Plan Review Details - Permit 04070734
Plan Review Stops For Permit 04070734
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-08-11 Cont ID  
Sent By lsmith Date 2004-08-11 Time 07:38 Rev Time 0.50
Received By lsmith Date 2004-08-11 Time 07:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-07-22 Cont ID  
Sent By dpalmer Date 2004-08-10 Time 16:45 Rev Time 2.00
Received By lsmith Date 2004-07-22 Time 11:55 Sent To  
Notes
2004-07-22 00:00:00BUILDING PLAN REVIEW: PROVISO
  
 1. BEFORE A PERMIT CAN BE ISSUED A
 NOTICE OF COMMENCEMENT MUST BE RECORDED
 AT THE COUNTY CLERK'S OFFICE AND A COPY
 SUBMITTED TO WPB.
  
 2. SEPARATE PERMITS ARE REQUIRED FOR
 THEPOOL SHOWN ON THE PLANS.
  
 3. THE VALUE OF THE HOUSE HAS BEEN
 ADJUSTED.THERE ARE ADDITIONAL FEES
 DUE BEFORE A PERMIT CAN BE ISSUED. SEE
 ATTACHED RECEIPT.
  
 ANY QUESTIONS PLEASE CALL;
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-04-07 Cont ID  
Sent By dpalmer Date 2005-04-07 Time 14:22 Rev Time 0.00
Received By dpalmer Date 2005-04-07 Time 14:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-03-02 Cont ID  
Sent By dpalmer Date 2005-03-02 Time 11:24 Rev Time 0.00
Received By dpalmer Date 2005-03-02 Time 11:24 Sent To  
Notes
2005-03-02 00:00:00210.52

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-02-28 Cont ID  
Sent By dpalmer Date 2005-02-28 Time 10:09 Rev Time 0.25
Received By dpalmer Date 2005-02-28 Time 09:45 Sent To  
Notes
2005-02-28 00:00:00** UNSAT **
  
 1)NOTE: PLEASE SEE 210.52 FOR MISSING
 RECETP IN MASTER SUITE.
  
 2)NOTE: PLEASE SEE FBC 104.2.1, PLANS
 MUST ALSO BE SIGNED ALONG WITH THE
 PRINTED NAME OF THE PERSON RESPONSIBLE
 FOR PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-08-10 Cont ID  
Sent By dpalmer Date 2004-08-10 Time 16:45 Rev Time 0.33
Received By dpalmer Date 2004-08-10 Time 16:38 Sent To B
Notes
2004-08-10 00:00:00PLANS REDLINED FOR WATER HEATER.
 VERIFY SIZE OF 6.5KW AND OCP @ 30A'S.
 OCP TO BE 125% MIN.422.13
  
 PLANS SENT TO LS FOR PROCESSING/PERMIT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-07-21 Cont ID  
Sent By csiegber Date 2004-08-04 Time 15:33 Rev Time 0.45
Received By dpalmer Date 2004-07-21 Time 11:43 Sent To M
Notes
2004-07-21 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE SEE FBC WHICH REQUIRES
 THE PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR PLANS.
 104.2.1
  
 2)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 WITH LOAD CALCULATIONS. PLEASE SEE POOL
 HEATER SHOWN ON LOAD CALCS BUT NOT
 PANEL?
 PLEASE ALSO SEE OCP AND AWG FOR WHAT IS
 SHOWN AS POOL EQUIPMENT? PLEASE CLARIFY
 EQUIPMENT. PUMP? 1.5KW LOAD SHOWN.
  
 3)NOTE: PLEASE SEE MISSING RECEPT PER
 210.52 IN MAST SUITE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-06 Cont ID  
Sent By adarroug Date 2005-04-06 Time 15:28 Rev Time 0.00
Received By adarroug Date 2005-04-06 Time 15:27 Sent To E
Notes
2005-04-06 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-23 Cont ID  
Sent By adarroug Date 2005-02-23 Time 15:56 Rev Time 0.00
Received By adarroug Date 2005-02-23 Time 15:56 Sent To E
Notes
2005-02-23 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-04 Cont ID  
Sent By csiegber Date 2004-08-04 Time 15:33 Rev Time 0.00
Received By csiegber Date 2004-08-04 Time 15:33 Sent To E
Notes
2004-08-04 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-03 Cont ID  
Sent By mmclean Date 2004-07-20 Time 16:37 Rev Time 0.00
Received By drunnels Date 2004-07-19 Time 14:58 Sent To  
Notes
2004-07-21 00:00:00TO SFD RACK/E
2004-07-19 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-07-26 Cont ID  
Sent By dpalmer Date 2004-07-21 Time 11:44 Rev Time 0.35
Received By pkrauss Date 2004-07-26 Time 08:17 Sent To P
Notes
2004-07-26 00:00:00PROVISO:
 PER THE REVISED 2001 FBC(M) 601.4,
 RETURN AIR IS TO BE EQUAL TO THE SUPPLY
 AIR INTO THAT SPACE.EXCEPTION #3, ALL
 AIR INTO THE MASTER SUITE IS TO BE
 INCLUDED.
  
 RETURN AIR FROM THE MASTER SUITE SHALL
 BE A MINIMUM OF 12".
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-08-03 Cont ID  
Sent By pkrauss Date 2004-07-26 Time 08:24 Rev Time 0.00
Received By drunnels Date 2004-08-03 Time 10:40 Sent To  
Notes
2004-08-03 00:00:00NO PLUMBING PLANS SUBMITTED PER KEN STEV
 ENS

Review Stop Z ZONING
Rev No 1 Status P Date 2004-07-20 Cont ID  
Sent By mmclean Date 2004-07-20 Time 16:37 Rev Time 0.00
Received By mmclean Date 2004-07-20 Time 16:37 Sent To I
Notes
***NONE***