Plan Review Details - Permit 04080473
Plan Review Stops For Permit 04080473
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-12-29 Cont ID  
Sent By kstevens Date 2004-12-29 Time 18:27 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
2004-12-29 00:00:00PLANS SIGNED OFF ON PLANS KSTEVENS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-11-02 Cont ID  
Sent By jwitmer Date 2004-11-02 Time 15:21 Rev Time 2.20
Received By jwitmer Date 2004-11-02 Time 15:21 Sent To  
Notes
2004-11-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04080473
 ADD: 1500 N DIXIE# 308
 CONT: D. F. CONTRACTORS
 TEL: (561)502-1761
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
 2NDREVIEW
 ACTION: DENIED
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1)COMMENT# (2) FROM THE PREVIOUS REVIEW,
 1012.1.4. DURING ITS SWING, ANY DOOR IN
 A MEANS OF EGRESS SHALL LEAVE
 UNOBSTRUCTED AT LEAST 1/2 OF THE REQUIRE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR,
 PASSAGEWAY, OR LANDING, NOR PROJECT MORE
 THAN 7" INTO THE REQUIRED WIDTH.
 ALTHOUGH YOU DO NOT CONSIDER THIS THE
 EXIT, IT IS A CORRIDOR THAT STILL LEAD
 YOU TO AN EXIT. THE CORRIDOR WILL STILL
 REQUIRE 1/2 OF THE REQUIRED (36")
 MINIMUM WIDTH PLUS THE DOOR IN THE OPEN
 POSITION, WITH AN OUTSWING DOOR A
 MINIMUM WIDTH OF 54".
  
 2) SINCE THE TRAVEL DISTANCE FROM THE
 ENTRY TO THE BACK WALL OF THE BREAK ROOM
 IS OVER 75', 2 EXITS ARE REQUIRED,
 INDICATE EXIT LIGHTING ON THE PLAN.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-24 Cont ID  
Sent By jwitmer Date 2004-08-24 Time 13:31 Rev Time 2.00
Received By jwitmer Date 2004-08-24 Time 13:31 Sent To  
Notes
2004-08-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04080473
 ADD: 1500 N DIXIE # 308
 CONT: D. F. CONTRACTORS INC
 TEL: (561)502-1761
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)1012.1.4. DURING ITS SWING, ANY
 DOOR IN A MEANS OF EGRESS SHALL LEAVE
 UNOBSTRUCTED AT LEAST 1/2 OF THE REQUIRE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR,
 PASSAGEWAY, OR LANDING, NOR PROJECT MORE
 THAN 7" INTO THE REQUIRED WIDTH.
  
 3)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 4)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 5)1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-12-27 Cont ID  
Sent By dpalmer Date 2004-12-27 Time 07:06 Rev Time 0.25
Received By dpalmer Date 2004-12-27 Time 07:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-11-02 Cont ID  
Sent By dpalmer Date 2004-11-02 Time 09:42 Rev Time 0.50
Received By dpalmer Date 2004-11-02 Time 09:42 Sent To  
Notes
2004-11-02 00:00:00********** UNSAT **************
  
 1)NOTE: PLEASE SEE NEW ELECTRICAL SHEET
 IS BEING SUBMITTED W/OUT ORIG DETAILED
 PANEL SCHEDULE. PLEASE SEE NOTE #3 FROM
 PREVIOUS REVIEW. CIRCUITS FOR NEW ARE
 NOT ON PLAN.
 PLEASE SEE 700.12E ALSO FOR EM/EXT LTS.
 PLEASE SEE DIFFERENCES IN PREVIOUS
 PANEL
 SCHEDULE TO NEW NOW SHOWN.
 PLEASE CORRELATE.
  
