Plan Review Details - Permit 04071122
Plan Review Stops For Permit 04071122
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-09-20 Cont ID  
Sent By mjacobs Date 2004-09-20 Time 15:54 Rev Time 2.00
Received By mjacobs Date 2004-09-20 Time 15:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-06 Cont ID  
Sent By pkrauss Date 2004-09-20 Time 12:48 Rev Time 3.00
Received By mjacobs Date 2004-08-06 Time 12:42 Sent To M
Notes
2004-08-06 00:00:00BUILDING PLAN REVIEW
 PERMIT:04071122
 ADD: 6718 FOX HOLLOW DRIVE
 CONT: RIF GROUP
 TEL: (561)997-5760
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION : DENIED.
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) PLEASE SUBMIT PRODUCT APPROVALS FOR
 ALL SIMPSON CONNECTORS AND STRAPS.
 SUBMIT 2 COPIES OF PRODUCT APPROVALS
 FOR GARAGE DOOR.
 MASONITE DOOR NEEDS PRODUCT APPROVAL.
 ONLY SPECS SUBMITTED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE
 WEBSITEAT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3) PLEASE SHOW THE ATTIC ACCESS
 DIMENTIONS. FBC. SEC.2309.6
  
 4) DOOR BETWEEN ATRIUM AND ZERO LOT
 LINEIS NOT LISTED ON THE DOOR SCHEDULE.
 ALSO SHOW DOOR RATING AND PRODUCT
 APPROVALS.
  
 5) THE DEN/BRM #4 WILL NEED AN
 EMERGENCYESCAPE RESCUE OPENING. SUCH
 OPENINGS
 NOT PERMITTED ON ZERO LOT LINE.
 BEDROOM NOT PERMITTED AT THIS LOCATION.
 SEE FBC. SEC. 1005.4 AND SEC.1005.4.2
  
 6. SUBMIT AN EMERGENCY ESCAPE EASEMENT
 FOR ZERO LOT LINE SIDE.
  
 7. BASED ON SBCCI BUIDING VALUATION
 DATA THE BUILDING VALUATION HAS BEEN
 CHANGED TO $271,152.
 A/C 76.96 PER SQ. FT. X 3096 =$235959
 OTHER $41.60 PER SQ.FT. X 846 =$35193
 ADDITION PERMIT FEES ARE DUE. $210.36
  
 8. SUBMIT PRODUCT APPROVALS FOR 1HR
 GLASS BLOCK.
  
 9. PLEASE DATE UNDER OWNER/AGENT ON
 ENERGY CALS.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 MYRON JACOBS
 BUILDING PLAN REVIEW
 TEL: (561)805-6726
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-08-23 Cont ID  
Sent By dpalmer Date 2005-08-23 Time 07:13 Rev Time 0.25
Received By dpalmer Date 2005-08-23 Time 07:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-08-03 Cont ID  
Sent By dpalmer Date 2005-08-03 Time 14:29 Rev Time 0.30
Received By dpalmer Date 2005-08-03 Time 14:29 Sent To  
Notes
2005-08-03 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEERISER DIAGRAM HAS
 BEEN REVISED TO INDICATE NO "POOL
 PANEL", HOWEVER MAIN PANEL STILL SHOWS
 POOL PANEL?
 PLEASE CORRELATE.215.5
  
  
 2)NOTE: PLEASE SEE REFERENCE TO 1999 NEC
 FOR ARC FAULT PROTECTION.
 210.12
  
  
 3)NOTE: PLEASE SEE PLANS DO NOT INDICATE
 THE NEW "MAIN DISCONNECT" AS SHOWN ON
 RISER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-09-16 Cont ID  
Sent By dpalmer Date 2004-09-16 Time 18:05 Rev Time 0.33
Received By dpalmer Date 2004-09-16 Time 18:05 Sent To P
Notes
2004-09-16 00:00:00** NOTES REDLINED ***
  
 SD'S SHOWN ON TWO CIRCUITS.
  
