2005-02-04 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)THE PLANS FOR THE STRUCTURE APPEAR | | TO CONFLICT WITH THE EXISTING BUILDING. | | TYPE VI IS DECLARED (DWG | | #XP-N-00-02-FL).THE ADDITION IS TO BE | | OF THE SAME BUILDING TYPE AS THE | | EXISTING. | | | | 2.)IS THIS BUILDING SPRINKLED?NOTE | | ON THE PLAN.SPRINKLERS REQUIRED AT | | NEW | | AREAS FOR ADDITIONS TO SPRINKLED | | BUILDINGS.PLEASE NOTE EXISTING | | BUILDING CONDITION ON THE PLAN. | | | | 5.)THE PLAN FOR THE ROOFTOP STRUCTURE | | ALSO DECLARE A BUSINESS OCCUPANCY, THEN | | STATES THAT IT "SHALL NOT BE LOCATED | | WHERE ACCESSIBILITY IS REQUIRED". | | BUSINESS OCCUPANCY REQUIRES | | ACCESSIBILITY.THE PLAN PREPARED BY | | MORRISON HERSCHFIELD INDICATE THAT THIS | | IS UNINHABITABLE.IF THIS STRUCTURE | | HAS | | A BUSINESS OCCUPANCY AS DECLARED, SHOW | | COMPLIANCE WITH FBC CHAPTER 11. | | | | 6.)SHOW OCCUPANCY SEPARATION | | COMPLIANCE (BETWEEN THE EXISTING | | STRUCTURE AND NEW), FBC CHAPTER 7. | | | | 6.)THE PLAN FOR THE ROOFTOP STRUCTURE | | DECLARES HVHZ; CITY OF WEST PALM BEACH | | IS NOT IN THE HVHZ. | | | | 7.)A TITLE BLOCK IS REQUIRED FOR THE | | ENGINEER (PLANS FOR ROOFTOP STRUCTURE). | | IF PRECISION QUINCY CORP IS THE TITLE | | BLOCK FOR THE ENGINEER, A CERTIFICATE | | OF AUTHORIZATION NUMBER IS TO BE ON THE | | PLAN.THE PRINTED NAME AND LICENSE | | NUMBER OF THE PERSON SEALING THE | | DOCUMENT IS TO BE ON THE PLAN. | | FAC61G15-23.002. | | | | 8.)THE TWO SETS OF PLANS PREPARED BY | | MORRISON HERSCHFIELD ARE NOT THE SAME. | | ONE IS DATED 8/27, REVISION 2.THE | | OTHER HAS AN UNDATED SEAL, REVISION 4. | | PLEASE DATE FAC61G1-15, AND SUBMIT TWO | | IDENTICAL SETS. | | | | 9.)A-S3, PROVIDE THE PRESCRIPTIVE | | STRENGTH FOR THE GUARDRAIL COMPLIANT | | WITH FBC1608.2.2(1) THROUGH (4). | | | | 10.) I AM STILL UNABLE TO FIND THE ROOF | | DESIGN PRESSURE ON THE PLAN.SEE THE | | PREVIOUS LISTS, SPECIFICALLY ITEM #2 ON | | PREVIOUS LIST.DPS CANNOT BE SPECIFIED | | BY THE ROOFER. | | | | 11.)SEE THE PREVIOUS LIST, ITEM #7. | | PROVIDE CALCULATIONS FOR THE EXISTING | | ROOF STRUCTURE AND ITS ABILITY TO | | ACCOMODATE THE NEW EQUIPMENT.THE | | CALCULATIONS REFER TO COLUMN CHECK, | | SHEAR WALL CHECK, FOUNDATION CHECK. | | WHAT ABOUT THE ROOF DECK? | | | | 12.)PROVIDE A DATE FOR THE SEAL FOR | | THE CALCS AND THE CERTIFICATE OF | | AUTHORIZATION NUMBER ON THE CALCS. | | SECOND TIME FOR THIS COMMENT; PLEASE | | COMPLY.THIS IS A REQUIREMENT FOR ALL | | DOCUMENTS. | | | | 13.)FS553.80(2)(B), 4X FEE WILL BE | | CHARGED, SEE ATTACHED. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2004-11-05 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2004-11-05 |
Time |
08:07 |
Rev Time |
2.00 |
Received By |
shill |
Date |
2004-11-05 |
Time |
07:28 |
Sent To |
|
|
Notes |
