Plan Review Details - Permit 04071255
Plan Review Stops For Permit 04071255 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2004-08-11 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2004-08-11 |
Time |
07:19 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2004-08-11 |
Time |
06:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2004-08-05 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-08-10 |
Time |
17:19 |
Rev Time |
1.00 |
Received By |
btrobaug |
Date |
2004-08-05 |
Time |
10:33 |
Sent To |
|
|
Notes |
2004-08-05 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW SERVICE EQUIPMENT BEING | | INSTALLED. MAINS/BRKRS AND PANELS ARE | | ALL TO BE RATED FOR THE AVAILABLE FAULT | | CURRENT PER 110.9. | | | | 2} PLEASE SHOW CONDUIT SIZE AND TYPE ON | | RISER. | | | | 3} PLEASE SUBMIT A PANEL SCHEDULE WITH | | WIRE AND BREAKER SIZES SO BC COMPLIANCE | | CAN BE DETERMINED.(IG: 210.12, | | 210.11(C)(3), 210.52(B), ETC.) | | | | 4} PLEASE SHOW OUTLET SPACING PER | | 210.52. 2',6',12' RULES. | | | | 5} PLEASE SEE RECEPTS SERVING | | KITCHEN COUNTERSPACE TO MEET 210.52C- | | SEC'S 1,2,3,4 AND 5. | | | | 6} SMOKE DETECTORS ARE REQUIRED | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | SEE 8-1.4.2 NFPA-72 FOR ADDITIONAL | | SPACING ISSUES, 1999 ED. | | | | 7} THE RANGE FEEDER MUST COMPLY WITH | | 250.140, 4 WIRE. | | | | 8} THE LAUNDRY CIRCUIT MUST BE | | CALCULATED @ 1500VA PER 220.16(B). | | | | ALL INFORMATION/DRAWINGS/SPECIFICATIONS | | AND ACCOMPANYING DATA SHALL BEAR THE | | NAME AND SIGNATURE OF THE PERSON RESPON- | | SIBLE FOR THE DESIGN. SECTION 104.2.1 | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2004-08-10 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-08-10 |
Time |
17:19 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-08-10 |
Time |
17:19 |
Sent To |
E |
|
Notes |
2004-08-10 00:00:00 | TO BT DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2004-07-28 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-07-28 |
Time |
11:44 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-07-28 |
Time |
11:44 |
Sent To |
E |
|
Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy