Plan Review Details - Permit 04071368
Plan Review Stops For Permit 04071368
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-09-21 Cont ID  
Sent By jwitmer Date 2005-09-21 Time 11:14 Rev Time 0.77
Received By jwitmer Date 2005-09-21 Time 11:14 Sent To PC
Notes
2005-09-21 00:00:00CONSTRUCTION BOARD OF ADJUSTMENET &
 APPEAL, CASE# 1282 VARIANCE GRANTED, FOR
 ONE EXIT. PROVISO, MANATORY POSTING THAT
 THE OCCUPANCY IS LIMITED TO 30 PEOPLE
 PER FLOOR. THE FIRE PROTECTION SYSTEM
 SHALL BE CONTINUOUSLY MONITORED AND
 ALWAYS MAINTAINED.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-09-08 Cont ID  
Sent By jwitmer Date 2005-08-22 Time 13:59 Rev Time 1.25
Received By jwitmer Date 2005-08-22 Time 06:32 Sent To  
Notes
2005-08-22 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04071368
 ADD: 809 N DIXIE HWY
 CONT: GABCO
 TEL: (561)644-1434
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISION
 ACTION: DENIED
  
  
 8-22-05 SENT E-MAIL OUT AFTER SITE VISIT
 INDICATED NO SECOND MEANS OF EGRESS IS
 INSTALLED ON THE BUILDING. WAITING ON
 RETURN EMAIL FROM B. O.
 NO EGRESS AS DETERMINED BY THE BOARD OF
 ADJUSTMENT AND APPEAL.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-11-10 Cont ID  
Sent By jwitmer Date 2004-11-03 Time 12:52 Rev Time 3.00
Received By jwitmer Date 2004-11-03 Time 10:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-04 Cont ID  
Sent By jwitmer Date 2004-08-04 Time 14:37 Rev Time 3.00
Received By jwitmer Date 2004-08-04 Time 14:37 Sent To  
Notes
2004-08-04 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04071368
 ADD: 809 N DIXIE HWY
 CONT: DK CONSTRUCTION GROUP
 TEL: (954)347-6365
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) 481.219(2) F.S.A CERTIFICATE OF
 AUTHORIZATION SHALL BE REQUIRED FOR A
 CORPORATION, PARTNERSHIP, OR PERSON
 PRACTICING UNDER A FICTITIOUS NAME,
 OFFERING ARCHITECTURAL SERVICES TO THE
 PUBLIC JOINTLY OR SEPARATELY.
  
 3) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 SEE MECH, ELEC & PLUMB.
  
 4) PROVIDE A SITE PLAN, IT APPEARS THAT
 THE SOUTH SIDE OF THE BUILDING IS
 LOCATED ON THE SOUTH PROPERTY LINE.
 TABLE 600 0-3' AWAY FROM THE PROPERTY
 LINE DOES NOT ALLOW FOR OPENINGS.
  
 5) SHEET A-2 INDICATES 4,697 SQ FT OR
 47 OCCUPANT LOAD. THIS OFFICE SPACE EX-
 CEEDS THE LIMITATIONS FOR SINGLE EXIT.
 SEE FBC 1020.1.
  
 6)1004.1.4 WHERE 2 OR MORE EXITS OR
 EXIT ACCESS DOORS ARE REQUIED, AT LEAST
 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL
 BE PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN 1/2 OF THE LENGTH OF THE MAX-
 IMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED.
 PROVIDE 2 EXIT STAIRWELLS FOR THE
 SECOND FLOOR.
  
 7) EXISTING STAIRS: EXTERIOR AND INTER-
 IOR EXIT STAIRWAYS SHALL BE CONSTRUCTED
 OF NONCOMBUSTIBLE MATERIALSTHROUGHOUT IN
 THE FOLLOWING BUILDINGS:(3) ALL BUILD-
 INGS 3 STORIES IN HEIGHT OR 40 PERSONS
 ABOVE OR BELOW THE LEVEL OF EXIT
 DIXCHARGE.
  
