Plan Review Details - Permit 04070644
Plan Review Stops For Permit 04070644 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2004-07-16 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-07-16 |
Time |
13:59 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-07-16 |
Time |
13:58 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2004-07-28 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2004-07-28 |
Time |
16:09 |
Rev Time |
0.50 |
Received By |
hmoser |
Date |
2004-07-28 |
Time |
16:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2004-07-19 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-07-16 |
Time |
13:59 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2004-07-16 |
Time |
16:30 |
Sent To |
P |
|
Notes |
2004-07-16 00:00:00 | DENIED: | | TRANSFER GRILLE FROM THE MASTER BEDROOM | | IS NOT SIZED PROPERLY.PER THE REVISED | | 2001 FBC(M) 601.4 EXCEPTION #2 & 3, | | TRANSFER GRILLES SHALL BE 50 SQ INCHES | | OF OPEN AREA TO 100 CFM OF SUPPLY AIR. | | ALL THE AIR INTO THE MASTER SUITE IS TO | | BE INCLUDED FOR A TOTAL OF SUPPLY AIR | | TO THAT SPACE.PLAN INDICATES A TOTAL | | OF 210 CFMFOR THE SUPPLY.RETURN AIR | | SHALL BE A MINIMUM OF 12" X 10". | | | | AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2004-07-20 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2004-07-20 |
Time |
18:57 |
Rev Time |
0.25 |
Received By |
jleech |
Date |
2004-07-20 |
Time |
18:57 |
Sent To |
|
|
Notes |
|
|
|