Plan Review Details - Permit 04080391
Plan Review Stops For Permit 04080391
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-02-03 Cont ID  
Sent By shill Date 2005-02-03 Time 14:56 Rev Time 1.50
Received By shill Date 2005-02-03 Time 14:56 Sent To PC
Notes
2005-02-03 00:00:00****PROVISO****
 QUALITY ASSURANCE ENTITY'S FINAL
 FINDINGS REPORT BEFORE CO
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-01-18 Cont ID  
Sent By shill Date 2005-01-18 Time 11:12 Rev Time 3.00
Received By shill Date 2005-01-18 Time 09:11 Sent To PC
Notes
2005-01-18 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PENDING LOCAL PRODUCT APPROVAL.
 APPLICATION FORWARDED TO BILL STAPLES'
 DESK FOR APPROVAL.
  
 2.)THE NOTICE OF COMMENCEMENT IS
 EXPIRED (MORE THAN 90 DAYS WITHOUT
 COMMENCING WORK), FS713.13(2).
  
  
 ****NO RESUB FEE****

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-12-14 Cont ID  
Sent By shill Date 2004-12-14 Time 08:34 Rev Time 3.00
Received By shill Date 2004-12-14 Time 07:10 Sent To PC
Notes
2004-12-14 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 COMMENTS FROM THE PREVIOUS REVIEW,
 ITEMS
 #3 AND #4 WERE NOT ADDRESSED.PLANS
 ARE
 DATED 8/3 AND 8/6, SAME PLANS AS
 REVIEWED PREVIOUSLY WITH NO REVISIONS.
  
 FOR YOUR CONVENIENCE, THE PREVIOUS
 COMMENTS ARE AS FOLLOWS:
  
 1.)PROVIDE DESIGN LOAD INFORMATION ON
 THE PLAN AS WELL AS THE INFORMATION
 REQUIRED BY FBC1609.1.72003
 AMENDMENTS.
  
 2.)SHOW FBC TABLE 500 COMPLIANCE;
 PROVIDE AREAS OF EXISTING BUILDING,
 ADDITION AREA, DECLARE BUILDING TYPE,
 SPRINKLED OR NONSPRINKLED AND
 OCCUPANCY.
  
 3.)SHOW HOW THE PANELS MEET FIRE
 RESISTANCE REQUIREMENTS.CANOPIES IN
 THE FIRE DISTRICT ARE TO CONFORM WITH
 THE CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC, SECTION F102.2.8.ROOF
 PANELS ARE NOT REQUIRED TO HAVE FIRE
 RESISTANCE RATING UNLESS FIRE
 RESISTANCE
 RATING IS REQUIRED FBC1604.5(2).ROOF
 FIRE RESISTANCE RATING IS REQUIRED CITY
 OF WEST PALM BEACH AMENDMENTS TO THE
 FBC
 F102.2.4.
  
 4.)SHOW HOW QUALITY ASSURANCE WILL BE
 ADDRESSED (LOCAL PRODUCT APPROVAL
 APPLICATION), FAC9B-72.
  
 5.)SEE ATTACHED FS553.80(2)(B).
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-12-01 Cont ID  
Sent By shill Date 2004-12-01 Time 15:31 Rev Time 2.00
Received By shill Date 2004-12-01 Time 15:31 Sent To PC
Notes
2004-12-01 00:00:00***LOCAL PRODUCT APPROVAL
 APPLICATION***
  
 ****NOT A PLAN REVIEW****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)ORIGINAL TEST REPORTS AND
 ENGINEERING REQUIRED.
  
 2.)THIRD PARTY QUALITY ASSURANCE
 ENTITY CANNOT BE THE MANUFACTURER (THEN
 IT WOULDN'T BE A THIRD PARTY).SEE
 FAC9B72.010(6).
  
 3.)PLEASE SIGN THE APPLICATION.
  
 4.)INDICATE METHOD 1 OR METHOD 2 (ITEM
 #1 ON APPLICATION).

