Plan Review Details - Permit 04080780
Plan Review Stops For Permit 04080780
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-02-16 Cont ID  
Sent By lsmith Date 2005-02-16 Time 11:16 Rev Time 1.50
Received By lsmith Date 2005-02-16 Time 11:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-01-05 Cont ID  
Sent By lsmith Date 2005-01-05 Time 15:03 Rev Time 1.00
Received By lsmith Date 2005-01-05 Time 15:03 Sent To  
Notes
2005-01-05 00:00:00BUILDINIG PLAN REVIEW: FAILED
  
 1. THE OWNER/AGENT STILL HAS NOT SIGNED
 THE ENERGY FORM.
  
 2.THE DADE COUNTY PRODUCT APPROVAL FOR
 THE ARCH WINDOWS FOR THE BUTT GLASS
 ASSEMBLY NEEDS TO BE SUBMITTED. THE
 GLASS IS NOT IMPACT AND WILL REQUIRE
 STORM PANEL PROTECTION. ACCORDING TO
 THE
 ENGINEER THE ARCH 4500 SERIES WINDOWS
 ARE TO BE USED IN THIS ASSEMBLY.
  
 3. THE APPLICATION FOR THE SITE
 SPECIFIC
 PRODUCT APPROVAL IS INCOMPLETE FOR THE
 BUTT GLASS WINDOWS.THE ENGINEER CANNOT
 BE THE TECHNICAL REPRESENTATIVE (6) AND
 (7) APPROVED THIRD PARTY QUALITY
 ASSURANCE ENTITY LISTED WITH THE STATE.
 THIS IS A CONFLICT OF INTEREST. THE
 DADE
 COUNTY PRODUCT APPROVAL FOR THE ARCH
 4500 SERIES SHOULD BE SUBMITTED WITH
 THE
 SITE SPECIFIC APPLICATION.
  
 4. THERE IS STILL A BALANCE OF $753.65
 IN PERMIT FEES DUE.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-31 Cont ID  
Sent By jleech Date 2004-08-28 Time 11:04 Rev Time 2.50
Received By lsmith Date 2004-08-31 Time 09:21 Sent To  
Notes
2004-08-31 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. ENERGY FORMS ARE NOT SIGNED BY
 OWNER/AGENT.
  
 2. SUBMIT PRODUCT APPROVALS FOR BUTT
 GLASS ASSEMBLY. SUBMIT ENGINEERING FOR
 BUTT GLASS ASSEMBLY.AN INSPECTION
 MUSTBE DONE BY THE ENGINEER WHEN THE
 BUTT
 GLASS IS INSTALLED.A LETTER STATING
 IT IS INSTALLED PER HIS DRAWINGS MUST
 BE SUBMITTED BEFORE A C/O.
  
 3. PLANS MUST BE TAKEN TO PBC AND IMPACT
 FEES PAID, PLANS STAMPED BEFORE A
 PERMIT CAN BE ISSUED.
  
 4. THE CALCULATED VALUE IS UNDERSTATED.
 ADDITIONAL PERMIT FEES ARE DUE.
  
 5. A NOTICE OF COMMENCEMENT MUST BE
 FILED AT THE COUNTY CLERKS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2006-09-26 Cont ID  
Sent By dpalmer Date 2006-09-26 Time 14:41 Rev Time 0.00
Received By dpalmer Date 2006-09-26 Time 12:15 Sent To PC
Notes
2006-09-26 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SEE ONLY ONE SET OF
 PLANS IS SIGNED , DATED AND SEALED.
 PLEASE SUBMIT OTHER SIGNED AND SEALED
 SHEET.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-08-08 Cont ID  
Sent By dpalmer Date 2006-08-08 Time 21:22 Rev Time 0.00
Received By dpalmer Date 2006-08-08 Time 21:22 Sent To PC
Notes
2006-08-08 00:00:00REVISED RECEPTS LOCATIONS ETC.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-04-21 Cont ID  
Sent By btrobaug Date 2006-04-21 Time 17:41 Rev Time 0.33
Received By btrobaug Date 2006-04-21 Time 17:34 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-04-04 Cont ID  
Sent By dpalmer Date 2006-04-04 Time 13:25 Rev Time 0.00
Received By dpalmer Date 2006-04-04 Time 12:58 Sent To PC
Notes
2006-04-04 00:00:00PLANS REDLINED,
  
