Plan Review Details - Permit 04071144
Plan Review Stops For Permit 04071144
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-10-26 Cont ID  
Sent By rbrown Date 2004-10-26 Time 07:47 Rev Time 0.00
Received By rbrown Date 2004-10-26 Time 07:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-30 Cont ID  
Sent By rbrown Date 2004-08-27 Time 16:31 Rev Time 0.00
Received By rbrown Date 2004-08-27 Time 11:18 Sent To Z
Notes
2004-08-27 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC 1606.1.7WIND LOAD.THE PLANS
 SHALL STATE THE BASIC WIND SPEED, WIND
 IMPORTANCE FACTOR, AND WIND EXPOSURE
 CATEGORY USED TO DETERMINE THE DESIGN
 WIND PRESSURES FOR THE LIGHT POLE
 DESIGN/SPECIFICATION.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-03-08 Cont ID  
Sent By dpalmer Date 2005-03-08 Time 11:17 Rev Time 0.00
Received By dpalmer Date 2005-03-08 Time 11:17 Sent To  
Notes
2005-03-08 00:00:00REV FOR SOFFIT SCONCE LT AND SITE
 LIGHTING./

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-11-24 Cont ID  
Sent By dpalmer Date 2004-11-24 Time 06:12 Rev Time 0.25
Received By dpalmer Date 2004-11-24 Time 06:10 Sent To  
Notes
2004-11-24 00:00:00NEED TO VERIFY PLANS WITH BLDG REVIEW
 BEFORE ISSUE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-10-06 Cont ID  
Sent By dpalmer Date 2004-10-06 Time 20:54 Rev Time 0.25
Received By dpalmer Date 2004-10-06 Time 20:51 Sent To  
Notes
2004-10-06 00:00:00********* UNSAT 2ND REVIEW **********
  
 1)NOTE: PLEASE SEE PLANS ARE REQUIRED TO
 BE SIGNED,DATED AND SEAL BY THE ENGINEER
 OF RECORD . FS 471.025
 PLEASE SEE PLANS ARE PHOTOCOPIES OF WHAT
 APPEARS TO BE SIGNED AND SEALED PLANS???
  
 2)NOTE: PLEASE SEE CONTINUOUS LOADS ARE
 TO BE SHOWN AT 125%.
 215.3,230.42 ETC
  
 3)NOTE: PLEASE CLARIFY WHERE POLE INFOR-
 -MATION AND WIND LOADS ARE NOTED ON ELEC
 -TRICAL PLANS?
 IS ABOVE INFORMATION ON OTHER SHEETS.
 COULD ONLY LOCATE NOTE ON SP-1??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-27 Cont ID  
Sent By mamini Date 2004-08-24 Time 13:40 Rev Time 0.33
Received By dpalmer Date 2004-08-27 Time 15:49 Sent To ENG
Notes
2004-08-27 00:00:00*********** UNSAT ********
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002 AND
 FS 471.023 FOR ALL REQUIRED INFORMATION
 TO BE ON TITLE BLOCK.
  
 2)NOTE: PLEASE SEE BLDG REVIEW COMMENTS.
 PLEASE PROVIDE ALL INFORMATION REQUIRED
 FOR WIND LOADS FOR LTS/ LT POLES.
 140 MPH FBC.
  
 3)NOTE: PLEASE SEE NO CIRCUITING OR
 INFORMATION WAS SUBMITTED ON FEEDING
 LT POLES ETC.
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2004-08-24 Cont ID  
Sent By csiegber Date 2004-08-31 Time 16:43 Rev Time 1.00
Received By mamini Date 2004-08-24 Time 13:22 Sent To E
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-08-04 Cont ID  
Sent By csiegber Date 2004-08-23 Time 11:01 Rev Time 1.00
Received By mamini Date 2004-08-04 Time 08:34 Sent To FIRE
Notes
2004-08-04 00:00:00FAILED:
 1. CIVIL SITE PLANS MUST BE REVIEWED AND
 AND APPROVED FOR ALL THE CONNECTION TO
 THE SREVICES, NO METER, DDCV FOR FIRE
 LINE OR BACKFLOWS FOR DOMESTIC ARE SHOWN
 SHEET 6 OF 10, NOTE THAT A SEPARATE
 BACKFLOWS FOR EACH BUILDING PER PLUMBING
 CODE IS REQUIRED.
 2. PLEASE PROVIDE STORM WATER CALC. FOR
 OUR REVIEW AND APPROVAL, INCLUDE
 PERVIOUS AND IMPERVIOUS AREA, BUILDING
 AREA FOR THE ENITRE SITE.
 3. WORK IN PUBLIC R.O.W REQUIRES A
 SEPARATE PERMIT FROM THE PUBLIC
 UTILITIES AND ENGINEERING, WINDEL PALMER
 494-1086 AND FROM PB COUNTY WILL BE
 REQUIRED.
 4. A SEPARATE PERMIT FOR SITE ELECTRICAL
 WORK IS REQUIRED.
 5. LANDSCAPING PLAN MUST BE REVIEWED AND
 APPROVED BY PLANNING AND ZONING, IT
 SHOULD BE PART OF BUILDING PERMIT
 APPLICATION SBMITTALS.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-12-01 Cont ID  
Sent By nmccray Date 2004-12-01 Time 14:53 Rev Time 0.00
Received By nmccray Date 2004-12-01 Time 14:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-09-01 Cont ID  
Sent By nmccray Date 2004-09-01 Time 11:17 Rev Time 0.00
Received By nmccray Date 2004-09-01 Time 11:17 Sent To  
Notes
2004-09-01 00:00:00************DENIED**********************
  
