Plan Review Details - Permit 04070185
Plan Review Stops For Permit 04070185
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-11-24 Cont ID  
Sent By lmartine Date 2004-11-24 Time 15:01 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2004-11-24 00:00:00PROVISO
  
  
 1]
 SEPERATE PERMIT REQUIRED FOR EXTERIOR
 ENTRY DOORS.
  
 2]
 BATHROOM WINDOWS SHALL COMPLY WITH FBC
 2405.2.1 FOR HAZARDOUS GLAZING.
  
  
  
  
 L. MARTINEZ
 805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-14 Cont ID  
Sent By jleech Date 2004-07-13 Time 19:39 Rev Time 0.75
Received By alange Date 2004-07-14 Time 12:00 Sent To  
Notes
2004-07-14 00:00:00DENIED
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2.SUBMIT 2 COPIES OF PRODUCT APPROVALS
 FOR OVERHEAD DOOR.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3.FBC 2405.2.1 SAFTEY GLAZING REQUIRED
 AT WINDOWS OVER TUB LOCATIONS.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-11-18 Cont ID  
Sent By btrobaug Date 2004-11-18 Time 15:49 Rev Time 0.50
Received By btrobaug Date 2004-11-18 Time 15:49 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-11-15 Cont ID  
Sent By btrobaug Date 2004-11-15 Time 14:38 Rev Time 0.50
Received By btrobaug Date 2004-11-15 Time 10:13 Sent To B
Notes
2004-11-15 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE SERVICE CALCULATED LOAD IS 240
 AMPS. THE RISER INDICATES A 200 AMP
 MAIN. THE SERVICE ENTRANCE CONDUCTORS
 MUST BE 4/0 PER 310.15(B)(6).
  
 2} THE SERVICE MUST BE 250 AMPS PER
 230.42.
  
  
 3} THE GEC MUST BE #2 CU PER 250.66.
  
 4} THERE MUST BE OUTSIDE RECEPTACLES
 FRONT AND REAR PER 210.52(E).
  
 5} THE GARAGE RECEPTACLES NUST BE GFI
 PER 210.8(A)(2).
  
 6} THERE ARE NUMEROUS LOCATIONS THAT DO
 NOT COMPLY WITH RECEPTACLE SPACING
 REQUIREMENT PER 210.52 ALL. SEE REVIEWED
 SET FOR SOME LOCATIONS.
  
 7} THE KITCHEN AND DINING ROOM
 RECEPTACLES ARE NOT SHOWN ON SHEET 3 OF
 3. SEE 210.52, 210.11 (C)(1), 210.52(B)
 AND 210.8(A)(6).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-07-08 Cont ID  
Sent By csiegber Date 2004-07-06 Time 16:27 Rev Time 0.50
Received By btrobaug Date 2004-07-08 Time 10:52 Sent To P
Notes
2004-07-08 00:00:00 
 PLEASE SUBMIT A SET OF PLANS REFLECTING
 THE PROPOSED SCOPE OF WORK PER 215.5 NEC
 AND 104.2.1 FBC.
  
 ALSO NOTE THE THAT THE WORK SUGGESTED
 REQUIRES A PERMIT ISSUED TO A LICENSED
 ELECTRICAL CONTRACTOR WHO MUST APPLY
 SEPARATELY.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-06 Cont ID  
Sent By csiegber Date 2004-07-06 Time 16:27 Rev Time 0.00
Received By csiegber Date 2004-07-06 Time 16:27 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-11-15 Cont ID  
Sent By pschmitz Date 2004-11-15 Time 08:22 Rev Time 0.00
Received By pschmitz Date 2004-11-15 Time 08:22 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-07-13 Cont ID  
Sent By btrobaug Date 2004-07-08 Time 11:01 Rev Time 0.40
Received By jleech Date 2004-07-13 Time 19:39 Sent To B
Notes
2004-07-13 00:00:00DENIED;
 LAUNDRY FACILITIES ARE REQUIRED TO MEET
 MINIMUM PLUMBING CODE PER. FBC PLUMBING
 TABLE 403.1. EACH UNIT IS REQUIRED TO
 HAVE A W/M OR ONE W/M IN CENTRAL LOCA-
 TION IS ACCEPTABLE, SO BOTH TENENT HAVE
 ACCESS TO FACILITIES.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695