Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-13 Cont ID  
Sent By csiegber Date 2004-09-15 Time 15:54 Rev Time 0.50
Received By btrobaug Date 2004-08-13 Time 09:59 Sent To  
Notes
2004-08-13 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE 2(TWO) SETS OF PLANS
 FOR REVIEW.
  
 2} ALL PLANS SUBMITTED BY AN ARCHITECT
 MUST BE SIGNED AND SEALED BY THE
 DESIGNER PER 481 FS.& 61G1-16.003 FAC.
  
 3} THE GENERAL LIGHTING LOAD MUST BE CAL
 CULATED @ 3 1/2 VA PER 220.3(A).
  
 4} THE SIGN LIGHTING CALCULATION MUST CO
 MPLY WITH 220.3(B)(6), 1200VA.
  
 5} THE TRACK LIGHTING LOAD MUST BE CALCU
 LATED @ 1200VA. PER 220.12(B).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-09-15 Cont ID  
Sent By csiegber Date 2004-09-15 Time 15:54 Rev Time 0.00
Received By csiegber Date 2004-09-15 Time 15:53 Sent To E
Notes
2004-09-15 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-06 Cont ID  
Sent By csiegber Date 2004-08-06 Time 15:04 Rev Time 0.00
Received By csiegber Date 2004-08-06 Time 15:04 Sent To E
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved