Plan Review Details - Permit 04070529
Plan Review Stops For Permit 04070529
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-27 Cont ID  
Sent By csiegber Date 2004-07-27 Time 10:45 Rev Time 0.00
Received By csiegber Date 2004-07-27 Time 10:45 Sent To P
Notes
2004-07-27 00:00:00TO KS DESK/PER SP

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-13 Cont ID  
Sent By mjacobs Date 2004-07-13 Time 15:37 Rev Time 0.00
Received By mjacobs Date 2004-07-13 Time 15:37 Sent To P
Notes
2004-07-13 00:00:00SENT TO "P" BOX

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-10-18 Cont ID  
Sent By kstevens Date 2004-10-18 Time 11:43 Rev Time 0.25
Received By kstevens Date 2004-07-27 Time 14:45 Sent To  
Notes
2004-10-18 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 PIPE SIZING FOR EXISTING AND NEW PIPE
 ARE NOT SUFFICIENT FOR THE ADDED LOAD OF
 THE POOL HEATER @ 100'. EIGHER A 2 LB
 SYSTEM WITH A REGULATOR OR LARGER PIPE
 IS REQUIRED. TABLE 402(2).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-07-24 Cont ID  
Sent By csiegber Date 2004-07-27 Time 10:45 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2004-07-24 00:00:00PLAN REVIEEW DENIED FBCFG 2001
 SEE ATTACHED GAS PERMIT APPLICATION
 REQUIRMEMNTS, ITEMS 4,6,7,9.