 8) 1006.1.1 EXIT STAIRWAYS BETWEEN
 FLOORS SHALL BE ENCLOSED IN OR SEPERATED
 BY FIRE RESISTANT CONSTRUCTION IN ACCORD
 ANCE WITH 705.2 & 705.1.2.
 1006.1.3.1 PENETRATIONS INTO AND
 THROUGH A STAIRWAY ENCLOSURE ASSEMBLY
 ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, DUCTWORK AND EQUIPMENT NECESSARY
 FOR THE INDEPENDENT STAIR PRESSURIZATION
 SPRINKLER PIPING, STANDPIPES AND ELECTRI
 CALCONDUIT SERVING THE STAIRWAY AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQ IN. SUCH PENETRATIONS SHALL BE PRO
 TECTED IN ACCORDANCE WITH 705.4
  
 9) PROVIDE EITHER THE FIRE SPRINKLER
 PLANS FOR THE 2ND FLOOR OR ELSE COMPLY
 WITH AREA OF REFUGE. 11-4.1.6.1(A)
 NO ALTERATION SHALL BE UNDERTAKEN WHICH
 DECREASES OR HAS THE EFFECT OF DECREAS-
 ING ACCESSIBILITY OR USABILITY BELOW THE
 REQUIREMENTS FOR NEW CONSTRUCTION AT THE
 TIME OF ALTERATION.SEE ALSO 11-4.1.3.11
 FOR REQUIREMENTS.
  
 10)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE
 MECHANICAL EQUIPMENT, APPLIANCES AND SUP
 PORTS THAT ARE EXPOSED TO WIND SHALL BE
 DESIGNED AND INSTALLED TO RESIST THE
 WIND PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
 11) RESTROOMS (A-6) FOR FINISH SCHEDULE:
 1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 12) A-7 INDICATES THE WINDOW SCHEDULE
 BUT THERE IS NO NOTES ABOUT SAFETY GLASS
 FL BLD CODE 2405.2 HAZARDOUS LOCATION
 PROVIDE SAFETY GLASS FOR THIS LOCATION:
 W2,W3 & W4.
  
 13)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A)WINDOWS, W1, W5, & W6.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 14) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 15)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING. PROVIDE
 DETAILS WHERE SHUTTERS WILL BE STORED.
 FBC 1606.4.1.
  
 16)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 17) 1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 18) 1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-07-06 Cont ID  
Sent By dpalmer Date 2005-07-06 Time 15:45 Rev Time 1.00
Received By dpalmer Date 2005-07-06 Time 14:43 Sent To  
Notes
2005-07-06 00:00:00**** NOTES REDLINED 2ND TIME *******
  
  
 1)NOTE: PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTORS ARE STILL BEING SHOWN WITH
 SEC'S ETC UP TO THE FIRST MEANS OF
 DISCONNECT.
  
 250.6,250.24

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-10-25 Cont ID  
Sent By dpalmer Date 2004-10-25 Time 14:38 Rev Time 0.50
Received By dpalmer Date 2004-10-25 Time 13:12 Sent To  
Notes
2004-10-25 00:00:00REDLINED NOTES***
  
 RISER SHOWS EQUIPMENT GROUNDING CONDUCT-
 -ORS FROM METER TO MAINS.
 THIS IS NOT PERMITTED PER 250.6,250.24,
 ONLY AFTER THE FIRST MEANS OF DISC.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-11 Cont ID  
Sent By dpalmer Date 2004-08-11 Time 13:57 Rev Time 1.00
Received By dpalmer Date 2004-08-11 Time 13:46 Sent To  
Notes
2004-08-11 00:00:00********** UNSAT ***********************
  
 1)NOTE PLEASE SEE ONLY ONE SET IF PLANS
 ARE SIGNED AND SEALED.FS 471.025
 PLEASE SEE OTHER; ALL TRADES.
  
 2) NOTE: PLEASE INDICATE AIC RATINGS OF
 MAINS. FUSES ARE NOTED AND INDICATED
 FOR ELEVATOR DISC.
 110.9/215.5
  
 3)NOTE: PLEASE SHOW CONTINUOUS LOADS
 AT 125%.230.42,215.3 ETC
  
  
 4)NOTE: PLEASE SEE 700.16 FOR LIGHTING
 IN ELEV MACHINE/ELEC EQUIPMENT RM.
  
 5)NOTE: PLEASE SEE CIRCUITING ON PLANS,
 SEEMS TO INDICATE CIRCUITS COMING FROM
 TWO SERVICES INTO SAME TENANT SPACE?
 230.2.
 EXISTING RISER FEEDS EXSITING PANEL.
 "L2B" AND NEW RISER/SERVICE FEEDS NEW
 PANELS: ARE THESE NEW PANELS NOT FOR
 NEW TENANT SPACE?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-07-27 Cont ID  
Sent By mwennerg Date 2005-07-27 Time 14:12 Rev Time 0.00
Received By mwennerg Date 2005-07-27 Time 14:12 Sent To  
Notes
2005-07-27 00:00:00REVISIONS DATED 6/20/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-11-23 Cont ID  
Sent By nmccray Date 2004-11-23 Time 12:27 Rev Time 0.00
Received By nmccray Date 2004-11-23 Time 12:27 Sent To  
Notes
2004-11-23 00:00:00LETTER RECIEVED RATED ENCLOSED STAIRS
 AND FIRE SPRINKLER PROTECTED UNDERNEATH

