Plan Review Details - Permit 04070525
Plan Review Stops For Permit 04070525
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-09-23 Cont ID  
Sent By alange Date 2004-09-23 Time 11:02 Rev Time 1.00
Received By alange Date 2004-09-23 Time 11:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-08-23 Cont ID  
Sent By jleech Date 2004-09-18 Time 13:35 Rev Time 0.75
Received By alange Date 2004-08-23 Time 08:51 Sent To  
Notes
2004-08-23 00:00:00DENIED
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-03 Cont ID  
Sent By pkrauss Date 2004-08-17 Time 12:09 Rev Time 1.66
Received By alange Date 2004-08-03 Time 14:30 Sent To  
Notes
2004-08-03 00:00:00DENIED
  
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SIGN OWNER/AGENT ON ENERGY CALCS.
  
 4.SUBMIT 2 COPIES OF PRODUCT APPROVALS
 FOR ROOFING AND STRAPING AND TIEDOWNS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 3 OR MORE COPIES SUBMITTED ONLY TWO
 REQUIRED.
  
 5.TWO TYPES OF PRODUCT APPROVALS
 SUBMITTED FOR ROLL UP DOOR.NONE
 SHOWN ON PLANS.SPECIFY WHAT DOOR YOU
 WILL BE USEING.
  
 6.SEPERATE PERMIT REQUIRED FOR POOL.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 TEL: (561)805-6672
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-09-17 Cont ID  
Sent By dpalmer Date 2004-09-17 Time 16:51 Rev Time 0.33
Received By dpalmer Date 2004-09-17 Time 16:51 Sent To P
Notes
2004-09-17 00:00:00NOTES REDLINED.
  
 110.9, NO AIC RATING SUBMITTED.
  
 LOAD CALCULATIONS TO BE DONE PER 220.31B
  
  
 REVISE BEFORE FINAL.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-08-09 Cont ID  
Sent By csiegber Date 2004-08-30 Time 10:24 Rev Time 0.50
Received By btrobaug Date 2004-08-09 Time 07:38 Sent To M
Notes
2004-08-09 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INDICATE CONDUIT & WIRE SIZE
 FOR THE FEEDER BETWEEN THE DISCONNECT
 AND PANEL ON THE RISER DIAGRAM. ALSO
 SEE 250.122 FOR GROUNDING CONDUCTOR.
  
 2} PLEASE SEE THAT THE REQUIRED BATH
 CIRCUIT 210.11(C)(3) IS LABELED "GAS
 BBQ" ON THE SCHEDULE.
  
 3} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 4} THE REQUIRED SMOKE DETECTORS PER
 NFPA-72 8-1.4.1.6.2 MUST BE SHOWN ON
 THE PLAN.
  
 5} THE TITLE BLOCK INDICATES A
 CORPORATION, THE AA NUMBER MUST BE IN
 THE TITLE BLOCK. SEE 61G1-16.004 FAC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-07-21 Cont ID  
Sent By csiegber Date 2004-08-06 Time 14:43 Rev Time 0.50
Received By btrobaug Date 2004-07-21 Time 11:13 Sent To P
Notes
2004-07-21 00:00:00 
 TITLE BLOCK REQUIRED.
 NOTE: PLEASE INCLUDE ALL LICENSE
 #'S ON THE REQ'D TITLE BLOCK.
 PLEASE ALSO INCLUDE CERTIFICATE OF
 AUTHORIZATION #'S WHERE REQ'D.
  
 PER FS 471.023, FAC 61G15-23.002 (ENG'S)
 PER FS 481.219, FAC 61G1-16.004 (ARCH'S)
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-08-30 Cont ID  
Sent By csiegber Date 2004-08-30 Time 10:24 Rev Time 0.00
Received By csiegber Date 2004-08-30 Time 10:24 Sent To E
Notes
2004-08-30 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-06 Cont ID  
Sent By csiegber Date 2004-08-06 Time 14:43 Rev Time 0.00
Received By csiegber Date 2004-08-06 Time 14:43 Sent To E
Notes
2004-08-06 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-16 Cont ID  
Sent By csiegber Date 2004-07-16 Time 08:48 Rev Time 0.00
Received By csiegber Date 2004-07-16 Time 08:48 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-13 Cont ID  
Sent By mmclean Date 2004-07-15 Time 16:54 Rev Time 0.00
Received By mjacobs Date 2004-07-13 Time 16:31 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-08-17 Cont ID  
Sent By pkrauss Date 2004-08-17 Time 12:09 Rev Time 0.30
Received By pkrauss Date 2004-08-16 Time 15:30 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-08-02 Cont ID  
Sent By btrobaug Date 2004-08-09 Time 10:23 Rev Time 0.30
Received By pkrauss Date 2004-08-02 Time 14:08 Sent To B
Notes
2004-08-02 00:00:00DENIED:
 1.PROVIDE TITLE BLOCK ON PLANS AS
 REQUIRED BY FS 481.219 & FAC 61G1-16.004
  
 2.PLEASE NOTE ON PLAN SHEET M-1, THE
 GRILLE/DIFFUSER SCHEDULE DOES NOT
 CORRELATE WITH THE PLAN.PLEASE CLARIFY
 THE MOUNTING INDICATES "F" (FLOOR?)
 WHICH IS NOT SPECIFIED ON THE SCHEDULE.
 PER 2001 FBC(M) 603.12, DUCTS SHALL NOT
 BE LOCATED IN OR WITHIN 6" OF THE GROUND
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-09-18 Cont ID  
Sent By jleech Date 2004-09-18 Time 13:35 Rev Time 0.50
Received By jleech Date 2004-09-18 Time 13:35 Sent To B
Notes
2004-09-18 00:00:00ADDITIONAL PERMIT REQUIRED FOR GAS WORK.
 GAS CONTRACTOR TO SUBMIT DRAWING WITH
 PERMIT APPLICATION.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-07-27 Cont ID  
Sent By dpalmer Date 2004-09-17 Time 16:52 Rev Time 0.33
Received By jleech Date 2004-07-27 Time 20:10 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-07-15 Cont ID  
Sent By mjacobs Date 2004-07-13 Time 16:35 Rev Time 0.00
Received By mmclean Date 2004-07-15 Time 16:54 Sent To I
Notes
2004-07-15 00:00:00MUST PULL SEPARATE PERMIT FOR POOL