Plan Review Details - Permit 04070988
Plan Review Stops For Permit 04070988
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-07-27 Cont ID  
Sent By shill Date 2004-07-27 Time 11:02 Rev Time 0.50
Received By shill Date 2004-07-27 Time 11:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-22 Cont ID  
Sent By shill Date 2004-07-22 Time 14:26 Rev Time 0.50
Received By shill Date 2004-07-22 Time 14:26 Sent To  
Notes
2004-07-22 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE ARCHITECT HAS SPECIFIED A
 NEGATIVE DESIGN PRESSURE OF -89 FOR
 ROOF CLADDING, ZONES 2 AND 3.THIS
 EXCEEDS THE PRODUCT LIMITATION.SUBMIT
 ENGINEERING AS PER PRODUCT APPROVAL.