 GEC TO FT STEEL. SLAB SHOWN.
  
 AWG FOR 60A AHU, SHOWN AS #8. 310.16 #6.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-08-02 Cont ID  
Sent By csiegber Date 2004-09-15 Time 14:36 Rev Time 0.50
Received By dpalmer Date 2004-08-02 Time 15:23 Sent To M
Notes
2004-08-02 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 NEC, ARC FAULT PROTECTIONS IS ON
 BRANCH CIRCUIT, NOT AT/IN DEVICES IN
 BEDRMS.
 210.12B
  
 3)NOTE: PLEASE SEE FOOTER STEEL AND
 COLD WATER PIPE TO SHOWN AS PART OF
 GROUNDING ELECTRODE SYSTEM. 250.50
  
 4)NOTE: PLEASE SEE 110.26 FOR CLEARENCE
 OF DISC FOR COND UNIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-08-19 Cont ID  
Sent By adarroug Date 2005-08-19 Time 10:47 Rev Time 0.00
Received By adarroug Date 2005-08-19 Time 10:47 Sent To E
Notes
2005-08-19 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-01 Cont ID  
Sent By adarroug Date 2005-08-01 Time 15:59 Rev Time 0.00
Received By adarroug Date 2005-08-01 Time 15:59 Sent To E
Notes
2005-08-01 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-01 Cont ID  
Sent By mjacobs Date 2005-02-01 Time 14:13 Rev Time 0.00
Received By mjacobs Date 2005-02-01 Time 14:13 Sent To M
Notes
2005-02-01 00:00:00TO "M/AC" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-09-15 Cont ID  
Sent By csiegber Date 2004-09-15 Time 14:36 Rev Time 0.00
Received By csiegber Date 2004-09-15 Time 14:36 Sent To E
Notes
2004-09-15 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-07 Cont ID  
Sent By mmclean Date 2004-07-28 Time 16:56 Rev Time 0.00
Received By csiegber Date 2004-07-28 Time 11:58 Sent To  
Notes
2004-07-29 00:00:00TO SFR RACK/E
2004-07-28 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-02-09 Cont ID  
Sent By prafter Date 2005-02-09 Time 12:26 Rev Time 1.50
Received By prafter Date 2005-02-09 Time 12:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-09-20 Cont ID  
Sent By pkrauss Date 2004-09-20 Time 12:47 Rev Time 0.30
Received By pkrauss Date 2004-09-20 Time 12:19 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-08-07 Cont ID  
Sent By jleech Date 2004-09-18 Time 11:16 Rev Time 0.50
Received By rregueir Date 2004-08-07 Time 09:50 Sent To  
Notes
2004-08-07 00:00:00-----------------DENIED-----------------
 NO MECHANICAL PLANS OR MANUAL J SUB-
 MITTED WITH THIS PERMIT APPLICATION
  
 ANY QUESTIONS PLEASE CALL:
 RONALD J REGUEIRO
 561-805-6734

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-09-18 Cont ID  
Sent By jleech Date 2004-09-18 Time 11:16 Rev Time 0.33
Received By jleech Date 2004-09-18 Time 11:16 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-07-31 Cont ID  
Sent By dpalmer Date 2004-09-16 Time 18:05 Rev Time 0.50
Received By jleech Date 2004-07-31 Time 07:24 Sent To E
Notes
2004-07-31 00:00:00DENIED;
 RISER DIAGRAM DOES NOT REFLECT FLOOR
 PLAN AND HAS CODE VIOLATIONS.
 TWO WAY CLEANOUT REQUIRED WITHIN THREE
 FEET OF BUILDING. SEE RED LINES ON
 DRAWINGS
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2004-07-28 Cont ID  
Sent By mmclean Date 2004-07-28 Time 16:56 Rev Time 0.00
Received By mmclean Date 2004-07-28 Time 16:56 Sent To I
Notes
***NONE***