Plan Review Stops For Permit 04080211 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2005-06-13 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2005-06-13 |
Time |
15:30 |
Rev Time |
0.50 |
Received By |
lsmith |
Date |
2005-06-13 |
Time |
15:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2005-05-04 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2005-05-04 |
Time |
09:30 |
Rev Time |
0.50 |
Received By |
lsmith |
Date |
2005-05-04 |
Time |
09:30 |
Sent To |
|
|
Notes |
2005-05-04 00:00:00 | BUILDING PLAN REVIEW FAILED | | | | 1. SLAB MUST BE MINIMUM OF 4". DRAWING | | SHOWS 3". | | | | 2. SHOW METHOD OF COMPLIANCE WITH POOL | | SAFETY ACT FOR PROTECTION OF OPENINGS | | FROM HOUSE TO POOL. | | | | 3. NO RECORD OF HISTORIC APPROVAL SHOWN | | ON PLANS OR APPLICATION. TAKE PLANS TO | | 5TH FLOOR FOR HISTORIC APPROVAL | | | | ANY QUESTIONS PLEASE CALL: | | LEA SMITH, BUILDING PLANS EXAMINER | | 805-6713 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2005-02-23 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2005-02-23 |
Time |
08:26 |
Rev Time |
0.50 |
Received By |
lsmith |
Date |
2005-02-23 |
Time |
08:26 |
Sent To |
|
|
Notes |
2005-02-23 00:00:00 | BUILDING PLAN REVIEW: FAILED | | | | 1. SHOW DETAIL OF ANCHORING EQUIPMENT TO | | SLAB. | | | | | | ANY QUESTIONS PLEASE CALL: | | LEA SMITH. BUILDING PLANS EXAMINER | | 805-6713 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
N |
Date |
2005-06-13 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-06-13 |
Time |
11:35 |
Rev Time |
0.25 |
Received By |
btrobaug |
Date |
2005-06-13 |
Time |
11:32 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2005-04-19 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-04-19 |
Time |
11:38 |
Rev Time |
0.25 |
Received By |
btrobaug |
Date |
2005-04-19 |
Time |
09:54 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2005-02-18 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-02-18 |
Time |
13:05 |
Rev Time |
0.33 |
Received By |
btrobaug |
Date |
2005-02-18 |
Time |
12:58 |
Sent To |
P |
|
Notes |
2005-02-18 00:00:00 | PLEASE SUBMIT DETAILS FOR THE PANEL | | SHOWN ON THE SCHEMATIC, FEEDER AND CONDU | | IT SIZE AND TYPE, PANEL RATING AND OCP, | | PANEL SCHEDULE AND COMPUTED LOAD, ETC. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2005-06-09 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-06-09 |
Time |
13:39 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2005-06-09 |
Time |
13:39 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2005-05-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-05-24 |
Time |
19:04 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-05-24 |
Time |
19:04 |
Sent To |
P |
|
Notes |
2005-05-24 00:00:00 | TO "KSTEVENS" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2005-04-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-04-14 |
Time |
09:40 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-04-14 |
Time |
09:40 |
Sent To |
E |
|
Notes |
2005-04-14 00:00:00 | TO "BT" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2005-02-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-02-17 |
Time |
12:55 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-02-17 |
Time |
12:55 |
Sent To |
E |
|
Notes |
2005-02-17 00:00:00 | TO "E" BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-02-07 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-02-07 |
Time |
14:11 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-02-07 |
Time |
14:11 |
Sent To |
Z |
|
Notes |
2005-02-07 00:00:00 | TO "Z"BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2004-08-04 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-08-04 |