 2)NOTE: PLEASE SEE PLANS NOW CONTAIN A
 COMPLETELY NEW "SIGNATURE" FOR THE
 ARCHITECT OF RECORD.
 PLANS ARE REQUIRED TO BE SIGNED WITH
 LEGAL
 "SIGNATURE". IF THIS IS ACTUAL LEAGL
 SIGNATURE, PLEASE PROVIDE A SIGNED,
 DATED AND SEALED NOTORIZED LETTER TO
 AFFIRM LEGAL SIGNATURE. THIS WILL BE
 PLACED IN A SIGNATURE FILE FOR FUTURE
 REFERENCE.PLANS MAY NOT BE SIGNED WITH
 MULTIPLE SIGNATURES.
 FS 481.025.
  
 PLEASE SEE POSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-19 Cont ID  
Sent By dpalmer Date 2004-08-19 Time 15:50 Rev Time 0.25
Received By dpalmer Date 2004-08-19 Time 15:49 Sent To  
Notes
2004-08-19 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE SEE PLANS ARE SEALED
 COPIES AND DO NOT CONTAIN ORIGINAL
 SIGNATURE AS REQUIRED UNDER FS 481.221
  
 2 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE SEE LOAD CALCS SHOWN ARE FOR A
 RESIDENTIAL HOUSE.
  
 3)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM/EXT LTS.
 PLEASE ALSO INDICATE CIRCUITS FOR NEW
 ITEMS, TO CORRELATE WITH PANEL SCHEDULE.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 WHICH MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE SET OF ORIG TO BE SUBMITTED FOR
 REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-12-27 Cont ID  
Sent By nmccray Date 2004-12-27 Time 12:47 Rev Time 0.00
Received By nmccray Date 2004-12-27 Time 12:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-09-15 Cont ID  
Sent By mcarsill Date 2004-09-15 Time 15:34 Rev Time 0.00
Received By mcarsill Date 2004-09-15 Time 15:34 Sent To  
Notes
2004-09-15 00:00:001) PLEASE INDICATE LOCATIONS OF
 EMERGENCY LIGHTS AND EXIT SIGNS.
  
 2) PLEASE VERIFY DOOR SWINGS IN
 EXIT AREAS. MINIMUM CORRIDOR
 WIDTHS ARE REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-16 Cont ID  
Sent By adarroug Date 2005-05-16 Time 14:21 Rev Time 0.00
Received By adarroug Date 2005-05-16 Time 14:21 Sent To P
Notes
2005-05-16 00:00:00TO "KSTEVENS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-12-14 Cont ID  
Sent By mjacobs Date 2004-12-14 Time 15:53 Rev Time 0.00
Received By mjacobs Date 2004-12-14 Time 15:53 Sent To  
Notes
2004-12-14 00:00:00SENT TO "COMM BD#16

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-27 Cont ID  
Sent By csiegber Date 2004-10-27 Time 11:16 Rev Time 0.00
Received By csiegber Date 2004-10-27 Time 11:16 Sent To  
Notes
2004-10-27 00:00:00TO COMM BD#1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-09-16 Cont ID  
Sent By kstevens Date 2004-09-16 Time 09:38 Rev Time 0.00
Received By kstevens Date 2004-08-11 Time 12:22 Sent To  
Notes
2004-08-11 00:00:00TO COMM BD#24

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-06-01 Cont ID  
Sent By kstevens Date 2005-06-01 Time 19:09 Rev Time 0.75
Received By kstevens Date 2005-06-01 Time 18:48 Sent To  
Notes
2005-06-01 00:00:00REVISION OK - NEW SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-12-29 Cont ID  
Sent By kstevens Date 2004-12-29 Time 18:13 Rev Time 1.00
Received By kstevens Date 2004-12-29 Time 18:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-11-22 Cont ID  
Sent By kstevens Date 2004-11-22 Time 09:05 Rev Time 1.25
Received By kstevens Date 2004-11-19 Time 16:43 Sent To  
Notes
2004-11-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 SHT 2 SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET
 CODE REQUIREMENTS.
 A) BREAK ROOM SINK NOT SHOWN ON RISER.
 B) (NEW) THE DRINKING FOUNTAIN IS NOT
 SHOWN ON THE RISER.
  
 SUBMIT A WATER RISER DIAGRAM. SECTION
 104.2.1.1
  
 SECTION 903.1 EACH SANITARY DRAINAGE
 SYSTEM SHALL HAVE ONE MAIN VENT STACK
 THAT WILL EXTEND THROUGH TO THE OPEN
 AIR.
  
 SEE NOTE #2 OF THE ELECTRICAL PLAN
 REVIEW CONCERNING THE SIGNATURE OF THE
 ARCHITECT. PLEASE SUBMIT A SIGNED/SEALED
 AND DATED NOTORIZED LETTER SHOWING LEGAL
 SIGNATURE OF ARCHITECT OF RECORD. FS
 481.025
  
 SEE ATTACHED SHEET CONCERNING FS
 553.80(2)(B) AND THE DESIGN
 PROFESSIONAL.
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-09-16 Cont ID  
Sent By kstevens Date 2004-09-16 Time 07:51 Rev Time 1.25
Received By kstevens Date 2004-09-16 Time 07:51 Sent To  
Notes
2004-09-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) MORE INFORMATION REQUIRED. INDICATE
 THE TYPE OF BUSINESS, AND EXPLAIN WHAT
 DRAWING ROOMS ARE.
 2) WATER COOLER SHALL BE ARI-1010 COM-
 PLIANT. SUBMIT MANUF. SPECIFICATIONS.
 SECTION 410.1
 3) SINK IN BREAKROOM SHALL COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 SUBMIT A DETAIL.
 4) ACCESSIBLE TOILET ROOM SHALL COMPLY
 WITH 11-4.16, 11-4.19, & 11-4.22 AND ALL
 SUBSECTIONS. SUBMIT A DETAIL. - W/C
 SHALL BE 18" FROM CENTER OF FIXTURE TO
 THE WALL, AND LAV SHALL BE MIN. 15" OFF
 WALL TO CENTER OF FIXTURE. SHOW THESE
 MEASUREMENTS ON THE DETAIL. SECTION
 104.2.1
 5) ORIGINAL SIGNATURE IS REQUIRED ON THE
 SEAL OF EACH SHEET. FAC 61G1-16.004(5)
 AND FS 481.2055 SIGNATURE STAMPS ARE NOT
 APPROVED.
 5) SHT 2 SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET
 CODE REQUIREMENTS.
 A) BREAK ROOM SINK NOT SHOWN ON RISER.
 C) DRY HORIZONTAL VENTS ARE NOT APPROV-
 ED. SECTION 905.3
 D) LAVS IN ACCESSIBLE TOILET ROOM AND
 ADJACENT TOILET ROOM ARE NOT VENTED AND
 ARE "S" TRAPS WHICH ARE NOT APPROVE.
 SECTION 1002.3(5)
 E) W/C'S ON RISER DIAGRAM SHALL NOT BE
 TRAPPED AS THEY HAVE AN INTEGRAL TRAP IN
 THE FIXTURE AND THEY WILL BE DOUBLE TRA-
 PPED. SECTION 1002.1
 (SEE RED LINE CORRECTIONS ON RISER FOR
 EXAMPLES OF HOW TO CORRECT RISER.)
 6) SUBMIT A WATER RISER DIAGRAM. SECTION
 104.3.1.1
 7) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2
 8) INDICATE WHAT WILL BE PROCESSED IN
 THE PROCESSING ROOM. IF CHEMICALS/METALS
 ARE USED IN THE PROCESSING A DILUTION
 TANK OR SEPARATOR MAY BE REQUIRED.
 SECTION 104.2.1
 9) SECTION 903.1 EACH SANITARY DRAINAGE
 SYSTEM SHALL HAVE ONE MAIN VENT STACK
 THAT WILL EXTEND THROUGH TO THE OPEN AIR
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved