Plan Review Details - Permit 04080846
Plan Review Stops For Permit 04080846
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-01-28 Cont ID  
Sent By rmcdouga Date 2005-01-28 Time 16:39 Rev Time 0.00
Received By rmcdouga Date 2005-01-28 Time 16:39 Sent To  
Notes
2005-01-28 00:00:00SUBMITTED CORRECTED KEY PLAN FOR STORM
 PANELS IS OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2004-12-10 Cont ID  
Sent By rmcdouga Date 2004-12-10 Time 08:06 Rev Time 0.00
Received By rmcdouga Date 2004-12-10 Time 07:09 Sent To  
Notes
2004-12-10 00:00:00PROVISO ITEMS WERE SUBMITTED.
  
 1) THE REVISED SIZE OF THE GAS BBQ ON
 SHEET 8 IS OK
  
 2) THE REVISED KEY PLAN FOR THE STORM
 PANELS IS NOT CORRECT. IT DOES NOT MATCH
 THE STRUCTURE. SUBMIT TWO COPIES OF A
 CORRECT KEY PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-11-04 Cont ID  
Sent By rmcdouga Date 2004-11-04 Time 09:57 Rev Time 0.00
Received By rmcdouga Date 2004-11-04 Time 10:21 Sent To  
Notes
2004-11-04 00:00:00BUILDING PROVISO
  
 1) SUBMIT REVISED SHEET 8 SHOWING A 36"
 WIDE GAS GRILL AS INDICATED BY THE
 PRODUCT APPROVAL SUBMITTAL.
  
 2) SUBMIT A REVISED KEY PLAN FOR THE
 STORM PANELS WHICH REFLECTS THE FOOT
 PRINT OF THE STRUCTURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-15 Cont ID  
Sent By csiegber Date 2004-10-25 Time 13:36 Rev Time 0.00
Received By rmcdouga Date 2004-10-15 Time 16:11 Sent To  
Notes
2004-10-15 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SUBMIT UL LISTING INFORMATION AND
 MANUFACTURER'S SPECIFICATIONS FOR THE
 BUILT IN GAS GRILL. SHEET 8 OF THE PLANS
 SPECIFY A 27" GRILL. THE INFORMATION
 SUBMITTED IS FOR A 36" GRILL.
  
 3) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. THE
 DRAWINGS FOR THE STORM PANELS ARE FOR
 ROBICO AND DO NOT BELONG WITH THE ALL
 AMERICAN SHUTTER PRODUCT APPROVALS AND
 STATE FL #393.
  
 4) SUBMIT PRODUCT APPROVALS FOR THE 16'
 WIDE GARAGE DOOR. THE ONES SUBMITTED ARE
 FOR A MAXIMUM WIDTH OF 9'.
  
 5) THE PRODUCT APPROVALS FOR THE SLIDING
 GLASS DOORS AND THE SINGLE HUNG WINDOWS
 ARE FOR NON-IMPACT RATED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-08-01 Cont ID  
Sent By dpalmer Date 2005-08-01 Time 19:54 Rev Time 0.25
Received By dpalmer Date 2005-08-01 Time 19:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-07-21 Cont ID  
Sent By dpalmer Date 2005-07-21 Time 13:41 Rev Time 0.33
Received By dpalmer Date 2005-07-21 Time 13:37 Sent To  
Notes
2005-07-21 00:00:00******* UNSAT ********
  
 1)NOTE: PLEASE SEE PLANS DO NOT INDICATE
 PANEL "B".
 PLEASE SEE GROUPING OF MAINS PER 230.72
 PLEASE SHOW 215.5
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM PANEL "B" TO
 PANEL "C".
 215.5,250.110,.250.24,250.122
  
 3)NOTE: PLEASE SEE LOAD CALCULATIONS
 INDICATE 2-OVENS ON PANEL "A", HOWEVER
 PANEL "A" DOES NOT SHOW THIS??
 PLEASE CLARIFY AND CORRELATE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-08-23 Cont ID  
Sent By dpalmer Date 2004-08-23 Time 15:44 Rev Time 0.50
Received By dpalmer Date 2004-08-23 Time 15:44 Sent To M
Notes
2004-08-23 00:00:00REDLINED RECEPTS PER 210.52

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-07-29 Cont ID  
Sent By adarroug Date 2005-07-29 Time 15:24 Rev Time 0.00
Received By adarroug Date 2005-07-29 Time 15:24 Sent To E
Notes
2005-07-29 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-20 Cont ID  
Sent By adarroug Date 2005-07-20 Time 14:12 Rev Time 0.00
Received By adarroug Date 2005-07-20 Time 14:12 Sent To E
Notes
2005-07-20 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-01-28 Cont ID  
Sent By mjacobs Date 2005-01-28 Time 14:10 Rev Time 0.00
Received By mjacobs Date 2005-01-28 Time 14:10 Sent To B
Notes
2005-01-28 00:00:00TO "ROB MCD" DESK/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-12-09 Cont ID  
Sent By mjacobs Date 2004-12-09 Time 09:58 Rev Time 0.00
Received By mjacobs Date 2004-12-09 Time 09:58 Sent To B
Notes
2004-12-09 00:00:00SENT TO "ROB MCD" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-25 Cont ID  
Sent By csiegber Date 2004-10-25 Time 13:36 Rev Time 0.00
Received By csiegber Date 2004-10-25 Time 13:36 Sent To B
Notes
2004-10-25 00:00:00TO RM DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-15 Cont ID  
Sent By mmclean Date 2004-08-20 Time 15:25 Rev Time 0.00
Received By rmcdouga Date 2004-08-19 Time 10:44 Sent To  
Notes
2004-08-20 00:00:00TO SFD RACK/E
2004-08-19 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-08-28 Cont ID  
Sent By dpalmer Date 2004-08-23 Time 15:44 Rev Time 0.35
Received By pkrauss Date 2004-08-28 Time 06:20 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-08-28 Cont ID  
Sent By pkrauss Date 2004-08-28 Time 06:20 Rev Time 0.25
Received By jleech Date 2004-08-28 Time 11:14 Sent To B
Notes
2004-08-28 00:00:00NO RISER DIAGRAM. NOT ENOUGH INFORMATION
 TO DO A PLUMBING PLAN REVIEW.

Review Stop Z ZONING
Rev No 1 Status P Date 2004-08-20 Cont ID  
Sent By mmclean Date 2004-08-20 Time 15:25 Rev Time 0.00
Received By mmclean Date 2004-08-20 Time 15:25 Sent To I
Notes
***NONE***