Plan Review Details - Permit 04070258
Plan Review Stops For Permit 04070258
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2004-08-16 Cont ID  
Sent By nmccray Date 2004-08-16 Time 14:43 Rev Time 0.00
Received By nmccray Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-08-18 Cont ID  
Sent By nmccray Date 2004-08-18 Time 13:39 Rev Time 0.00
Received By nmccray Date 2004-08-18 Time 13:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-08-16 Cont ID  
Sent By csiegber Date 2004-08-18 Time 12:45 Rev Time 0.00
Received By nmccray Date 2004-08-16 Time 14:45 Sent To  
Notes
2004-08-16 00:00:00**********DENIED************************
 1) ON SHEETS FP-2 AND FP-3 APPEARS THAT
 THE PUMP ROOM, GENERATOR ROOM, ELECTRIC
 ROOM, AND TRANSFORMER VAULT ARE NOT FIRE
 SPRINKLER PROTECTED.
  
 2) PLEASE BE ADVISED THAT THE FOUR
 STANDPIPES REQUIRES 1250 GPM FIRE PUMP
 AND SEPARATE PERMIT APPLICATION AND CUT
 SHEETS MAYBE REQUIRED.
  
 NATE MCCRAY, CAPTAIN
 835-2910 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-18 Cont ID  
Sent By csiegber Date 2004-08-18 Time 12:45 Rev Time 0.00
Received By csiegber Date 2004-08-18 Time 12:45 Sent To FIRE
Notes
2004-08-18 00:00:00TO NM DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-08 Cont ID  
Sent By csiegber Date 2004-07-08 Time 08:22 Rev Time 0.00
Received By csiegber Date 2004-07-08 Time 08:22 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-08-16 Cont ID  
Sent By nmccray Date 2004-08-16 Time 14:43 Rev Time 0.00
Received By nmccray Date   Time   Sent To  
Notes
***NONE***