Plan Review Details - Permit 04071378
Plan Review Stops For Permit 04071378
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-09-15 Cont ID  
Sent By alange Date 2004-09-15 Time 16:18 Rev Time 0.50
Received By alange Date 2004-09-15 Time 16:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-09 Cont ID  
Sent By alange Date 2004-08-09 Time 15:49 Rev Time 0.50
Received By alange Date 2004-08-09 Time 15:49 Sent To  
Notes
2004-08-09 00:00:00DENIED
  
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2. SHOW SINK AND COUNTER COMPLYING WITH
 FBC 11.4.24
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 TEL: (561)805-6672
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-09-16 Cont ID  
Sent By dpalmer Date 2004-09-16 Time 20:25 Rev Time 0.25
Received By dpalmer Date 2004-09-16 Time 20:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-03 Cont ID  
Sent By csiegber Date 2004-08-30 Time 10:35 Rev Time 0.25
Received By dpalmer Date 2004-08-03 Time 09:19 Sent To  
Notes
2004-08-03 00:00:00******** UNSAT ************
  
 1)NOTE: ELECTRICAL IS OK, HOWEVER THERE
 IS A HANDRAWN PLUMB RISER ON PLANS
 WHICH ARE SIGNED AND SEALED BY AN ARCH.
 PLEASE SEE THIS IS NOT PERMITTED UNDER
 FS 481
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-08-18 Cont ID  
Sent By mcarsill Date 2004-08-18 Time 16:11 Rev Time 0.00
Received By mcarsill Date 2004-08-18 Time 16:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-30 Cont ID  
Sent By csiegber Date 2004-08-30 Time 10:35 Rev Time 0.00
Received By csiegber Date 2004-08-30 Time 10:35 Sent To  
Notes
2004-08-30 00:00:00TO COMM BD#22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-19 Cont ID  
Sent By kstevens Date 2004-08-19 Time 11:10 Rev Time 0.00
Received By kstevens Date 2004-07-30 Time 08:51 Sent To  
Notes
2004-07-30 00:00:00TO COMM BD#58

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-10-07 Cont ID  
Sent By kstevens Date 2004-10-07 Time 11:49 Rev Time 1.00
Received By kstevens Date 2004-09-21 Time 17:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-08-19 Cont ID  
Sent By kstevens Date 2004-08-19 Time 11:00 Rev Time 0.50
Received By kstevens Date 2004-08-19 Time 11:00 Sent To  
Notes
2004-08-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) HAND DRAWN INFORMATION IS NOT PERMIT-
 TED ON SIGNED/SEALED DRAWINGS. FS 481.
 2) SUBMIT A WATER RISER DIAGRAM SHOWING
 POINT OF CONNECTION, PIPE SIZES, AND
 LOCATION OF REQUIRED WATER HAMMER ARRES-
 TORS, (AT WASH MACHINE).
 3) SANITARY RISER DIAGRAM SHOWS AIR AD-
 MITTENCE VALVES FOR BRANCH LINE TO W/M &
 SINK, BUT NOTE ON PLANS STATES, "CONNECT
 2" VENT TO EXISTING VENT @ WATER COOLER"
 PLEASE CORRELATE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]