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-11-17 Cont ID  
Sent By shill Date 2004-11-17 Time 12:14 Rev Time 2.00
Received By shill Date 2004-11-17 Time 12:14 Sent To  
Notes
2004-11-17 00:00:00****INFORMATIONAL ONLY****
  
 AS PER DISCUSSION WITH A TESTING
 LABORATORY (JIM, 800-381-7744), THE
 FOLLOWING HAS BEEN ADDRESSED IN REGARDS
 TO THE SKYLIGHT ROOF PANELS:
  
 1.)PURSUANT TO FAC9B-72, LOCAL OR
 STATE PRODUCT APPROVAL REQUIRED.
  
 2.)FBC CHAPTER 2, DEFINITIONS, THE
 SKYLIGHT ROOF PANELS ARE POLYCARBONATE
 SO WOULD THEREFORE FALL UNDER THE
 DEFINITION OF PLASTIC, ROOF PANELS.
  
 3.)FBC1706.1, ESTABLISHED TEST
 PROCEDURES, ASTM E 72, CONDUCTING
 STRENGTH TESTS OF PANELS FOR BUILDING
 CONSTRUCTION WOULD BE APPLICABLE.
  
 4.)IT IS ADVISED THAT THE LOCAL
 PRODUCT APPROVAL APPLICATION BE FILLED
 OUT AND BE SUBMITTED BY FAX FOR A
 PRELIMINARY REVIEW; 561-653-2692 ATTN
 SAMANTHA.
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-09-20 Cont ID  
Sent By shill Date 2004-08-31 Time 14:28 Rev Time 3.00
Received By shill Date 2004-08-31 Time 14:28 Sent To  
Notes
2004-08-31 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE PLANS SHOW A "FUTURE GARAGE".
 PLEASE NOTE THAT COMPLIANCE WITH THE
 BUILDING CODE OR CODES WHICH WILL BE IN
 EFFECT AT THE TIME OF SUBMITTAL HAS NOT
 PERFORMED FOR THIS FUTURE STRUCTURE
 RELATIVE TO THIS AWNING.
  
 2.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED FOR THE ROOF,FAC9B-72.
 SEE WWW.FLORIDABUILDING.ORG.AN
 APPLICATION WAS SUBMITTED BUT IS
 INCOMPLETE.PLEASE NOTE THAT ITEM
 #2, 7 THROUGH 10 ARE INCOMPLETE.PLEASE
 SEE ATTACHED APPLICATION WITH CHECKLIST.
 ORIGINAL DOCUMENTS REQUIRED, INCLUDING
 SEALED TEST REPORT.A COPY OF A TEST
 REPORT WHICH I FOUND ON THE INTERNET
 IS INCLUDED FOR YOUR CONVENIENCE.IT
 IS THE RESPONSIBILITY OF THE DESIGNER
 TO DETERMINE WHETHER OR NOT THIS IS
 THE PRODUCT YOU WISH TO INSTALL.
 ALSO PLEASE SEE THE VALIDATION CHECKLIST
 TO ASSIST YOU IN FILLING OUT THIS FORM.
 ADDITIONAL INFORMATION IS ALSO
 AVAILABLE IN THE RULE 9B-72 FOUND AT
 WWW.FLORIDABUILDING.ORG.
  
 3.)PROVIDE DESIGN LOAD INFORMATION
 ON THE PLAN AS WELL AS THE INFORMATION
 (WIND LOAD) REQUIRED BY FBC1609.1.7,
 2003 AMENDMENTS.
  
 4.)YOU ARE CONNECTING TWO EXISTING
 BUILDINGS TO BECOME ONE STRUCTURE.
 PROVIDE AREAS OF THE EXISTING BUILDINGS,
 DECLARE BUILDING TYPE AND OCCUPANCY,
 SHOW COMPLIANCE WITH FBC TABLE 500.
  