  
 SERVICE CONDUITS FROM METER TO MCB
 PANELS ARE TO BE IN SLAB 230.70
  
 CIRCUIT FOR UTIL/HALL LTS, SHOWS 15A OCP
 ON #12, WHICH IS OK.
  
 EITHER FOYER OR LIVING ROOM RQUIRES A LT
 FIXTURE OF SOME SORT FOR REQUIRED MEANS
 OF EGRESS LIGHTING. 230.70, LS 101 7.8.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-11-16 Cont ID  
Sent By dpalmer Date 2005-11-16 Time 19:21 Rev Time 0.40
Received By dpalmer Date 2005-11-16 Time 19:07 Sent To M
Notes
2005-11-16 00:00:00REDLINED POSSIBLE MISSING RECEPTS PER
 210.52,210.52C1
  
 REDLINED, PLANS SHOW MAIN DISCONNECT
 LOCATED OUTSIDE, HOWEVER RISER DOES NOT
 SHOW THIS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-02-16 Cont ID  
Sent By dpalmer Date 2005-02-16 Time 06:26 Rev Time 0.25
Received By dpalmer Date 2005-02-16 Time 06:17 Sent To B
Notes
2005-02-16 00:00:00AIC RATING SHEET ATTACHED TO ELECTRICAL
 PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-12-27 Cont ID  
Sent By dpalmer Date 2004-12-27 Time 15:13 Rev Time 0.30
Received By dpalmer Date 2004-12-27 Time 15:13 Sent To M
Notes
2004-12-27 00:00:00**** UNSAT ****
  
 PLEASE SEE NOTE #1 FROM PREVIOUS
 REVIEW.
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 THIS COULD NOT BE LOCATED ON PLANS.
  
 2)NOTE: PLEASE SEE NOTICE FOR FS
 553.80(2)(B) ATTACHED. THIS IS GIVEN AS
 A NOTICE ONLY AT THIS TIME.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-23 Cont ID  
Sent By dpalmer Date 2004-08-23 Time 14:40 Rev Time 0.50
Received By dpalmer Date 2004-08-23 Time 14:09 Sent To M
Notes
2004-08-23 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 3)NOTE: PLEASE SEE LAUNDRY LOAD SHOWN AT
 1.2KW. PLEASE SEE 220.16 FOR MIN 1.5KW
  
