Plan Review Stops For Permit 04070529 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2004-07-27 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-07-27 |
Time |
10:45 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-07-27 |
Time |
10:45 |
Sent To |
P |
|
Notes |
2004-07-27 00:00:00 | TO KS DESK/PER SP |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2004-07-13 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2004-07-13 |
Time |
15:37 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2004-07-13 |
Time |
15:37 |
Sent To |
P |
|
Notes |
2004-07-13 00:00:00 | SENT TO "P" BOX |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2004-10-18 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2004-10-18 |
Time |
11:43 |
Rev Time |
0.25 |
Received By |
kstevens |
Date |
2004-07-27 |
Time |
14:45 |
Sent To |
|
|
Notes |
2004-10-18 00:00:00 | DENIED | | REFERENCE: FBC-2001 FUEL GAS | | | | PIPE SIZING FOR EXISTING AND NEW PIPE | | ARE NOT SUFFICIENT FOR THE ADDED LOAD OF | | THE POOL HEATER @ 100'. EIGHER A 2 LB | | SYSTEM WITH A REGULATOR OR LARGER PIPE | | IS REQUIRED. TABLE 402(2). | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2004-07-24 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-07-27 |
Time |
10:45 |
Rev Time |
1.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2004-07-24 00:00:00 | PLAN REVIEEW DENIED FBCFG 2001 | | SEE ATTACHED GAS PERMIT APPLICATION | | REQUIRMEMNTS, ITEMS 4,6,7,9. |
|
|
|