Plan Review Details - Permit 04080987
Plan Review Stops For Permit 04080987
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2005-01-19 Cont ID  
Sent By rbrown Date 2005-01-19 Time 15:44 Rev Time 0.00
Received By rbrown Date 2005-01-19 Time 15:44 Sent To  
Notes
2005-01-19 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 REVISED PLANS ORIGINALLY SUBMITTED
 12/7/04 AND RE-SUBMITTED 1/18/05.
  
 --PROVISO--
 SHEETS LS-1 AND A1-2 REDLINED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2004-12-20 Cont ID  
Sent By rregueir Date 2005-06-02 Time 15:03 Rev Time 0.00
Received By rbrown Date 2004-12-20 Time 11:39 Sent To  
Notes
2004-12-20 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 REVISED PLANS SUBMITTED 12/7/04.
  
 1) FBC 1006.2.4PROTECTION OF EXTERIOR
 EXIT STAIR.SEE SHEET LS-1 FOR REDLINED
 COMMENT.AMEND THE PLAN TO INCORPORATE
 THE NOTE BEFORE RESUBMITTAL.
  
 2) FBC* 11-4.3.2(1)ACCESSIBLE ROUTE
 TO BUILDING ENTRANCE.SHEET A1-1, THE
 ACCESSIBLE CAR PARKING AND
 ACCESSIBILITY
 RAMPS HAVE BEEN REVISED, AMEND THE
 PLANS
 TO SHOW THE ACCESSIBLE ROUTE FROM
 PARKING TO THE ENTRY LOBBY (MAIN
 ENTRANCE).
  
 3) FBC* F102.2.8SHEETS A1-2, A2-1,
 A4-3 AND A4-4 ALL REFER TO A FABRIC
 AWNING OVER THE ENTRANCE.PERMANENT
 CANOPIES/ AWNINGS AND THEIR SUPPORTS,
 ON BUILDINGS LOCATED IN THE FIRE
 DISTRICT, SHALL BE OF NON-COMBUSTIBLE
 MATERIAL, FIRE RETARDANT TREATED WOOD,
 WOOD OF TYPE III SIZES OR OF 1-HOUR
 RESISTANT CONSTRUCTION.ANNOTATE THE
 PLANS TO DEMONSTRATE COMPLIANCE.
  
 4) FBC 1608.2.2THE GUARDRAIL STRENGTH
 NOTE HAS BEEN REMOVED FROM SHEETS A4-3
 AND A4-4.THERE ARE STILL TWO
 GUARDRAILS SHOWN ON SECTION 01/A5-1 AND
 WEST ELEVATION 01/A4-4 (ALSO SHOWN ON
 SECOND FLOOR PLAN - SHEET A1-2).THE
 GUARDRAILS SHALL BE DESIGNED AND
 CONSTRUCTED FOR A CONCENTRATED LOAD OF
 200 LB APPLIED IN ANY DIRECTION AT THE
 TOP OF THE GUARDRAIL, A CONCENTRATED
 HORIZONTAL LOAD OF 200 LB APPLIED ON A
 1
 SQ FT AREA AT ANY POINT, AND A LINE
 LOAD OF 50 PLF APPLIED HORIZONTALLY AT
 THE REQUIRED GUARDRAIL HEIGHT WITH A
 SIMULTANEOUS LINE LOAD OF 100 PLF
 APPLIED VERTICALLY DOWNWARD ON THE TOP
 OF THE GUARDRAIL. THESE LOADS SHALL NOT
 BE APPLIED SIMULTANEOUSLY (UNLESS NOTED
 ABOVE) BUT SHALL BE APPLIED
 INDIVIDUALLY
 TO PRODUCE MAXIMUM STRESS IN EACH OF
 THE COMPONENTS OR SUPPORTS.
 AMEND/ANNOTATE THE PLANS TO SPECIFY
 THESE DESIGN LOADS.
 ALSO, THE ELEVATOR 'BRIDGE' GUARDRAIL
 HEIGHT REQUIREMENT OF 42" SHALL BE
 ANNOTATED ON THE PLANS.
  