 4 )NOTE: PLEASE SHOW /CLARIFY METHOD
 OF THE EQUIPMENT GROUNDING BETWEEN
 MAIN MEANS OF DISC AND PANELS.
 250.110,250.24
 PLEASE SIZE ALL EQUIPMENT GROUNDING
 CONDUCTORS PER 250.122
 PLEASE SEE 250.66 FOR SIZING OF GROUND-
 -ING ELECTRODE CONDUCTOR.
 310.15B6
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-09-20 Cont ID  
Sent By adarroug Date 2006-09-20 Time 16:26 Rev Time 0.00
Received By adarroug Date 2006-09-20 Time 16:26 Sent To E
Notes
2006-09-20 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-08-08 Cont ID  
Sent By adarroug Date 2006-08-08 Time 16:56 Rev Time 0.00
Received By adarroug Date 2006-08-08 Time 16:56 Sent To E
Notes
2006-08-08 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-04-12 Cont ID  
Sent By adarroug Date 2006-04-12 Time 16:30 Rev Time 0.00
Received By adarroug Date 2006-04-12 Time 16:30 Sent To E
Notes
2006-04-12 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-04-03 Cont ID  
Sent By adarroug Date 2006-04-03 Time 09:12 Rev Time 0.00
Received By adarroug Date 2006-04-03 Time 09:12 Sent To E
Notes
2006-04-03 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-03-31 Cont ID  
Sent By adarroug Date 2006-03-31 Time 16:34 Rev Time 0.00
Received By adarroug Date 2006-03-31 Time 16:34 Sent To M
Notes
2006-03-31 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-11-15 Cont ID  
Sent By adarroug Date 2005-11-15 Time 18:02 Rev Time 0.00
Received By adarroug Date 2005-11-15 Time 18:02 Sent To E
Notes
2005-11-15 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-10-06 Cont ID  
Sent By adarroug Date 2005-10-06 Time 16:55 Rev Time 0.00
Received By adarroug Date 2005-10-06 Time 16:55 Sent To M
Notes
2005-10-06 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-11 Cont ID  
Sent By adarroug Date 2005-02-11 Time 09:24 Rev Time 0.00
Received By adarroug Date 2005-02-11 Time 09:24 Sent To E
Notes
2005-02-11 00:00:00TO DPALMER DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-22 Cont ID  
Sent By mjacobs Date 2004-12-22 Time 09:01 Rev Time 0.00
Received By mjacobs Date 2004-12-22 Time 09:01 Sent To E
Notes
2004-12-22 00:00:00SENT TO "DP" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-31 Cont ID  
Sent By mmclean Date 2004-08-20 Time 15:12 Rev Time 0.00
Received By lsmith Date 2004-08-18 Time 12:17 Sent To  
Notes
2004-08-20 00:00:00TO SFD RACK/E
2004-08-18 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-04-03 Cont ID  
Sent By tgordon Date 2006-04-03 Time 12:02 Rev Time 0.20
Received By tgordon Date 2006-04-03 Time 12:02 Sent To  
Notes
2006-04-03 00:00:00REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-11-17 Cont ID  
Sent By tgordon Date 2005-11-17 Time 16:00 Rev Time 0.30
Received By tgordon Date 2005-11-17 Time 16:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-10-14 Cont ID  
Sent By tgordon Date 2005-10-14 Time 08:54 Rev Time 0.25
Received By tgordon Date 2005-10-14 Time 08:54 Sent To  
Notes
2005-10-14 00:00:00*** DENIED ***
 1) MECHANICAL REVISION PLANS DO NOT
 MATCH ENERGY CALCULATIONS. A/C EQUIP.
 LIST ON PLANS ARE CALLING FOR (1) 4 TON,
 (1) 2 1/2 TON ,AND (1) 1 1/2 TON. ENERGY
 CAL'S. ARE CALLING FOR (1) 3 1/2 TON,
 (1) 2 TON, AND (1) 1 1/2 TON. THEY MUST
 COINCIED.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-01-05 Cont ID  
Sent By prafter Date 2005-01-05 Time 14:42 Rev Time 0.45
Received By prafter Date 2005-01-05 Time 14:42 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-08-25 Cont ID  
Sent By dpalmer Date 2004-08-23 Time 14:40 Rev Time 0.35
Received By pkrauss Date 2004-08-25 Time 10:37 Sent To P
Notes
2004-08-25 00:00:00PROVISO:
 PER THE REVISED 2001 FBC(M) 601.4
 AND EXCEPTION #3; BALANCED AIR REQUIRED
 ALL INTO THE MASTER SUITE IS TO BE
 INCLUDED FOR PROPER SIZING OF THE RETURN
 AIR.RETURN AIR SHOULD BE A MINIMUM OF
 14".
  
 AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 CONDENSATE SHALL TERMIANTE A MINIMUM OF
 12" FROM THE BUILDING STRUCTURE.2001
 FBC 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-08-28 Cont ID  
Sent By pkrauss Date 2004-08-25 Time 10:38 Rev Time 0.33
Received By jleech Date 2004-08-28 Time 11:04 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-08-20 Cont ID  
Sent By mmclean Date 2004-08-20 Time 15:12 Rev Time 0.00
Received By mmclean Date 2004-08-20 Time 15:12 Sent To I
Notes
***NONE***