN KITCHEN AND BATHROOM BRANCH
 DRAINS DOWN STREAM OF TUB.
 5.PLUMBING NOTE #3 SHOWER VALVE TO BE
 ANTI SCALD NOT SHOWER HEAD.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2005-02-11 Cont ID  
Sent By mmclean Date 2005-02-11 Time 13:55 Rev Time 0.00
Received By mmclean Date 2005-02-10 Time 09:24 Sent To  
Notes
2005-02-15 00:00:002/15/05 RETURNED PLANS TO MYRON J.
 STAMPED THE SECOND PLANS.
2005-02-11 00:00:00LEFT THE OTHER PLANS ON 5TH FLOOR
 SHIRLEY'S DECK.SHIRLEY WILL STAMP AND
 BRING DOWN OTHER PLAN
2005-02-10 00:00:00SHIRLEY WILL BE GOING OUT TO LOOK AT
 PROPERTY REGARDING THE OVERHANG IN FRONT
 PROPERTY

Review Stop Z ZONING
Rev No 1 Status F Date 2004-08-31 Cont ID  
Sent By mjacobs Date 2004-08-31 Time 16:22 Rev Time 0.00
Received By mmclean Date 2004-08-31 Time 11:54 Sent To E
Notes
2004-09-14 00:00:00NEED TO BE SPECIFIC ON WHAT IS BEEN
 BUILT.DRAWINGS SHOWS 3FT 6IN OVERHANG
 AND NEED VERIFICATION.CALLED CONT TO
 COME IN AND MEET WITH MYSELF AND MYRON