Plan Review Details - Permit 04080798
Plan Review Stops For Permit 04080798
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-10-25 Cont ID  
Sent By mmclean Date 2004-10-25 Time 16:22 Rev Time 1.00
Received By jgomez Date 2004-10-25 Time 15:53 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-25 Cont ID  
Sent By btrobaug Date 2004-10-25 Time 08:06 Rev Time 1.50
Received By jgomez Date 2004-08-24 Time 16:09 Sent To PC
Notes
2004-08-24 00:00:00CHECKLIST:
 1-BRING DWGS TO PALM BEACH COUNTY TO
 CHECK IF IMPACT FEES ARE DUE OR NOT.
 BRING BACK STAMPED DRAWINGS & RECEIPT.
 2-NEED TO RECORD NOTICE OF COMMENCEMENT.
 3-PROVIDE ENERGY CALCULATIONS. SEE
 ATTACHED. COMPLETE ALL INFORMATION AND
 PREPARER AND OWNER TO SIGN AND DATE
 BOTTOM OF FORM.
 4-DRAWINGS TO SHOW ALL INFORMATION AS
 REQUIRED BY SECTION 1606.1.7 FBC 2001.
 5-DRAWINGS NEED TO SHOW ELECTRICAL WORK.
 SEE COMMENTS BY ELECTRICAL REVIEWER.
 6-CLARIFY WHAT IS A "HOMESTEAD" AS
 SHOWN ON PLANS. IF IT IS A UTILITY
 SHED, THEN PROVIDE COMPLETE PACKAGE
 SHOWING ENGINEERING FOR 140MPH WIND
 LOAD ZONE.
 **ALSO, SHOW DIMENSIONS & EXACT LOCATION
 FOR ZONING REVIEW. SEE ZONING COMMENTS
 7-DECLARED VALUE IS TOO LOW. OWES $37.20
 FOR UPDATED VALUATION.
 8-PROVIDE COMPLETE WALL SECTION THRU
 NEW CONCRETE BLOCK WALL SHOWING 1.5"
 WATER STOP AS REQ'D BY SEC. 2111.1.9
 CITY AMENDMENTS TO FBC 2001.
 **ALSO, SPECIFY INSULATION REQUIRED AT
 WALLS AND CEILING AS REQUIRED BY THE
 ENERGY CALCULATIONS.
 9-CLARIFY NOTE SPECIFYING DOWELS INTO
 EXISTING COLUMN. WHY VERTICAL #5 BARS?
 SPECIFY DOWEL SIZE, EMBEDMENTAND
 SPACING.SECTION 104.2.1.2 OF CITY
 AMENDMENTS TO FBC 2001.
 10-IDENTIFY ROOM WHERE EXISTING WINDOW
 WILL REMAIN. NEED TO VERIFY EGRESS
 REQUIREMENTS FOR BEDROOM AREAS.
 SEC. 1005.4.4 FBC 2001.
 11-PROVIDE PRODUCT APPROVAL FOR SLIDING
 GLASS DOOR AND STORM SHUTTERS AS REQ'D
 BY RULE CHAPTER 9B-72 AS OF OCTOBER
 1ST 2003.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-10-25 Cont ID  
Sent By btrobaug Date 2004-10-25 Time 08:06 Rev Time 0.50
Received By btrobaug Date 2004-10-25 Time 07:44 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-25 Cont ID  
Sent By btrobaug Date 2004-10-22 Time 16:49 Rev Time 0.33
Received By btrobaug Date 2004-08-25 Time 12:11 Sent To B
Notes
2004-08-25 00:00:00 
 1} PLEASE SHOW RECEPTACLE SPACING AS A
 CONTINUATION OF THE DINING ROOM PER
 210.52(A)(1). ALSO NOTE THAT THE
 CONDUCTORS MUST BE # 12 PROTECTED BY A
 20 AMP OCP PER 210.52(B)(1).
  
 2} EGRESS LIGHTING IS REQUIRED PER
 210.70(B)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-10-22 Cont ID  
Sent By btrobaug Date 2004-10-22 Time 16:49 Rev Time 0.00
Received By btrobaug Date 2004-10-22 Time 16:49 Sent To E
Notes
2004-10-22 00:00:00TO BT"S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-24 Cont ID  
Sent By csiegber Date 2004-08-24 Time 09:32 Rev Time 0.00
Received By csiegber Date 2004-08-24 Time 09:32 Sent To B
Notes
2004-08-24 00:00:00TO JG DESK/PER MM

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-18 Cont ID  
Sent By mmclean Date 2004-08-23 Time 16:20 Rev Time 0.00
Received By csiegber Date 2004-08-18 Time 14:26 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-10-25 Cont ID  
Sent By mmclean Date 2004-10-25 Time 16:21 Rev Time 0.00
Received By mmclean Date 2004-10-25 Time 16:21 Sent To B
Notes
2004-10-25 00:00:00APPROVED CONCRETE PATIO WITH NO ROOF MM

Review Stop Z ZONING
Rev No 1 Status F Date 2004-08-23 Cont ID  
Sent By jgomez Date 2004-10-25 Time 15:53 Rev Time 0.00
Received By mmclean Date 2004-08-23 Time 16:20 Sent To I
Notes
2004-08-23 00:00:00WAITING FOR CUSTOMER TO COME IN TO SHOW
 WORK ON SURVEY.JULIO WILL CALL
 CUSTOMER TO EXPLAIN OTHER QUESTIONS MM