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-11-03 Cont ID  
Sent By nmccray Date 2004-11-02 Time 14:45 Rev Time 0.00
Received By nmccray Date 2004-11-02 Time 14:45 Sent To  
Notes
2004-11-03 00:00:00PROVISO
 ONLY IF THIS BUILDING IS A SINGLE
 TENANT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-08-12 Cont ID  
Sent By mcarsill Date 2004-08-12 Time 16:30 Rev Time 0.00
Received By mcarsill Date 2004-08-12 Time 16:22 Sent To  
Notes
2004-08-12 00:00:001) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) DEBRIS SHALL BE REMOVED FROM THE
 SITE DAILY.
  
 3) SOME FIRE SPRINKLER HEADS NOTED
 ON HALLWAY WALL NEAR DOORS 203,205,
 206. PLEASE REVISE.
  
 4) PLEASE EXPLAIN SINGLE EXIT OPEN
 EXIT STAIR FROM SECOND FLOOR.
  
 5) NO FIRE SPRINKLER IN CLOSET 215.2.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-08-19 Cont ID  
Sent By adarroug Date 2005-08-19 Time 11:14 Rev Time 0.00
Received By adarroug Date 2005-08-19 Time 11:14 Sent To B
Notes
2005-08-19 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-28 Cont ID  
Sent By adarroug Date 2005-06-28 Time 15:46 Rev Time 0.00
Received By adarroug Date 2005-06-28 Time 15:45 Sent To  
Notes
2005-07-01 00:00:00TO "COMM"BD#58
2005-06-28 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-06 Cont ID  
Sent By adarroug Date 2005-05-06 Time 15:35 Rev Time 0.00
Received By adarroug Date 2005-05-06 Time 15:35 Sent To M
Notes
2005-05-06 00:00:00TO "PKRAUSS" BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-08 Cont ID  
Sent By adarroug Date 2005-04-08 Time 10:27 Rev Time 0.00
Received By adarroug Date 2005-04-08 Time 10:27 Sent To M
Notes
2005-04-08 00:00:00TO "PKRAUSS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-18 Cont ID  
Sent By csiegber Date 2004-10-18 Time 17:36 Rev Time 0.00
Received By csiegber Date 2004-10-18 Time 17:36 Sent To  
Notes
2004-10-18 00:00:00TO COMM BD#62

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-20 Cont ID  
Sent By csiegber Date 2004-10-18 Time 17:35 Rev Time 0.00
Received By csiegber Date 2004-07-30 Time 08:10 Sent To  
Notes
2004-07-30 00:00:00TO COMM BD#17

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2005-07-26 Cont ID  
Sent By pkrauss Date 2005-07-26 Time 10:45 Rev Time 0.40
Received By pkrauss Date 2005-07-26 Time 09:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2005-05-16 Cont ID  
Sent By pkrauss Date 2005-05-16 Time 08:37 Rev Time 0.40
Received By pkrauss Date 2005-05-16 Time 08:37 Sent To  
Notes
2005-05-16 00:00:00DENIED:
 PLANS ARE TO HAVE THE PRINTED NAME,
 ADDRESS, AND LICENSE NUMBER OF THE
 ENGINEER.IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING FIRM, PROVIDE
 CERTIFICATE OF AUTHORIZATION NUMBER.
 THIS ALSO APPLIES TO THE ARCHITECT.
 FS471.021, FAC61G15-23.002 (2),
 FS481.221, FAC 61G1-16.004.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-04-11 Cont ID  
Sent By prafter Date 2005-04-11 Time 10:05 Rev Time 0.50
Received By prafter Date 2005-04-11 Time 10:05 Sent To  
Notes
2005-04-11 00:00:00 
 MECH. PLAN REVIEW REVISION.
 CHANGE EXISTING DUCTWORK TO SPIRAL
 DUCT, SWITCH AIR HANDLER AROUND AND
 INSTALL R/A GRILLS.
  
  
 A/C PLAN REVISION MUST REFLECT SAME
 ENG. OF RECORD.
 PLEASE CORRECT AND RESUBMITT.
  
 PAT RAFTER 805/6728 OR 805/6719 PATTY
 KRAUSS.
 PLEASE CALL IF THEAR ANY QUESTION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-11-15 Cont ID  
Sent By pkrauss Date 2004-11-15 Time 16:37 Rev Time 0.40
Received By pkrauss Date 2004-11-15 Time 16:33 Sent To  
Notes
2004-11-15 00:00:00PROVISO:
 AUXILIARY DRAIN PAN SHALL OVERFLOW
 PROTECTION BY MEANS OF A FLOAT SWITCH OR
 A SEPARATE DRAIN LINE THAT TERMINATES AT
 A CONSPICUOUS POINT (INDICATE ON THE
 PLAN TERMINATION OF SECONDARY LINE).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS @ (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-08-20 Cont ID  
Sent By pkrauss Date 2004-08-20 Time 11:15 Rev Time 0.00
Received By jwitmer Date 2004-11-03 Time 10:51 Sent To  
Notes
2004-08-20 00:00:00DENIED:
 1. PLEASE PROVIDE OUTSIDE AIR CALCS PER
 2001 FBC(M) 403.3.
  
 2.NO COMBUSTIBLES ABOVE THE CEILING
 IN THE RETURN AIR PLENUM PER 2001 FBC(M)
 602.2.1.
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 REQUIRED PER 2001 FBC(M) 606.2.2, ALSO
 NOTIFICATION TO ALARM/STROBE IN NORMALLY
 OCCUPIED AREAS.
  
 4.PLANS ARE REQUIRED TO SIGNED, SEALED
 AND DATED BY THE ENGINEER IN ACCORDANCE
 WITH FS 471.025 & FAC 61G15-23.002.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-08-05 Cont ID  
Sent By kstevens Date 2005-08-05 Time 13:18 Rev Time 1.23
Received By kstevens Date 2005-08-05 Time 13:18 Sent To  
Notes
2005-08-05 00:00:00REVISION OK - SHTS P0.1 & P2.1

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-11-22 Cont ID  
Sent By kstevens Date 2004-11-22 Time 10:18 Rev Time 1.15
Received By kstevens Date 2004-11-22 Time 10:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-11-08 Cont ID  
Sent By kstevens Date 2004-11-08 Time 07:50 Rev Time 0.62
Received By kstevens Date 2004-11-08 Time 07:50 Sent To  
Notes
2004-11-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
  
 A) COMMENT FROM PREVIOUS REVIEW HAS NOT
 BEEN ADDRESSED.
 2) STAFF SINK SHALL COMPLY WITH SECTION
 11-4.24 AND ALL SUBSECTIONS. SUBMIT A
 DETAIL SHOWING REQUIREMENTS. SHOW:
 A) HEIGHT 4.24.2
 B) KNEE CLEARANCE 4.24.3
 C) SINK DEPTH 4.24.4
 D) CLEAR FLOOR SPACE - SHALL BE PROVIDED
 IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH, AND SHALL EXTEND A MAXIMUM OF
 19" UNDERNEATH THE SINK. (FIG 32).
 E) EXPOSED PIPES AND SURFACES. 4.24.6
 - RESPONSE STATES "REFER TO
 ARCHITECTURAL PLANS", BUT UNABLE TO
 LOCATE DETAIL FOR SINK.
 *****NEW COMMENT*****
 B) SUBMIT A DETAIL FOR THE DRINKING
 FOUNTAIN SHOWING COMPLIANCE WITH 11-4.15
  
 AND ALL SUBSECTIONS. SHOW:
 1) SPOUT HEIGHT 4.15.2
 2) CLEARANCES 4.15.5 WITH CLEAR FLOOR
 SPACE.
 3) ACCESSIBILITY FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
 11-4.1.3(10)(A).
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-08-18 Cont ID  
Sent By kstevens Date 2004-08-18 Time 18:14 Rev Time 0.50
Received By kstevens Date 2004-08-18 Time 18:14 Sent To  
Notes
2004-08-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) MINIMUM FACILITIES REQUIRES A DRINK-
 ING FOUNTAIN. TABLE 403.1 - ALSO SEE
 SECTION 410.1
 2) STAFF SINK SHALL COMPLY WITH SECTION
 11-4.24 AND ALL SUBSECTIONS. SUBMIT A
 DETAIL SHOWING REQUIREMENTS.
 3) SHT P2.1 WATER FILTER SHALL COMPLY
 WITH NSF-42. SUBMIT MANUF. SPECIFICATION
 SHEET. SECTION 104.2.1
 4) SHT P2.1 MORE INFORMATION IS REQUIRED
 FOR THE CONDENSATE PUMPING SYSTEM. ALL
 CONDENSATE PUMPING SYSTEMS SHALL COMPLY
 WITH SECTION 712. SUBMIT A DETAIL SHOW-
 ING ALL COMPONETS OF THE PUMPING SYSTEM.
 SECTION 104.2.1
 5)A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]