2004-11-05 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURTS BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2.)AS PER DISCUSSION WITH DOR, | | PRODUCT | | APPROVALS FOR THE ROOF CAN BE SUBMITTED | | AT A FUTURE DATE WHEN THE PRODUCT TO BE | | USED IS DETERMINED.HOWEVER, THE | | DESIGN | | PRESSURES CANNOT BE SPECIFIED BY THE | | ROOFER, SEE FBC1606.1.1, | | FBC104.3.1.1(8).ALSO PROVIDE DESIGN | | PRESSURE FOR COMPONENTS AND CLADDING | | FOR | | THE SHELTER. | | | | 3.)SEE THE PREVIOUS LIST #6; A | | RESPONSE WAS PREPARED THAT ITEM #6 WAS | | ADDRESSED BUT I WAS UNABLE TO FIND IT | | ON | | THE PLAN (IN REGARDS TO DESIGN CRITERIA | | FOR THE RAILING). | | | | 4.)IT IS NOT CLEAR AS TO WHETHER ITEM | | #5 FROM THE PREVIOUS LIST WAS | | ADDRESSED. | | PLEASE PROVIDE A DETAIL FOR THE | | ANTENNAS | | TO BE INSTALLED AT THE STAIRWELL. | | | | 5.)THE STRUCTURALS FOR THE SHELTER | | SHOW STEEL FRAMING ONLY.DOES THIS | | STRUCTURE HAVE WALLS, ROOF, ROOF | | COVERING, AND DOORS OR WINDOWS?THE | | ELEVATIONS ON THE ARCHITECTURALS APPEAR | | TO HAVE ALL OF THESE ITEMS; IN CONFLICT | | WITH THE STRUCTURALS. | | | | 6.)IF DOORS, WINDOWS, ROOF ARE BEING | | INSTALLED, SUBMIT TWO COPIES OF PRODUCT | | APPROVALS; TEST OR EVALUATION REPORTS | | (SUCH AS DADE COUNTY NOAS) AND FLORIDA | | STATE PRODUCT APPROVALS.SEE FAC9B-72; | | WWW.FLORIDABUILDING.ORG. | | | | 7.)PLEASE HAVE BRENDAN LARKIN, PE | | CALL | | ME IN REGARDS TO THE STRUCTURAL CALCS. | | IT IS UNCLEAR AS TO WHERE THE CALCS ARE | | FOR THE EXISTING ROOF STRUCTURE AND ITS | | ABILITY TO ACCOMODATE THE NEW | | EQUIPMENT, | | INCLUDING A FACTOR OF SAFETY.CALLED | | 11/05/04, LEFT MESSAGE 954-577-4655. | | | | 8.)PLEASE PROVIDE DATES FOR THE SEALS, | | FAC61G15-23.002, FACG1-16.003,004. | | | | | | ***NOTE - CALLED ANN HOCTOR AND | | REQUESTED THAT DOR CONTACT ME TO GET | | CLARIFICATION.11/05/04*** | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2004-09-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2004-09-21 |
Time |
16:37 |
Rev Time |
2.00 |
Received By |
shill |
Date |
2004-09-21 |
Time |
16:37 |
Sent To |
|
|
Notes |
2004-09-21 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURTS BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2.)THE CA NUMBER FOR MORRISON | | HERSCHFELD IS REQUIRED ON THE CALCS | | FAC61G15-23.002. | | | | 3.)THE CALCS REFER TO THE IBC AS THE | | BUILDING CODE. | | | | 4.)PROVIDE DESIGN PRESSURE REQUIREMENT | | FOR THE ROOF.SUBMIT PRODUCT APPROVAL | | FOR THE MEMBRANE (TEST REPORT AND | | FLORIDA STATE OR LOCAL PRODUCT APPROVAL | | FAC9B72, WWW.FLORIDABUILDING.ORG). | | | | 5.)PENETRATIONS THROUGH THE STAIR | | ENCLOSURE ARE PROHIBITED BY FBC1006.1.3. | | 1. | | | | 6.)RAILING TO COMPLY WITH FBC1608.1.2. | | 1.SPECIFY; DO NOT QUOTE CODE REFERENCE | | NUMBER ONLY. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2005-06-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-06-15 |
Time |
10:54 |
Rev Time |
0.25 |
Received By |
dpalmer |
Date |
2005-06-15 |
Time |
10:54 |
Sent To |
|
|
Notes |
2005-06-15 00:00:00 | ********** UNSAT ********** | | | | 1)NOTE: PLEASE SEE ALL ELECTRICAL | | SUB-PERMITS HAVE BEEN FINALED AND THOSE | | PERMIT HAVE BEEN CLOSED OUT. | | NO REVSIONS ARE TO BE DONE UNLESS NEW | | PERMITS ARE APPLIED FOR. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2005-01-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-01-27 |
Time |
13:31 |
Rev Time |
0.70 |
Received By |
dpalmer |
Date |
2005-01-27 |
Time |
13:30 |
Sent To |
|
|
Notes |
2005-01-27 00:00:00 | NOTES REDLINED | | PER 230.76, 230.79, 110.27 | | REDLINED SIGNAGE REQUIRED. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2004-10-23 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-10-23 |