 5) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE
 RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
  
  
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-12-08 Cont ID  
Sent By rbrown Date 2004-12-08 Time 14:33 Rev Time 0.00
Received By rbrown Date 2004-12-08 Time 14:33 Sent To  
Notes
2004-12-08 00:00:00STRUCTURAL SUBMITTAL ON 12/7/04 FOR
 SKETCH CLARIFICATION ON PARAPET WALL
 DETAIL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-12-08 Cont ID  
Sent By rbrown Date 2004-12-08 Time 14:33 Rev Time 0.00
Received By rbrown Date 2004-12-08 Time 14:33 Sent To  
Notes
2004-12-08 00:00:00STRUCTURAL SUBMITTAL ON 12/7/04 FOR
 SKETCH CLARIFICATION ON MACHINE ROOM TIE
 BEAM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-12-08 Cont ID  
Sent By rbrown Date 2004-12-08 Time 14:33 Rev Time 0.00
Received By rbrown Date 2004-12-08 Time 14:33 Sent To  
Notes
2004-12-08 00:00:00STRUCTURAL SUBMITTAL ON 12/7/04 FOR
 SKETCH CLARIFICATION ON MACHINE ROOM
 FOOTING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-10-05 Cont ID  
Sent By rbrown Date 2004-10-05 Time 17:33 Rev Time 0.00
Received By rbrown Date 2004-10-05 Time 17:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-09-15 Cont ID  
Sent By rbrown Date 2004-09-15 Time 17:56 Rev Time 0.00
Received By rbrown Date 2004-09-15 Time 17:56 Sent To  
Notes
2004-09-15 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC 1006.2.4SHEET LS-1,PROTECTION
 OF EXTERIOR EXIT STAIRS.THE ONE-HOUR
 FIRE RATED WALL SHOWN ON THE FIRST AND
 SECOND FLOOR LIFE SAFETY PLANS SHALL BE
 EXTENDED TO COVER AN AREA THAT EXTENDS
 10 FEET BEYOND THE EDGE OF THE LANDING.
 ALTERNATIVEY, THE PAINTED METAL WALL
 PANEL ASSEMBLY (SHEET A1-2, KEY NOTE 10)
 SHALL BE FIRE-RATED.AMEND THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 2) FBC 1015.4SHEET A4-4.THE 'TYPICAL
 NOTE' COVERING STRENGTH OF GUARDRAILS
 SHALL ALSO APPLY TO THE METAL WALL PANEL
 (KEY NOTE ITEM 9).AMEND THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 3) FBC 2405.2THE GLAZED PANELS
 ADJACENT DOORS 101 AND 110 ARE IN A
 'HAZARDOUS LOCATION' AND ARE REQUIRED TO
 BE SAFETY GLASS SATISFYING THE
 REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 4) FBC* F102.2.7SHEET A4-3, FOAM
 MOULDING (KEY NOTE 21).ARCHITECTURAL
 TRIM ON BUILDINGS LOCATED IN THE FIRE
 DISTRICT, SHALL BE CONSTRUCTED OF
 APPROVED NON-COMBUSTIBLE MATERIALS OR
 FIRE RETARDANT TREATED WOOD.ANNOTATE
 THE PLANS TO DEMONSTRATE COMPLIANCE.
  
 5) SUBMIT A PRODUCT APPROVAL FOR THE
 MODIFIED BITUMEN ROOFING SYSTEM
 REFERENCED ON SHEET A2-1, ROOF PLAN.
 ALSO, (FBC* F102.2.4) ROOF COVERINGS ON
 BUILDINGS LOCATED IN THE FIRE DISTRICT,
 SHALL CONFORM TO THE REQUIREMENTS OF
 CLASS A OR B ROOF COVERINGS, AS DEFINED
 IN FBC 1505.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 6) SUBMIT PRODUCT APPROVALS FOR THE NEW
 WINDOWS AND GLASS BLOCK AND FOR EXTERIOR
 DOORS 101, 105, 106 AND 207.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
  
 7) PRODUCT APPROVAL.RULE 9B-72 FAC.
 FOR PRODUCTS WHICH DO NOT HAVE STATEWIDE
 PRODUCT APPROVAL, LOCAL PRODUCT APPROVAL
 CAN BE ACHIEVED IF THERE IS A QUALITY
 ASSURANCE PROGRAM IN PLACE WITH A STATE
 APPROVED QUALITY ASSURANCE ENTITY.IF
 NEITHER IS APPLICABLE, THEN SITE
 SPECIFIC APPROVAL IS REQUIRED.LOCAL
 PRODUCT APPROVAL WILL ALLOW A PRODUCT TO
 BE USED, IN ACCORDANCE WITH THE TEST
 CRITERIA, THROUGHOUT THE JURISDICTION OF
 WEST PALM BEACH.SITE SPECIFIC PRODUCT
 APPROVAL WILL ALLOW A PRODUCT TO BE
 USED ONLY ON THE PROJECT FOR WHICH THAT
 SITE SPECIFIC APPROVAL IS GRANTED.
 LOCAL AND SITE SPECIFIC PRODUCT APPROVAL
 APPLICATION FORMS ARE AVAILABLE FROM
 THIS OFFICE.APPROVED QUALITY ASSURANCE
 ENTITIES ARE LISTED ON THE DCA WEBSITE:
 WWW.FLORIDABUILDING.ORG/COMMON/C_ORG_
 REGI_SRCH.ASP
  
