Plan Review Details - Permit 04071011
Plan Review Stops For Permit 04071011
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date   Cont ID  
Sent By   Date 2004-11-12 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2004-11-12 00:00:00REVISION OK LM

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-11-04 Cont ID  
Sent By jwitmer Date 2004-11-04 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2004-11-04 Time 07:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-09-20 Cont ID  
Sent By jwitmer Date 2004-09-20 Time 09:56 Rev Time 1.55
Received By jwitmer Date 2004-09-20 Time 08:46 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-03 Cont ID  
Sent By jwitmer Date 2004-08-03 Time 14:14 Rev Time 2.22
Received By jwitmer Date 2004-08-03 Time 14:13 Sent To  
Notes
2004-08-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04071011
 ADD: 315 S OLIVE AV SUITE 104
 CONT: RAPP CONSTRUCTION
 TEL: (561)248-6411
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) MISSING ELECTRICL PAGE? THERE IS NO
 ELECTRIC SHOWN FOR THE CORRESPONDING
 A3.1 PAGE. NO EXIT SIGNS CAN BE IDENTI-
 FIED ON THE CORRIDORS, 140, UNNUMBERED
 CORRIDOR LINKING WITH 140 TO 131, 128
 AND 132.
  
 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3) UNISEX RESTROOM SHEET 8.2 GRAB BAR
 BEHIND THE WATERCLOSET, THE DIMENSION IS
 3'-0" BUT THE PLAN IS DRAWN SHORTER?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-11-10 Cont ID  
Sent By btrobaug Date 2004-11-10 Time 16:12 Rev Time 0.00
Received By btrobaug Date 2004-11-10 Time 15:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-10-27 Cont ID  
Sent By dpalmer Date 2004-10-27 Time 06:08 Rev Time 0.25
Received By dpalmer Date 2004-10-27 Time 06:05 Sent To  
Notes
2004-10-27 00:00:00REV ON E-1,E-2 OK.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-08-30 Cont ID  
Sent By dpalmer Date 2004-08-30 Time 15:23 Rev Time 0.33
Received By dpalmer Date 2004-08-30 Time 15:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-07-27 Cont ID  
Sent By dpalmer Date 2004-07-27 Time 14:02 Rev Time 0.50
Received By dpalmer Date 2004-07-27 Time 14:02 Sent To  
Notes
2004-07-27 00:00:00********** NOTES REDLINED ************
  
 1)NOTE: PLEASE SEE 210.63 FOR MISSING
 ROOFTOP GFI RECEPT.
  
 2)NOTE: PLEASE CORRELATE ALL OCP, AWG
 AND LOADS FOR AHU'S/ A/C SYSTEMS.
 PLEASE SEE 424.3B FOR SIZING OF OCP.
  
 THE ABOVE HAS BEEN REDLINED AND THERE IS
 NO NEED FOR CORRECTION AT THIS TIME.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 ELETCRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2004-11-23 Cont ID  
Sent By nmccray Date 2004-11-23 Time 10:04 Rev Time 0.00
Received By nmccray Date 2004-11-23 Time 10:04 Sent To  
Notes
2004-11-23 00:00:00REVISION BLDG/ELEC/MECH DATED 10-12-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-11-10 Cont ID  
Sent By mcarsill Date 2004-11-10 Time 17:03 Rev Time 0.00
Received By mcarsill Date 2004-11-10 Time 17:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-09-16 Cont ID  
Sent By mcarsill Date 2004-09-16 Time 12:16 Rev Time 0.00
Received By mcarsill Date 2004-09-16 Time 12:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-07-30 Cont ID  
Sent By mcarsill Date 2004-07-30 Time 10:01 Rev Time 0.00
Received By mcarsill Date 2004-07-30 Time 10:01 Sent To  
Notes
2004-07-30 00:00:001) IT WOULD APPEAR THAT ADDITIONAL
 EXIT SIGNS ARE NEEDED IN CORRIDOR 128
 AND 132.
  
 2) ARE THERE ANY EXISTING EMERGENCY
 LIGHTS IN RESTROOMS.
  
 3) PLEASE EXPLAIN ABANDONED EXISTING
 STAIRS NOTE.
  
 4) ANY FIRE ALARM EQUIPMENT PRESENT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-25 Cont ID  
Sent By csiegber Date 2004-10-25 Time 11:49 Rev Time 0.00
Received By csiegber Date 2004-10-25 Time 11:49 Sent To  
Notes
2004-10-25 00:00:00TO COMM BD#2

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-10-20 Cont ID  
Sent By csiegber Date 2004-10-20 Time 16:52 Rev Time 0.00
Received By csiegber Date 2004-10-20 Time 16:52 Sent To  
Notes
2004-10-20 00:00:00TO COMM BD#

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-19 Cont ID  
Sent By csiegber Date 2004-08-19 Time 14:24 Rev Time 0.00
Received By csiegber Date 2004-08-19 Time 14:24 Sent To  
Notes
2004-08-19 00:00:00TO COMM BD#32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-23 Cont ID  
Sent By lsmith Date 2004-07-23 Time 12:25 Rev Time 0.00
Received By lsmith Date 2004-07-23 Time 12:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-11-05 Cont ID  
Sent By pkrauss Date 2004-11-05 Time 14:16 Rev Time 0.45
Received By pkrauss Date 2004-11-05 Time 13:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-09-17 Cont ID  
Sent By pkrauss Date 2004-09-17 Time 14:26 Rev Time 0.45
Received By pkrauss Date 2004-09-17 Time 14:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-08-05 Cont ID  
Sent By pkrauss Date 2004-08-05 Time 15:50 Rev Time 0.45
Received By pkrauss Date 2004-08-05 Time 15:18 Sent To  
Notes
2004-08-05 00:00:00DENIED:
 PLEASE PROVIDE ADDITIONAL INFORMATION
 ON A/C SYSTEM #1 & 3.PROVIDE
 MANUFACTURER CONFIRMATION THAT AHU 1 &
 3 DOES NOT HAVE THE CAPACITY TO OUTPUT
 GREATER THAN 2,000 CFM.
  
 PLAN SHEET M1, DUCT & GRILLE SIZE
 MISSING ON 1 BRANCH LINE FROM SYSTEM
 2 AND ONE BRANCH LINE FROM SYSTEM 1.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status N Date 2004-11-17 Cont ID  
Sent By kstevens Date 2004-11-17 Time 15:19 Rev Time 0.33
Received By kstevens Date 2004-11-17 Time 15:19 Sent To  
Notes
2004-11-17 00:00:00NO PLUMBING REVISION SHOWN

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-09-16 Cont ID  
Sent By kstevens Date 2004-09-16 Time 18:53 Rev Time 0.50
Received By kstevens Date 2004-09-16 Time 18:52 Sent To  
Notes
2004-09-16 00:00:00PASSED/PROVISO
  
  
 SINK SHALL COMPLY WITH 11-4.24 AND ALL
 SUBSECTIONS

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-07-31 Cont ID  
Sent By pschmitz Date 2004-07-31 Time 11:12 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2004-07-31 00:00:00PLUMBING PLAN REVIEW FBC 2001 FL ADA
 SEC 11-4.24 SINK CLEARANCE, HGTH 34" FF
 CLEAR FLOOR SPACE 30" X 48".


Account Summary | Usage Policy | Privacy Policy