Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-07-28 Cont ID  
Sent By hmoser Date 2004-07-28 Time 16:09 Rev Time 0.50
Received By hmoser Date 2004-07-28 Time 16:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-07-19 Cont ID  
Sent By csiegber Date 2004-07-16 Time 13:59 Rev Time 0.35
Received By pkrauss Date 2004-07-16 Time 16:30 Sent To P
Notes
2004-07-16 00:00:00DENIED:
 TRANSFER GRILLE FROM THE MASTER BEDROOM
 IS NOT SIZED PROPERLY.PER THE REVISED
 2001 FBC(M) 601.4 EXCEPTION #2 & 3,
 TRANSFER GRILLES SHALL BE 50 SQ INCHES
 OF OPEN AREA TO 100 CFM OF SUPPLY AIR.
 ALL THE AIR INTO THE MASTER SUITE IS TO
 BE INCLUDED FOR A TOTAL OF SUPPLY AIR
 TO THAT SPACE.PLAN INDICATES A TOTAL
 OF 210 CFMFOR THE SUPPLY.RETURN AIR
 SHALL BE A MINIMUM OF 12" X 10".
  
 AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.