 8) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-01-20 Cont ID  
Sent By dpalmer Date 2005-01-20 Time 10:26 Rev Time 0.25
Received By dpalmer Date 2005-01-20 Time 10:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-01-19 Cont ID  
Sent By dpalmer Date 2005-01-19 Time 17:16 Rev Time 0.30
Received By dpalmer Date 2005-01-19 Time 17:16 Sent To  
Notes
2005-01-19 00:00:00*********** UNSAT *************
  
 1)NOTE: PLEASE SEE SHEET E0.0 IN SECOND
 SET IS A PHOTOCOPY OF SIGNED AND SEALED
 PLANS.
 MUST BE ORIG SIGNED AND SEALED FOR
 SECOND SET. FS 471.023
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-12-21 Cont ID  
Sent By dpalmer Date 2004-12-21 Time 13:34 Rev Time 0.50
Received By dpalmer Date 2004-12-21 Time 13:34 Sent To  
Notes
2004-12-21 00:00:00*********** UNSAT ***************
  
 PLEASE SEE NOTES FROM PREVIOUS TWO
 REVIEWS.
  
 1)NOTE: PLEASE SEE ELEVATOR DISC IS
 STILL BEING SHOWN AS 100A WITH A 150A
 FEED.??
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-10-06 Cont ID  
Sent By dpalmer Date 2004-10-06 Time 15:43 Rev Time 1.00
Received By dpalmer Date 2004-10-06 Time 15:43 Sent To  
Notes
2004-10-06 00:00:00********PROVISO/REVISION *************
  
 1)NOTE: PLEASE SEE ELEVATOR DISCONNECT
 IS STILL SHOWN AS 100A W/ A 150A FEED.
 THIS DISCONNECT MUST BE RATED AT 150A'S
 AND MAY HAVE THE 100A FUSES AS NOTED.
 THIS HAS BEEN REDLINED ON PLANS.
 PLEASE REVISE BEFORE ROUGH ELECTRICAL
 INSPECTION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-27 Cont ID  
Sent By dpalmer Date 2004-08-27 Time 14:42 Rev Time 1.00
Received By dpalmer Date 2004-08-27 Time 14:42 Sent To  
Notes
2004-08-27 00:00:00******** UNSAT ********
  
 1)NOTE: PLEASE PROVIDE WIND LOADING FOR
 LT POLE TO FBC 140.
 THIS INFORMATION SHOULD BE REFERENCED ON
 ELECTRICAL PLANS AND/OR STRUCTUAL/ARCH
 SHEETS.
  
 2)NOTE: PLEASE SEE 700.16 FOR ELECTRICAL
 /ELEVATOR MACHINE RM.
  
 3 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 4)NOTE: PLEASE SEE ELEVATOR MAIN DISC
 IS SHOWNAS 100A'S AND YET SEEMS TO BEING
 FED W/ 150A BRKR?
 PLEASE VERIFY AND CORRELATE.
 215.5
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT ONLY NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2004-12-20 Cont ID  
Sent By mamini Date 2004-12-20 Time 13:39 Rev Time 0.50
Received By mamini Date 2004-12-20 Time 13:39 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-08-23 Cont ID  
Sent By mamini Date 2004-08-23 Time 13:34 Rev Time 1.00
Received By mamini Date 2004-08-23 Time 13:34 Sent To  
Notes
2004-08-23 00:00:00PASSED WITH PROVISOS:
 1. ANY WORK WITHIN PUBLIC R.O.W WILL
 REQUIRE A SEPARATE PERMIT FROM PUBLIC
 UTILITIES AND ENGINEERING; 949-1086
 WINDELL PALMER.
 2. APPROACHES (TURN OUTS) MUST BE
 CONSTRUCTED PER CITY OF WEST PALM BEACH'
 STANDARD AND REQUIREMENTS.
 3. ANY NEW CONNECTION TO CITY SERVICES
 MUST BE APPROVED BY THE PUBLIC UTILITIES
 AND ENGINEERING; 949-1085 MANNY GONZALEZ
 4. POLLUTION/ EROSION PLANS MUST BE
 INSTALLED PRIOR TO ANY CONSTRUCTION AND
 MAINTAINED DURING.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-12-21 Cont ID  
Sent By mcarsill Date 2004-12-21 Time 12:53 Rev Time 0.00
Received By mcarsill Date 2004-12-21 Time 12:53 Sent To  
Notes
2004-12-21 00:00:001. ENSURE THAT EMERGENCY LIGHTING
 IS AVAILABLE TO DIRECT PERSONS
 DOWN SECOND FLOOR STAIRS.
  
