Plan Review Details - Permit 04080236
Plan Review Stops For Permit 04080236
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-08-23 Cont ID  
Sent By btrobaug Date 2004-08-23 Time 08:57 Rev Time 0.50
Received By btrobaug Date 2004-08-23 Time 07:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-12 Cont ID  
Sent By csiegber Date 2004-08-05 Time 13:36 Rev Time 1.00
Received By btrobaug Date 2004-08-12 Time 15:29 Sent To  
Notes
2004-08-12 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE A RISER DIAGRAM PER
 215.5.
  
 2} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110.9.
  
 3} PLEASE VERIFY THAT THE AIR HANDLER
 HAS ONLY 10K OF HEAT FOR A 1100 SQ FT.
 RESIDENCE. ALSO INDICATE THE COMPRESSOR
 LOAD.
  
 4} PROVIDE A PANEL SCHEDULE SO THAT BC
 BREAKER & WIRE SIZES ARE PER CODE.
  
 5} PLEASE LABEL ROOMS.
  
 6} SHOW STAIR LIGHTING PER 210.70.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-20 Cont ID  
Sent By ptjomsto Date 2004-08-20 Time 14:47 Rev Time 0.00
Received By ptjomsto Date 2004-08-20 Time 14:47 Sent To  
Notes
2004-08-20 00:00:00RESUB GIVEN TO BILL TROBAUGH

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-05 Cont ID  
Sent By csiegber Date 2004-08-05 Time 13:36 Rev Time 0.00
Received By csiegber Date 2004-08-05 Time 13:36 Sent To E
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved