Plan Review Details - Permit 04071290
Plan Review Stops For Permit 04071290
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-08-06 Cont ID  
Sent By lsmith Date 2004-08-06 Time 11:24 Rev Time 2.00
Received By lsmith Date 2004-08-06 Time 11:24 Sent To  
Notes
2004-08-06 00:00:00BUILDING PLAN REVIEW: PROVISO
  
 1. A NOTICE OF COMMENCEMENT MUST BE
 FILED AT THE COUNTY CLERK OFFICE AND A
 COPY SUBMITTED BEFORE A PERMIT CAN BE
 ISSUED.
  
 2. SUBMIT MANUFACTURERS SHEETS ON THE
 GAS BBQ TO BE INSTALLED.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-12-07 Cont ID  
Sent By dpalmer Date 2005-12-07 Time 14:40 Rev Time 0.00
Received By dpalmer Date 2005-12-07 Time 14:32 Sent To  
Notes
2005-12-07 00:00:00REDLINED NFPA 72
 11.8.3.5

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-10-21 Cont ID  
Sent By dpalmer Date 2005-10-21 Time 15:06 Rev Time 1.00
Received By dpalmer Date 2005-10-21 Time 14:22 Sent To  
Notes
2005-10-21 00:00:00******** UNSAT *********
  
 1)NOTE: PLEASE SEE LOAD ON PANEL "C"
 EXCEEDS FEEDER AND OCP FOR PANEL.
 PLEASE ALSO INDICATE ALL CONTINUOUS
 LOADS AT 125%.
 215.3,230.42 ETC.
 PLEASE REVISE 240.4,310.16,310.15B6
  
 2)NOTE: PLEASE SEE BOTH PANELS "A" AND
 "B" INDICATE BEING MLO.
 PLEASE SEE RISER SHOWS THESE AS MCB.
 PLEASE CORRELATE AND INDICATE MCB'S AS
 REQIRED 230.70
  
 3)NOTE: PLEASE SEE GROUNDING ELECTRODE
 IS NOW SHOWN GOING TO SLAB, HOWEVER THIS
 SHOULD BE NOTED AS FOOTER STEEL. 250.50
  
 4)NOTE: PLEASE CORRELATE RECESSED LTS ON
 LOAD CALCULATIONS AND THE NUMBER OF LTS
 SHOWN ON PLANS.
 215.5,220.3
  
  
 ** NOTE ALL SD'S ARE TO BE INSTALLED
 WITH IN THE HIGHEST POINT OF A FLAT
 CEILING.
 PLEASE BE SURE TO VERIFY INSTALLATION IN
 FIELD.
 NFPA-72 8-1
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-05-16 Cont ID  
Sent By dpalmer Date 2005-05-16 Time 06:57 Rev Time 0.25
Received By dpalmer Date 2005-05-16 Time 06:57 Sent To  
Notes
2005-05-16 00:00:00 
 REV OK.
 TRIED TO LEAVE MESSAGE AT 6:58AM ON 5/16
 NO ANSWERING MACHINE/OR VOICE MAIL.
 PLANS UNDER "T" FOR PU.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-04-20 Cont ID  
Sent By dpalmer Date 2005-04-20 Time 07:22 Rev Time 0.30
Received By dpalmer Date 2005-04-20 Time 07:22 Sent To  
Notes
2005-04-20 00:00:00******* UNSAT *******
  
 1)NOTE: PLEASE SEE PANEL "C" IS MISSING
 FROM PLANS. PLEASE SHOW LOCATION OF
 PANEL "C" ON PLANS.
 215.5
  
 2)NOTE: PLEASE SEE RECEPT FOR WHIRLPOOL
 TUB NOT SHOWN AS GFI/GFI PROTECTED.
 680.24
  
 3)NOTE: PLEASE SEE MISSING GFI ON
 POWDER/BATHRM. 210.52D, 210.8
  
 4)NOTE: PLEASE SEE NOTE #2 ON GEN NOTES
 MENTIONS SD'S ON KIT/BATH LIGHTING
 CIRCUITS, HOWEVER THESE ARE REQUIRED TO
 HAVE ARC FAULT PROTECTION PER 210.12
 2002 NEC.
 IF ON KIT/BATH LIGHTING CIRCUIT(S),
 THESE WOULD ALSO BE REQUIRED TO BE AFCI.
  
 PLEASE KNOW, SINCE PLANS ARE IN FOR
 FINAL, ALL ITEMS MUST BE CORRECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-08-03 Cont ID  
Sent By jleech Date 2004-07-31 Time 08:48 Rev Time 0.50
Received By dpalmer Date 2004-08-03 Time 09:01 Sent To M
Notes
2004-08-03 00:00:00******** REDLINED ************
  
 1)NOTE: PLEASE SEE AHU#3 AND MEANS OF
 DISC AND OCP SHOWN ON CLOTHES CLOSET.
 THIS IS NOT PERMITTED.
 PLEASE SEE 240.24D AND 110.26

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-11-28 Cont ID  
Sent By adarroug Date 2005-11-28 Time 15:50 Rev Time 0.00
Received By adarroug Date 2005-11-28 Time 15:50 Sent To E
Notes
2005-11-28 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-10-12 Cont ID  
Sent By adarroug Date 2005-10-12 Time 13:05 Rev Time 0.00
Received By adarroug Date 2005-10-12 Time 13:05 Sent To E
Notes
2005-10-12 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-10 Cont ID  
Sent By adarroug Date 2005-05-10 Time 12:15 Rev Time 0.00
Received By adarroug Date 2005-05-10 Time 12:15 Sent To E
Notes
2005-05-10 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-14 Cont ID  
Sent By adarroug Date 2005-04-14 Time 17:46 Rev Time 0.00
Received By adarroug Date 2005-04-14 Time 17:46 Sent To E
Notes
2005-04-14 00:00:00TO "DPALMER"DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-01 Cont ID  
Sent By mjacobs Date 2005-02-01 Time 14:30 Rev Time 0.00
Received By mjacobs Date 2005-02-01 Time 14:30 Sent To M
Notes
2005-02-01 00:00:00TO "M/AC"/REVISIONS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-06 Cont ID  
Sent By mmclean Date 2004-07-29 Time 16:07 Rev Time 0.00
Received By lsmith Date 2004-07-28 Time 14:36 Sent To  
Notes
2004-07-29 00:00:00TO SFD RACK/E
2004-07-28 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-02-09 Cont ID  
Sent By prafter Date 2005-02-09 Time 11:31 Rev Time 1.50
Received By prafter Date 2005-02-09 Time 11:31 Sent To  
Notes
2005-02-09 00:00:00PROVISO:
 PROVIDE FOR COMBUSTION AIR FOR DRYER
 IF REQUIRED.
 GAS DRYED INFORMATION ,NOT WITH PLAN
 PACKAGE.
 PAT RAFTER 2/9/05 651/805/6728.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-08-07 Cont ID  
Sent By dpalmer Date 2004-08-03 Time 09:01 Rev Time 0.50
Received By rregueir Date 2004-08-07 Time 10:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-07-31 Cont ID  
Sent By jleech Date 2004-07-31 Time 08:48 Rev Time 0.33
Received By jleech Date 2004-07-31 Time 08:48 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-07-29 Cont ID  
Sent By mmclean Date 2004-07-29 Time 16:07 Rev Time 0.00
Received By mmclean Date 2004-07-29 Time 16:07 Sent To I
Notes
***NONE***