 2. ENSURE BUILDING ADDRESS IS MOUNTED
 ON PROPER ELEVATION. A MINIMUM OF
 6" NUMBERS REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-10-08 Cont ID  
Sent By lmartine Date 2004-10-08 Time 13:41 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2004-10-08 00:00:00PLANS WERE REVIEWED WITH MIKE CARSILLO
 ON CONFERENCE CALL LM

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-09-01 Cont ID  
Sent By nmccray Date 2004-09-01 Time 11:41 Rev Time 0.00
Received By nmccray Date 2004-09-01 Time 11:41 Sent To  
Notes
2004-09-01 00:00:00**********DENIED************************
  
 1) EXTERIOR STAIRS ALL OPENINGS WITHIN
 10 FEET SHALL BE 1 HOUR FIRE RATED. ON
 SHEET LS-1 SHOWS OPENINGS WITHIN 10 FEET
 TO THE RIGHT APPEARS NOT TO BE 1 HOUR
 FIRE RATED.
  
 2) INTERIOR WALL AND CEILING FINISH
 SHALL COMPLY WITH CH. 38.3.3.2.
  
 3) BUILDING ADDRESS IS REQUIRED.
  
 4) SEPARATE PLANS AND PERMIT APPLICATION
 ARE REQUIRED FOR THE FIRE ALARM SYSTEM.
  
 NATE MCCRAY, CAPTAIN
 835-2910 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-06-02 Cont ID  
Sent By rregueir Date 2005-06-02 Time 15:03 Rev Time 0.00
Received By pkrauss Date 2005-06-02 Time 14:35 Sent To  
Notes
2005-06-02 00:00:00GIVEN TO RON REGUEIRO

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-04-26 Cont ID  
Sent By pkrauss Date 2005-04-26 Time 10:04 Rev Time 0.00
Received By pkrauss Date 2005-04-26 Time 10:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-04-22 Cont ID  
Sent By adarroug Date 2005-04-22 Time 15:08 Rev Time 0.00
Received By adarroug Date 2005-04-22 Time 15:08 Sent To M
Notes
2005-04-22 00:00:00TO "PKRAUSS" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-04-18 Cont ID  
Sent By adarroug Date 2005-04-18 Time 15:47 Rev Time 0.00
Received By adarroug Date   Time   Sent To M
Notes
2005-04-18 00:00:00TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-01-18 Cont ID  
Sent By mjacobs Date 2005-01-18 Time 13:08 Rev Time 0.00
Received By mjacobs Date 2005-01-18 Time 13:08 Sent To  
Notes
2005-01-18 00:00:00TO "COMM BD#33/ REV.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-12-08 Cont ID  
Sent By mjacobs Date 2004-12-08 Time 09:10 Rev Time 0.00
Received By mjacobs Date 2004-12-08 Time 09:10 Sent To  
Notes
2004-12-08 00:00:00SENT TO "COMM BD#9" /REV.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-12-07 Cont ID  
Sent By mjacobs Date 2004-12-07 Time 16:03 Rev Time 0.00
Received By mjacobs Date 2004-12-07 Time 16:03 Sent To B
Notes
2004-12-07 00:00:00SENT TO "RB" DESK./SUBMITTALS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-04 Cont ID  
Sent By csiegber Date 2004-10-04 Time 11:43 Rev Time 0.00
Received By csiegber Date 2004-10-04 Time 11:43 Sent To  
Notes
2004-10-04 00:00:00TO COMM BD#37

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-09-15 Cont ID  
Sent By mmclean Date 2004-08-26 Time 16:08 Rev Time 0.00
Received By rbrown Date 2004-08-20 Time 12:29 Sent To  
Notes
2004-08-20 00:00:00TO COMM BD#62

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2005-06-02 Cont ID  
Sent By rregueir Date 2005-06-02 Time 15:03 Rev Time 0.33
Received By rregueir Date 2005-06-02 Time 15:01 Sent To  
Notes
2005-06-02 00:00:00SUBMITTAL RECEIVED FOR CURB EXTENSIONS
 RAISING ROOFTOP EQUIPMENT.
  
 RONALD J REGUEIRO
 561-805-6734

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2005-04-26 Cont ID  
Sent By pkrauss Date 2005-04-26 Time 10:04 Rev Time 0.35
Received By pkrauss Date 2005-04-26 Time 10:04 Sent To  
Notes
2005-04-26 00:00:00AS-BUILT DRAWINGS

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-04-22 Cont ID  
Sent By pkrauss Date 2005-04-22 Time 16:07 Rev Time 0.40
Received By pkrauss Date 2005-04-22 Time 16:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-04-19 Cont ID  
Sent By pkrauss Date 2005-04-19 Time 09:58 Rev Time 0.55
Received By pkrauss Date 2005-04-19 Time 09:57 Sent To  
Notes
2005-04-19 00:00:00DENIED:
 RETURN AIR FROM ROOM 110 AND 105 ARE NOT
 SIZED IN ACCORDANCE WITH 2001 FBC/M
 601.4 EXCEPTION #1.RETURN TRANSFER
 PLENUMS SHALL BE 1 1/2 TIMES THE SQUARE
 INCHES OF THE SUPPLY AIR INTO THAT
 SPACE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-12-21 Cont ID  
Sent By pkrauss Date 2004-12-21 Time 07:52 Rev Time 2.00
Received By pkrauss Date 2004-12-21 Time 06:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-09-15 Cont ID  
Sent By pkrauss Date 2004-09-15 Time 11:18 Rev Time 1.10
Received By pkrauss Date 2004-09-15 Time 09:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-12-21 Cont ID  
Sent By kstevens Date 2004-12-21 Time 18:13 Rev Time 1.00
Received By kstevens Date 2004-12-21 Time 18:13 Sent To  
Notes
2004-12-21 00:00:00REVISION OK - CHANGED THE CONDENSATE
 PIPING AND LOCATION OF THE DRYWELL -
 REMOVED DRYWELL LOCATIONS

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-10-08 Cont ID  
Sent By kstevens Date 2004-10-08 Time 14:21 Rev Time 1.00
Received By kstevens Date 2004-10-08 Time 14:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-09-01 Cont ID  
Sent By kstevens Date 2004-08-28 Time 15:30 Rev Time 1.00
Received By kstevens Date 2004-08-28 Time 15:30 Sent To  
Notes
2004-08-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHTS A1-1 & A1-2 SUBMIT A DETAIL FOR
 TOILET ROOMS SHOWING COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.19, & 11-4.22 &
 ALL SUBSECTIONS. SHOW MEASUREMENTS TO
 THE CENTER OF THE W/C OFF THE WALL AND
 THE CENTER OF LAV OFF WALL. SEE FIG 28
 FOR THE W/C AND LAV MIN. 15" TO CENTER
 ON CLEAR FLOOR SPACE.
 2) SHTS A1-1 & A1-2 SUBMIT A DETAIL FOR
 DRINKING FOUNTAINS SHOWING COMPLIANCE
 WITH SECTION 11-4.15.
 3) COMMENT ADDRESSED ON PERMIT 04081108
 4) COMMENT ADDRESSED ON PERMIT 04081108
 5) SHT A2-2 DETAILS 04 & 08 SHOW HEIGHT
 AND WIDTH FOR SCUPPERS AND OVERFLOW
 SCUPPERS. SECTION 104.2.1
 6) SHT PO.1 GENERAL SPECIFICATIONS #24,
 AIR CHAMBERS ARE NOT APPROVED. DELETE
 REFERENCE. SECTION 604.9
 7) IN THE REMOVAL OF ANY PARY OF A
 DRAINAGE SYSTEM, DEAD ENDS SHALL BE PRO-
 HIBITED. SECTION 704.5 - ALL CAPPED PIP-
 ES SHALL BE CAPPED WITH A PERMINATE CAP
 8) SHT P2.2 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 THE RISER DIAGRAM. IS WATER HAMMER ARR-
 ESTORS ARE INSTALLED THEY SHALL BE LOCA-
 TED NEAR THE FIXTURE IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING. PDI-WH 201.
 9) SHT P3.1 TANKLESS WATER HEATERS SHALL
 BE LISTED. SUBMIT MANUF. SPECIFICATIONS
 SECTION 303.4
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-08-26 Cont ID  
Sent By mmclean Date 2004-08-26 Time 16:08 Rev Time 0.00
Received By mmclean Date 2004-08-26 Time 16:07 Sent To  
Notes
2004-08-26 00:00:00APPROVED BY SHIRLEY GRAHAM, PLANNER
 822-1458 MM