Time |
14:48 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-08-04 |
Time |
14:48 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2005-06-13 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2005-06-13 |
Time |
10:54 |
Rev Time |
0.75 |
Received By |
jleech |
Date |
2005-06-13 |
Time |
10:54 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2005-04-28 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2005-04-28 |
Time |
15:29 |
Rev Time |
0.75 |
Received By |
kstevens |
Date |
2005-04-28 |
Time |
15:29 |
Sent To |
B |
|
Notes |
2005-04-28 00:00:00 | DENIED | | REFERENCE: FBC-2001 CHAPTER 1 | | | | 1) GAS WATER HEATER TIE DOWN DETAIL | | SHOWS THE CONCRETE PAD AS 3", WHEREAS | | THE TYPICAL SLAB DETAIL ON THE GENERAL | | NOTES SHEET SHOW A 4" THICK SLAB AS IS | | REQUIRED. PLEASE CORRELATE DETAILS. | | SECTION 104.2.1. | | 2) SPECIFICATION SHEET SHOWS THE SHEER | | DECENT/LION HEAD RETURNS ON THE SIDE OF | | THE POOL, BUT THE LAYOUT SHEET SHOWS | | THESE RETURNS AT THE END OF THE POOL. | | PLEASE CLARIFY AND CORRELATE SHEETS. | | SECTION 104.2.1. | | 3) TWO SETS OF PLANS ARE REQUIRED TO BE | | SUBMITTED WITH APPLICATION FOR PERMIT. | | LOOSE SHEETS ARE NOT SETS OF PLANS. | | SECTION 104.2.1. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2005-02-22 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2005-02-22 |
Time |
18:48 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2005-02-22 |
Time |
18:48 |
Sent To |
B1 |
|
Notes |
2005-02-22 00:00:00 | DENIED | | REFERENCE: FBC-424.2 SWIMMING POOLS | | FBC-2001 CHAPTER 1 | | | | | | 1) THE FOLLOWING INFORMATION IS REQUIRED | | ON THE PLANS EITHER IN THE FORM OF | | NOTES, DRAWINGS, OR SUBMITTALS: | | 2) FBC-2001424.2.6.6.2 SHOW COMPLIANCE | | WITH ANSI/ASME A112.19.8M. PROVIDE MODEL | | NUMBER AND MANUF INFO FOR VAC LOCK. - NO | | VACUUM LINE IS SHOWN ON THE POOL LAYOUT | | SHEET, BUT A VACUUM LINE IS INDICATED ON | | THE PIPING SCHEMATIC. PLEASE CLAIRFY AND | | CORRELATE PIPING SCHEMATIC WITH POOL | | LAYOUT. (GIVE DETAIL, SUBMITTAL OR ADD | | TO NOTES) SECTION 104.2.1. | | 3) FBC-2001424.2.6.6.4 MINIMUM OF TWO | | SUCTION INLETS SHALL BE PROVIDED FOR EA | | PUMP. SEPARATED BY A MINIMUM OF 3 FEET | | OR LOCATED ON TWO DIFFERENT PLANES. | | (DETAIL)- UNABLE TO READ MINIMUM | | SEPARATION BETWEEN MAIN DRAINS ON THE | | PLANS. PLEASE INDICATE 3 FT. SECTION | | 104.2.1. | | 4) SHEET WITH PIPING SCHEMATIC HAS A | | NOTE THAT STATES "HEATER IS EXCEMPT FROM | | STATE ENERGY CODE AS HEAT SOURCE IS AND, | | IS 90% EFICIENT". THIS IS NOT THE CASE | | WITH GAS POOL HEATERS AND SHALL BE | | DELETED FROM THE PLANS. | | 5) FBC-2001 424.2.14.1 SWIMMING POOL | | WATER HEATERS SHALL BEAR THE LABEL OF A | | RECOGNIZED TESTING AGENCY. MANUFACTURE | | SHEETS REQUIRED. (SUBMITTAL) | | 6) FBC-2001 424.2.14.2 WATER RETENTION, | | PROVIDE A POSITIVE MEANS OF RETAINING | | WATER IN THE HEATER WHEN PUMP IS SHUT | | OFF. (MANUF. CUT SHEETS - SUBMITTAL) | | 7) FBC-2001 424.2.15 GAS PIPING SHALL | | COMPLY WITH FBC FUEL GAS. SEPARATE PLANS | | AND PERMIT REQUIRED. (ADD TO NOTES) | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2005-02-16 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-02-16 |
Time |
15:30 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-02-16 |
Time |
15:30 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2004-08-10 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-08-04 |
Time |
14:48 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2004-08-10 |
Time |
11:42 |
Sent To |
|
|
Notes |
2004-08-10 00:00:00 | DENIED, MUST BE 10FT ON THE SIDE. | | CALLED CONTR FILE UNDER B FOR P/U MM |
|
|