Plan Review Details - Permit 04080979
Plan Review Stops For Permit 04080979
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-10-13 Cont ID  
Sent By jwitmer Date 2004-10-07 Time 14:58 Rev Time 0.55
Received By jwitmer Date 2004-10-07 Time 14:58 Sent To  
Notes
2004-10-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04080979
 ADD: 1900 CONSULETE PLACE
 CONT: E W KELSON BUILDERS
 TEL: (561)399-2241
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1)PLANS ARE CODE COMPLIANT, BUT WITH THE
 DOLLAR AMOUNT FL SATE STAT,481.229(1)
 DESIGN PROFESSIONAL REQUIRED ON ANY
 COMMERCIAL WORK OVER $25,000.00.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-24 Cont ID  
Sent By jwitmer Date 2004-08-24 Time 15:14 Rev Time 1.11
Received By jwitmer Date 2004-08-24 Time 15:14 Sent To  
Notes
2004-08-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04080979
 ADD: 1900 CONSULATE PLACE
 CONT: E. W. KELSON BUILDERS INC
 TEL: (561)399-2241
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) ALL INFORMATION, DRAWINGS, SPECIF-
 ICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 CITY AMENDMENTS 104.2.1
  
 2) VALUE OF PROJECT IS TO LOW SUBMIT
 CORRECT VALUE OR WE WILL CALCULATE THE
 VALUE FROM MARSHALL SWIFT WITH FLORIDA
 MULTIPLIERS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-09-20 Cont ID  
Sent By csiegber Date 2004-09-20 Time 16:13 Rev Time 0.00
Received By csiegber Date 2004-09-20 Time 16:13 Sent To  
Notes
2004-09-20 00:00:00TO COMM BD#50

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-09-17 Cont ID  
Sent By kstevens Date 2004-09-17 Time 10:26 Rev Time 0.00
Received By kstevens Date 2004-08-20 Time 12:18 Sent To  
Notes
2004-08-20 00:00:00TO COMM BD#9

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-10-09 Cont ID  
Sent By kstevens Date 2004-10-09 Time 12:49 Rev Time 0.25
Received By kstevens Date 2004-10-09 Time 12:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-09-17 Cont ID  
Sent By kstevens Date 2004-09-17 Time 10:13 Rev Time 1.00
Received By kstevens Date 2004-09-17 Time 10:13 Sent To  
Notes
2004-09-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA STATUTES
  
 1) DESIGN PROFESSIONAL REQUIRED ON ANY
 COMMERCIAL WORK OVER $25,000.00. SEE
 FS 481.229(1)(C)
 2) NEW SHOWER IN THE LOCATION OF THE TUB
 SHALL REQUIRE A 2" TRAP PER TABLE 709.1
 3) WHEN REMOVING FIXTURES FROM THE SANT.
 SYSTEM, DEAD ENDS ARE NOT ALLOWED.
 SECTION 704.5
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]