Plan Review Details - Permit 04080461
Plan Review Stops For Permit 04080461
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-10-26 Cont ID  
Sent By lsmith Date 2004-10-26 Time 07:45 Rev Time 0.50
Received By lsmith Date 2004-10-26 Time 07:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-08-19 Cont ID  
Sent By csiegber Date 2004-08-16 Time 16:50 Rev Time 0.33
Received By btrobaug Date 2004-08-19 Time 10:31 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-12 Cont ID  
Sent By csiegber Date 2004-10-12 Time 11:49 Rev Time 0.00
Received By csiegber Date 2004-10-12 Time 11:49 Sent To P
Notes
2004-10-12 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-24 Cont ID  
Sent By csiegber Date 2004-08-24 Time 15:55 Rev Time 0.00
Received By csiegber Date 2004-08-24 Time 15:55 Sent To P
Notes
2004-08-24 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-16 Cont ID  
Sent By csiegber Date 2004-08-16 Time 16:50 Rev Time 0.00
Received By csiegber Date 2004-08-16 Time 16:50 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-11 Cont ID  
Sent By mmclean Date 2004-08-16 Time 16:03 Rev Time 0.00
Received By csiegber Date 2004-08-11 Time 15:12 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-10-26 Cont ID  
Sent By kstevens Date 2004-10-26 Time 07:40 Rev Time 0.50
Received By kstevens Date 2004-10-26 Time 07:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-09-18 Cont ID  
Sent By csiegber Date 2004-10-12 Time 11:49 Rev Time 2.00
Received By kstevens Date 2004-09-18 Time 13:13 Sent To  
Notes
2004-09-18 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 BADUJET SYSTEM DOES NOT SHOW COMPLIANCE
 WITH SECTIONS 424.2.6.1 ENTRAPMENT PRO-
 TECTION, 424.2.6.6.3 ENTRAPMENT AVOID-
 ANCE, OR 424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS PER PUMP. PLEASE PROVIDE
 INFORMATION SHOWING COMPLIANCE WITH
 THESE SECTIONS OF THE FBC-2001
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-08-21 Cont ID  
Sent By csiegber Date 2004-08-24 Time 15:55 Rev Time 0.50
Received By kstevens Date 2004-08-21 Time 09:48 Sent To  
Notes
2004-08-21 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) FBC-2001424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MINIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL) - SUPPLY INFORMATION ON THE
 "BADU" PUMP (4HP) AND SHOW HOW THIS WILL
 COMPLY WITH THE ABOVE REQUIREMENT.
 - ALSO PLANS STATE "SEE MANUF. SPECS.
 FOR BADU JET" - SUBMIT SPECS FOR REVIEW
 AND FOR INSPECTORS AT TIME OF INSPECTION
 SECTION 104.2.1
 2) INDICATE ON EQUIPMENT LAYOUT THE NUM-
 BERS AND LETTERS FROM THE LEDGEND FOR
 THE BADU SYSTEM. SECTION 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-08-16 Cont ID  
Sent By csiegber Date 2004-08-11 Time 15:12 Rev Time 0.00
Received By mmclean Date 2004-08-16 Time 16:03 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved