Plan Review Details - Permit 04071423
Plan Review Stops For Permit 04071423
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-10-14 Cont ID  
Sent By jwitmer Date 2004-10-14 Time 13:13 Rev Time 1.11
Received By jwitmer Date 2004-10-14 Time 12:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-10-06 Cont ID  
Sent By csiegber Date 2004-10-13 Time 11:45 Rev Time 0.77
Received By jwitmer Date 2004-10-06 Time 16:34 Sent To  
Notes
2004-10-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04071423
 ADD: 625 N FLAGLER# 700
 CONT: PASS INTERNATIONAL
 TEL: (561)289-0125
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) SECOND REQUEST, REFRENCE (4) SHEET
 A-101 SEE NEW OFFICE 0712A, IN FRONT OF
 THIS NEW OFFICE THERE IS A EXISTING COL-
 UMN. WITH THE CREATION OF THE OFFICE AND
 NEW WORK STATION IT APPEARS TO BE LESS
 THAN 30". MEANS OF EGRESS FOR LESS THAN
 50 IS 36" FOR THE OCCUPANT LOAD INDICAT-
 ED AS (124) THE MINIMUM CLEAR WIDTH OF
 CORRIDOR BEING PART OF A MEANS OF EGRESS
 IS 44" CLEAR, SEE TABLE 1004 / FLORIDA
 BUILDING CODE FOR MINIMUM CORRIDOR/
 AISLE WIDTH.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-05 Cont ID  
Sent By jwitmer Date 2004-08-05 Time 13:37 Rev Time 2.22
Received By jwitmer Date 2004-08-05 Time 11:42 Sent To  
Notes
2004-08-05 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04071423
 ADD: 625 N FLAGLER DR# 700
 CONT: SGRA. LOURDES GURREA
 TEL: (954) 961-6806
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PLANS DO NOT INDICATE WHAT THE RATING
 IS ON THE FRONT ENTRY DOORS WILL BE, IT
 IS IN A HIGHLIGHTED AREA WORK TO BE
 COMPLETED?
  
 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 4) SHEET A-101 SEE NEW OFFICE 0712A,
 IN FRONT OF THIS NEW OFFICE THERE IS A
 EXISTING COLUMN. WITH THE CREATION OF
 THE NEW OFFICE IT APPEARS TO BE LESS
 THAN 30" CLEAR.MEANS OF EGRESS REQUIRES
 44", 36" FOR CORRIDORS WITH AN OCCUPANT
 LOAD LESS THAN 50.
  
 5) PROVIDE THE MINIMUM BUILDING TYPE?
 7 STORIES SHOULD REQUIRE TYPE II ,
 609.2.1 PARTITIONS AND BACKING ARE TO BE
 NONCOMBUSTIBLE.
  
 8)11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
 OFFICE 708, THE ENTRY DOES NOT MEET THE
 REQUIRED 18" CLEAR ON THE PULL SIDE OF
 THE OFFICE DOORWAY.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 9)DOES THIS BUILDING HAVE FIRE SPRINKLER
 SYSTEM? IF SO PROVIDE UPDATES TO THIS
 FLOOR.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-09-24 Cont ID  
Sent By dpalmer Date 2004-09-24 Time 10:01 Rev Time 0.25
Received By dpalmer Date 2004-09-24 Time 10:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-09-22 Cont ID  
Sent By dpalmer Date 2004-09-22 Time 06:50 Rev Time 0.25
Received By dpalmer Date 2004-09-22 Time 06:38 Sent To  
Notes
2004-09-22 00:00:00** UNSAT **
  
 1)NOTE: PLEASE SEE ELECTRICAL PLANS ARE
 OK.
 PLEASE BE ADVISED THAT THIS OFFICE HAS
 NOT YET RECEIVED ANY CONFORMATION OR
 RESULTS FROM FBPE'S AS TO THE ACCEPTABLE
 SIGNATURE FOR MR. JULIO VIDAL.
 THIS OFFICE HAS FOUR DIFFERENT SIGNATURE
 'S ON FILE FOR MR. VIDAL AND WE ARE
 UNABLE TO VERIFY AT THIS TIME AS TO
 WHICH "ONE" IS AND WILL BE ACCEPTABLE.
 PLEASE CONTACT FBPE'S SO THAT THIS MAY
 BE ADDRESSED AS SOON AS POSSIBLE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
 SPOKE TO STATE FBPE'S , AND MR VIDAL
 AWAITING LETTER FROM MR VIDAL AND
 ELECTRICAL PLANS CAN BE SIGNED OFF AND
 STAMPED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-03 Cont ID  
Sent By dpalmer Date 2004-08-03 Time 10:31 Rev Time 0.33
Received By dpalmer Date 2004-08-03 Time 10:31 Sent To  
Notes
2004-08-03 00:00:00********* UNSAT ************
  
 ** PLANS ARE ONLY IN FOR PLAN REVIEW
 AND NOT FOR PERMIT. **
  
 1)NOTE: TITLE BLOCK ON PLANS SHOULD
 CONTAIN NAME AS SHOWN ON LICENSE/CA #
 WITH STATE DBPR.
 TITLE BLOCK SHOWS COMPANY AS LNI WHEREAS
 STATE LIST LEONARDO NAVEIRAS INC.
 FS 471.023
  
 2)NOTE: PLEASE SEE FAC 61G15-23.002,
 PRINTED NAME AND LIC # OF ENGINEER IS
 ALSO REQUIRED ON TITLE BLOCK.
  
 PLEASE NOTE: SIGNATURE AS SHOWN FOR
 MR JULIO VIDAL HAS NOT BEEN VERIFIED TO
 THIS OFFICE FROM FBPE'S.
 THIS WAS SENT TO FBPE'S AND THIS OFFICE
 HAS NOT RECIEVED ANY RESULTS FROM FBPE'S
 FULL LEGAL SIGNATURE WILL BE REQUIRED
 BY THIS OFFICE AS ON PREVIOUS REQUESTS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-10-01 Cont ID  
Sent By mcarsill Date 2004-10-01 Time 13:35 Rev Time 0.00
Received By mcarsill Date 2004-10-01 Time 13:35 Sent To  
Notes
2004-10-01 00:00:001) FIRE SPRINKLER PERMIT REQUIRED
 SINCE WORK INVOLVES MORE THAN FIVE
 SPRINKLER HEADS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-08-13 Cont ID  
Sent By mcarsill Date 2004-08-13 Time 13:55 Rev Time 0.00
Received By mcarsill Date 2004-08-13 Time 13:55 Sent To  
Notes
2004-08-13 00:00:001) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) DEBRIS SHALL BE REMOVED FROM
 THE SITE DAILY.
  
 3) ONLY 30" PROVIDED FOR EXITING
 IN EXISTING HALLWAY 0737. 44" REQUIRED.
 PLEASE REVISE AS NECESSARY.
  
 4) NO 04 ON PAGE DE-101.
  
 5) FUEL POWERED EQUIPMENT USED MUST
 BE PROVIDED WITH PROPER VENTILATION
 TO PREVENT THE ACCUMULATION OF
 CARBON MONOXIDE.
  
 6) PLEASE ILLUSTRATE ALL ILLUMINATED
 EXIT SIGNS AND EMERGENCY LIGHTS.
  
 7) ON PAGE E-101, ONLY ONE FIRE ALARM
 HORN STROBE COULD BE LOCATED ON
 THE PLANS. PLEASE ADVISE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-10-13 Cont ID  
Sent By csiegber Date 2004-10-13 Time 11:44 Rev Time 0.00
Received By csiegber Date 2004-10-13 Time 11:44 Sent To B
Notes
2004-10-13 00:00:00TO JW DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-09-20 Cont ID  
Sent By csiegber Date 2004-09-20 Time 07:47 Rev Time 0.00
Received By csiegber Date 2004-09-20 Time 07:47 Sent To  
Notes
2004-09-20 00:00:00TO COMM BD#19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-19 Cont ID  
Sent By kstevens Date 2004-08-19 Time 08:10 Rev Time 0.00
Received By kstevens Date 2004-07-30 Time 16:28 Sent To  
Notes
2004-07-30 00:00:00TO COMM BD#32

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-10-04 Cont ID  
Sent By pkrauss Date 2004-10-04 Time 07:22 Rev Time 0.35
Received By pkrauss Date 2004-10-04 Time 07:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-08-13 Cont ID  
Sent By pkrauss Date 2004-08-13 Time 09:07 Rev Time 0.35
Received By pkrauss Date 2004-08-13 Time 09:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-10-09 Cont ID  
Sent By kstevens Date 2004-10-09 Time 12:35 Rev Time 0.33
Received By kstevens Date 2004-10-09 Time 12:35 Sent To  
Notes
2004-10-09 00:00:00SEE NOTE IN ELECTRICAL REVIEW CONCERNING
 ENGINEER'S SIGNATURE

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-08-19 Cont ID  
Sent By kstevens Date 2004-08-19 Time 08:02 Rev Time 1.00
Received By kstevens Date 2004-08-19 Time 07:59 Sent To  
Notes
2004-08-19 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
  
 1) ACCESSIBLE STALL SHALL COMPLY WITH
 SECTION 11-4.17.3 OR THE EXCEPTION TO
 THIS SECTION. SEE FIGURE 30(A) OR FIGURE
 30(B).
 2) SHOW AN UNOBSTRUCTED TURINIG SPACE IN
 EACH TOILET ROOM PER SECTION 11-4.22.3
 3) INDICATE ACCESSIBLE TOILET HEIGHT PER
 SECTION 11-4.16.3
 4)A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]