 5.)THE TEST REPORT WHICH I OBTAINED
 FROM THE INTERNET (ENCLOSED) INDICATES A
 FAILURE OF THE PANELS AT 161.2.THE
 DECK CONNECTION ANALYSIS SHOW A DESIGN
 PRESSURE OF -128.2 FOR ZONE 3.WHERE
 IS THE SAFETY FACTOR FOR THE PANELS,
 WHICH DO NOT APPEAR TO BE COMPLIANT
 FOR ZONE 3 (ALTHOUGH THE CONNECTORS
 ARE APPARENTLY COMPLIANT)?IS THIS
 TEST FOR THE SAME PRODUCT?
  
 6.)DELEGATED ENGINEERING IS TO BE
 REVIEWED BY THE DESIGNER OF RECORD,
 PLEASE REVIEW FAC61G15-30.005, .006.
 DESIGN PERFORMED BY DELEGATED ENGINEER
 IS TO BE IN CONFORMANCE WITH THE PLAN,
 WHICH IS LACKING DESIGN CRITERIA.
  
 7.)FOR THE CONNECTOR CALCS, A TITLE
 BLOCK WITH ALL INFORMATION REQUIRED
 BY FAC61G15-23.002 IS REQUIRED.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2004-08-23 Cont ID  
Sent By dpalmer Date 2004-08-23 Time 16:28 Rev Time 0.27
Received By dpalmer Date 2004-08-23 Time 16:28 Sent To  
Notes
2004-08-23 00:00:00NO ELECTRICAL PLANS SUBMITTED FOR REVIEW
 NO ELECTRICAL CONTRACTOR SIGNED ON
 APPLICATION.
 ANY ELECTRICAL WORK/LIGHTING ETC TO BE
 UNDER SEPARATE PERMIT AND FEES.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-12-09 Cont ID  
Sent By nmccray Date 2004-12-09 Time 16:16 Rev Time 0.00
Received By nmccray Date 2004-12-09 Time 16:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-09-15 Cont ID  
Sent By nmccray Date 2004-09-15 Time 11:03 Rev Time 0.00
Received By nmccray Date 2004-09-15 Time 11:03 Sent To  
Notes
2004-09-15 00:00:00*************DENIED*********************
  
 1) WHAT IS THE FLAMESPREAD OF THE
 PLASTIC ?
  
 2) WILL THERE BE CARS STORED UNDERNEATH
 THESE CANOPIES ?
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-01-12 Cont ID  
Sent By mjacobs Date 2005-01-12 Time 11:21 Rev Time 0.00
Received By mjacobs Date 2005-01-12 Time 11:21 Sent To B
Notes
2005-01-12 00:00:00TO "SH" DESK/RESUB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-12-02 Cont ID  
Sent By mjacobs Date 2004-12-02 Time 13:08 Rev Time 0.00
Received By mjacobs Date 2004-12-02 Time 13:08 Sent To B
Notes
2004-12-03 00:00:00SUBMITTAL WAS PERMIT APPLICATION AND
 LOCAL PA - PUT W/PKG, #21
 DID NOT REVIEW PA BECAUSE IT IS PENDING
 LETTER FROM ENGINEER TO DO QUALITY
 ASSURANCE, TO SUBMIT NEXT WEEK
2004-12-02 00:00:00TO "SH" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-01 Cont ID  
Sent By mjacobs Date 2004-12-01 Time 17:54 Rev Time 0.00
Received By mjacobs Date 2004-12-01 Time 17:54 Sent To  
Notes
2004-12-01 00:00:00SENT TO COMM BD#21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-09-20 Cont ID  
Sent By shill Date 2004-09-20 Time 12:20 Rev Time 0.00
Received By shill Date 2004-08-12 Time 10:07 Sent To  
Notes
2004-08-12 00:00:00TO COMM BD#14

Review Stop Z ZONING
Rev No 1 Status P Date 2004-08-30 Cont ID  
Sent By gjoyce Date 2004-08-30 Time 09:43 Rev Time 0.50
Received By gjoyce Date 2004-08-30 Time 09:43 Sent To  
Notes
***NONE***