Plan Review Details - Permit 04071021
Plan Review Stops For Permit 04071021
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-08-26 Cont ID  
Sent By btrobaug Date 2004-08-26 Time 09:25 Rev Time 0.50
Received By btrobaug Date 2004-08-26 Time 09:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-07-26 Cont ID  
Sent By csiegber Date 2004-08-23 Time 11:36 Rev Time 0.50
Received By btrobaug Date 2004-07-26 Time 16:36 Sent To  
Notes
2004-07-26 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SUBMIT CONDUIT & WIRE SIZE FOR ALL
 NEW WIRING BEING INSTALLED OR EXISTING
 WIRING BEING REUSED.
  
 2} INDICATE THE NAMEPLATE RATING OF THE
 UNIT(S) BEING INSTALLED.IF ADDED UNITS
 OR LARGER REPLACEMENT UNITS, PROVIDE
 LOAD CALCS.
  
 3} INDICATE CIRCUIT NUMBERS BEING USED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-23 Cont ID  
Sent By csiegber Date 2004-08-23 Time 11:36 Rev Time 0.00
Received By csiegber Date 2004-08-23 Time 11:36 Sent To E
Notes
2004-08-23 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-23 Cont ID  
Sent By lsmith Date 2004-07-23 Time 12:19 Rev Time 0.00
Received By lsmith Date 2004-07-23 Time 12:19 Sent To E
Notes
***NONE***