Plan Review Details - Permit 04070185
Plan Review Stops For Permit 04070185 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2004-11-24 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2004-11-24 |
Time |
15:01 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2004-11-24 00:00:00 | PROVISO | | | | | | 1] | | SEPERATE PERMIT REQUIRED FOR EXTERIOR | | ENTRY DOORS. | | | | 2] | | BATHROOM WINDOWS SHALL COMPLY WITH FBC | | 2405.2.1 FOR HAZARDOUS GLAZING. | | | | | | | | | | L. MARTINEZ | | 805-6710 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2004-07-14 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2004-07-13 |
Time |
19:39 |
Rev Time |
0.75 |
Received By |
alange |
Date |
2004-07-14 |
Time |
12:00 |
Sent To |
|
|
Notes |
2004-07-14 00:00:00 | DENIED | | 1. THE NOTICE OF COMMENCEMENT SHALL BE | | RECORDED AT PALM BEACH COUNTY COURTHOUSE | | AND A COPY SUBMITTED TO THIS OFFICE | | BEFORE A PERMIT CAN BE ISSUED.BLANK | | FORMS ARE AVAILABLE FROM THIS OFFICE. | | | | 2.SUBMIT 2 COPIES OF PRODUCT APPROVALS | | FOR OVERHEAD DOOR. | | PRODUCT APPROVALS SUBMITTED WITH | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | SPECIFIC FORM PER RULE 9B-72. SEE | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | 3.FBC 2405.2.1 SAFTEY GLAZING REQUIRED | | AT WINDOWS OVER TUB LOCATIONS. | | | | ANY QUESTIONS CALL ME. | | | | ART LANGE | | BUILDING PLANS EXAMINER | | 805-6672 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2004-11-18 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2004-11-18 |
Time |
15:49 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2004-11-18 |
Time |
15:49 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2004-11-15 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2004-11-15 |
Time |
14:38 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2004-11-15 |
Time |
10:13 |
Sent To |
B |
|
Notes |
2004-11-15 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE SERVICE CALCULATED LOAD IS 240 | | AMPS. THE RISER INDICATES A 200 AMP | | MAIN. THE SERVICE ENTRANCE CONDUCTORS | | MUST BE 4/0 PER 310.15(B)(6). | | | | 2} THE SERVICE MUST BE 250 AMPS PER | | 230.42. | | | | | | 3} THE GEC MUST BE #2 CU PER 250.66. | | | | 4} THERE MUST BE OUTSIDE RECEPTACLES | | FRONT AND REAR PER 210.52(E). | | | | 5} THE GARAGE RECEPTACLES NUST BE GFI | | PER 210.8(A)(2). | | | | 6} THERE ARE NUMEROUS LOCATIONS THAT DO | | NOT COMPLY WITH RECEPTACLE SPACING | | REQUIREMENT PER 210.52 ALL. SEE REVIEWED | | SET FOR SOME LOCATIONS. | | | | 7} THE KITCHEN AND DINING ROOM | | RECEPTACLES ARE NOT SHOWN ON SHEET 3 OF | | 3. SEE 210.52, 210.11 (C)(1), 210.52(B) | | AND 210.8(A)(6). | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2004-07-08 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-07-06 |
Time |
16:27 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2004-07-08 |
Time |
10:52 |
Sent To |
P |
|
Notes |
2004-07-08 00:00:00 | | | PLEASE SUBMIT A SET OF PLANS REFLECTING | | THE PROPOSED SCOPE OF WORK PER 215.5 NEC | | AND 104.2.1 FBC. | | | | ALSO NOTE THE THAT THE WORK SUGGESTED | | REQUIRES A PERMIT ISSUED TO A LICENSED | | ELECTRICAL CONTRACTOR WHO MUST APPLY | | SEPARATELY. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2004-07-06 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-07-06 |
Time |
16:27 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-07-06 |
Time |
16:27 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2004-11-15 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2004-11-15 |
Time |
08:22 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2004-11-15 |
Time |
08:22 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2004-07-13 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2004-07-08 |
Time |
11:01 |
Rev Time |
0.40 |
Received By |
jleech |
Date |
2004-07-13 |
Time |
19:39 |
Sent To |
B |
|
Notes |
2004-07-13 00:00:00 | DENIED; | | LAUNDRY FACILITIES ARE REQUIRED TO MEET | | MINIMUM PLUMBING CODE PER. FBC PLUMBING | | TABLE 403.1. EACH UNIT IS REQUIRED TO | | HAVE A W/M OR ONE W/M IN CENTRAL LOCA- | | TION IS ACCEPTABLE, SO BOTH TENENT HAVE | | ACCESS TO FACILITIES. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
|