Time |
10:22 |
Rev Time |
0.33 |
Received By |
dpalmer |
Date |
2004-10-23 |
Time |
10:21 |
Sent To |
|
|
Notes |
2004-10-23 00:00:00 | ******** UNSAT *********** | | | | 1)NOTE: PLEASE SEE 230.72 FOR GROUPING | | OF MAINS. | | RESPONSE LTR MENTIONS "SHUNT TRIP" ADDED | | , THIS IS NOT PERMITTED. PLEASE SEE | | 230.76,230.79 FOR MEANS OF DISCONNECTS | | REQUIRED. | | RESPONSE LTR ALSO MENTIONS TO SEE NOTES: | | 25,26,27 ON E-2? THESE COULD NOT BE | | LOCATED. | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | INSERT NEW SHEETS INTO COMPLETE SETS FOR | | REVIEW AND STAMPING. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2004-08-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-08-30 |
Time |
16:29 |
Rev Time |
0.75 |
Received By |
dpalmer |
Date |
2004-08-30 |
Time |
16:29 |
Sent To |
|
|
Notes |
2004-08-30 00:00:00 | ************* UNSAT ***************** | | | | 1)NOTE:PLEASE SEE BLDG/FIRE COMMENTS | | WITH REGARD TO ROUTING OF CONDUIT/CABLE | | THROUGH FIRE-RATED STAIRS. | | | | 2)NOTE: PLEASE SEE 300.19 FOR SUPPORT OF | | CONDUCTORS. | | | | 3)NOTE: PLEASE VERIFY GROUPING OF MAINS | | PER 230.72 | | | | 4)NOTE: PLEASE SEE BLDG COMMENTS AND | | PROVIDE CONTACT FOR WORK SHOWN IN SCOPE | | OF PERMIT. PLEASE NOTE: VALUE IS BASED | | ON ALL LABOR AND MATERIALS/EQUIPMENT | | ETC, EVEN IF OWNER SUPPLIED. | | FBC 104.6.5 | | | | PLEASE SEE OTHER REVIEWERS NOTES, | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2005-04-06 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2005-04-06 |
Time |
14:00 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2005-04-06 |
Time |
14:00 |
Sent To |
|
|
Notes |
2005-04-06 00:00:00 | 1) ALL PENETRATIONS AND EQUIPMENT THAT | | IS NOT APPROVED IN ACCORDANCE WITH NFPA | | 101, SECTION 7.1.3.2.1 IS PROHIBITED IN | | EXIT ENCLOSURES. | | | | | | MIKE WENNERGREN, A/CAPTAIN | | WPBFR(561) 835-2910 OR 805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
F |
Date |
2005-02-25 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2005-02-25 |
Time |
17:00 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2005-02-25 |
Time |
17:00 |
Sent To |
|
|
Notes |
2005-02-25 00:00:00 | 1. PLEASE EXPLAIN RATIONALE OF TYPE VI | | BUILDING BEING PLANNED ON TOP OF | | A FIRE RESISTIVE POSSIBLY A TYPE | | II STRUCTURE. WHAT ALLOWS THIS TO | | OCCUR. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2004-11-05 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2004-11-05 |
Time |
13:45 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2004-11-05 |
Time |
13:45 |
Sent To |
|
|
Notes |
2004-11-05 00:00:00 | 1) PLEASE INDICATE ON THE PLANS THAT | | NO PENETRATIONS ARE ALLOWED IN ANY | | REQUIRED EXIT STAIRWELL. THE PLANS | | ARE NOT CLEAR WITH REGARDS TO THIS | | MATTER. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2004-09-16 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2004-09-16 |
Time |
13:02 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2004-09-16 |
Time |
13:01 |
Sent To |
|
|
Notes |