 PLEASE SHOW THE FIRE DEPT CONNECTIONS
 FOR EACH BUILDING.
  
 NATE MCCRAY, CAPTAIN
 835-2910 OR 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-08-04 Cont ID  
Sent By mamini Date 2004-08-04 Time 10:03 Rev Time 0.00
Received By nmccray Date 2004-08-04 Time 11:59 Sent To ENG
Notes
2004-08-04 00:00:00*******DENIED***************************
 1) PLANS DO NOT SHOW FIRE DEPARTMENT
 CONNECTIONS (FDC).
  
 2) FDC IS TO BE LOCATED NO MORE THAN 150
 FEET FROM A FIRE HYDRANT.
  
 NATE MCCRAY, CAPTAIN
 835-2910 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-03-03 Cont ID  
Sent By adarroug Date 2005-03-03 Time 14:55 Rev Time 0.00
Received By adarroug Date 2005-03-03 Time 14:55 Sent To E
Notes
2005-03-03 00:00:00TO DPALMER DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mjacobs Date 2004-11-19 Time 11:14 Sent To  
Notes
2004-11-19 00:00:00SENT TO COMM BD#52

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-05 Time 16:00 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 16:00 Sent To  
Notes
2004-10-05 00:00:00TO COMM BD#18

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-08-31 Cont ID  
Sent By csiegber Date 2004-08-31 Time 16:43 Rev Time 0.00
Received By csiegber Date 2004-08-31 Time 16:43 Sent To ENG
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-30 Cont ID  
Sent By csiegber Date 2004-08-30 Time 09:12 Rev Time 0.00
Received By csiegber Date 2004-08-30 Time 09:12 Sent To Z
Notes
2004-08-30 00:00:00TO MM/NEEDS LANDSCAPING REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-23 Cont ID  
Sent By csiegber Date 2004-08-23 Time 11:01 Rev Time 0.00
Received By csiegber Date 2004-08-23 Time 11:01 Sent To ENG
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-28 Cont ID  
Sent By csiegber Date 2004-07-28 Time 12:07 Rev Time 0.00
Received By csiegber Date 2004-07-28 Time 12:07 Sent To ENG
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2004-12-02 Cont ID  
Sent By jroach Date 2004-12-02 Time 08:44 Rev Time 0.00
Received By jroach Date 2004-12-02 Time 08:44 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2004-08-31 Cont ID  
Sent By jroach Date 2004-08-31 Time 15:49 Rev Time 0.00
Received By jroach Date 2004-08-31 Time 15:49 Sent To  
Notes
2004-08-31 00:00:008/31/2004 ***FAILED***
  
 1) MODIFY LANDSCAPE PLAN TO PROVIDE A
 VINE ALONG THE NORTH SIDE OF THE
 DUMPSTER AS REQUIRED BY FORMAL SITE
 PLAN REVIEW APPROVAL LETTER DATED
 6/22/2004.
  
 2) CORRECT NORTH ARROW TO REFLECT
 PROPER DIRECTION.
  
 QUESTIONS, CALL JOHN ROACH, PLANNER AT
 561.822.1448

Review Stop Z ZONING
Rev No 2 Status P Date 2004-10-13 Cont ID  
Sent By jroach Date 2004-10-13 Time 16:51 Rev Time 0.00
Received By jroach Date 2004-10-13 Time 16:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-08-31 Cont ID  
Sent By jroach Date 2004-08-31 Time 15:54 Rev Time 0.00
Received By jroach Date 2004-08-31 Time 15:54 Sent To  
Notes
2004-08-31 00:00:008/31/2004 ***FAILED***
  
 1) PROVIDE A PARKING DETAIL THAT
 CONFORMS TO ARTICLE XV, SECTION 94-485
 AND ARTICLE XIV, SECTION 94-443 OF THE
 ZONING AND LAND DEVELOPMENT
 REGULATIONS.ALL PARKING SPACES SHALL
 BE DOUBLE-STRIPED AND THE BACK FACE OF
 THE WHELL STOP SHALL BE TWO (2) FEET
 FROM THE CURB.
  
 QUESTIONS, CALL JOHN ROACH, PLANNER AT
 561.822.1448