2004-09-16 00:00:00 | 1) NO PROPOSED EQUIPMENT CAN ENTER, | | TRAVEL THRU OR TERMINATE WITHIN THE | | REQUIRED EXIT STAIRS FOR THE BUILDING. | | ONLY CERTAIN EQUIPMENT CAN BE CONTAINED | | WITHIN THE BUILDING EXIT STAIRS AND | | CELLULAR EQUIPMENT IS NOT LISTED. | | PLEASE CORRECT PLANS SO NO EQUIPMENT | | OR WIRING ARE LOCATED WITHIN THE | | STAIRS. | | | | 2) PLEASE INDICATE PRESCRIPTIVE STRENGTH | | REQUIREMENTS FOR HANDRAILS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2005-06-07 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2005-06-07 |
Time |
10:46 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2005-06-07 |
Time |
10:46 |
Sent To |
E |
|
Notes |
2005-06-07 00:00:00 | TO 'DP' DESK. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2005-01-24 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2005-01-24 |
Time |
13:24 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2005-01-24 |
Time |
13:24 |
Sent To |
|
|
Notes |
2005-01-24 00:00:00 | TO "COMM BD#48/RESUB. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2004-10-18 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-10-18 |
Time |
15:10 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-10-18 |
Time |
15:10 |
Sent To |
|
|
Notes |
2004-10-18 00:00:00 | TO COMM BD#27 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2004-09-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2004-09-21 |
Time |
16:39 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2004-08-18 |
Time |
15:11 |
Sent To |
|
|
Notes |
2004-08-18 00:00:00 | TO COMM BD#54 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2004-09-16 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-09-16 |
Time |
15:37 |
Rev Time |
0.20 |
Received By |
pkrauss |
Date |
2004-09-16 |
Time |
15:37 |
Sent To |
|
|
Notes |
2004-09-16 00:00:00 | NO MECHANICAL PLANS SUBMITTED OR | | CONTRACTOR INDICATED ON PERMIT | | APPLICATION. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
2005-04-15 |
|
|
Cont ID |
|
Sent By |
rgranber |
Date |
2005-04-15 |
Time |
09:08 |
Rev Time |
0.00 |
Received By |
rgranber |
Date |
2005-04-15 |
Time |
09:08 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2005-02-15 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-02-15 |
Time |
15:10 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-02-15 |
Time |
15:10 |
Sent To |
|
|
Notes |
2005-02-15 00:00:00 | DENIED, | | 1. LANDSCAPE REGULATIONS: ALL PROPERTIES | | SHALL BE BROUGHT INTO COMPLIANCE WITH | | THE LANDSCAPE REGULATIONS PROVIDED | | HEREIN AT SUCH TIME THAT A BUILDING | | PERMIT IS ISSUED FOR WORK VALUE AT | | $5,000 OR MORE.THE PLANNING DIRECTOR | | SHALL HAVE AUTHORITY TO GRANT A | | ONE-TIME, THREE (3) MONTH EXTENSION. | | ANY QUESTIONS, PLEASE FEEL FREE TO | | CONTRACT RANDALL GRANBERRY, PLANNER | | 822-1454 MM | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2004-10-21 |
|
|
Cont ID |
|
Sent By |
rgranber |
Date |
2004-10-21 |
Time |
15:34 |
Rev Time |
0.00 |
Received By |
rgranber |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2004-09-15 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2004-09-15 |
Time |
11:39 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2004-09-15 |
Time |
11:39 |
Sent To |
|
|
Notes |
2004-09-15 00:00:00 | DENIED, PER RANDALL GRANBERRY, PLANNER | | 822-1454.NEED TO PROVIDE INFO FOR AN | | INFORMAL. |
|
|