Plan Review Details - Permit 04061388
Plan Review Stops For Permit 04061388
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-04-10 Cont ID  
Sent By alange Date 2006-04-10 Time 15:28 Rev Time 1.00
Received By alange Date 2006-04-10 Time 15:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2006-03-29 Cont ID  
Sent By alange Date 2006-03-29 Time 15:44 Rev Time 0.50
Received By alange Date 2006-03-29 Time 15:44 Sent To  
Notes
2006-03-29 00:00:00REVISION DENIED
 THIRD REVIEW:
  
 NOTE ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-12-28 Cont ID  
Sent By alange Date 2005-12-28 Time 09:34 Rev Time 1.00
Received By alange Date 2005-12-28 Time 09:21 Sent To  
Notes
2005-12-28 00:00:00REVISION DENIED
 SECOND REVIEW:
  
 NOTE ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 NEW COMMENTS:
 A. GAF BITUMEN ROOF FOR CONCRETE DECK
 PRODUCT APPROVAL.SUBMIT THE FIRST 8
 PAGES AND THEN ADD THE PAGES USED FOR
 THE ASSEMBLY SELECTED.
 B.PRODUCT APPROVAL SUBMITTED IS NOT
 APPROVED TO BE USED VERTICALLY ON STEEL
 BEAMS.PRODUCT APPROVAL SUBMITTED IS
 FOR CONCRETE DECKS.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-11-22 Cont ID  
Sent By alange Date 2005-11-22 Time 09:52 Rev Time 0.66
Received By alange Date 2005-11-22 Time 09:47 Sent To  
Notes
2005-11-22 00:00:00REVISION DENIED
  
 SUBMIT 2 SETS PRODUCT APPROVALS FOR GAF
 GLASPLY 4 PLY AND MODIFIED BITUMEN ROOF.
 NOTE ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-10-20 Cont ID  
Sent By alange Date 2004-10-20 Time 12:57 Rev Time 1.00
Received By alange Date 2004-10-20 Time 12:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-09-16 Cont ID  
Sent By alange Date 2004-09-16 Time 08:39 Rev Time 0.50
Received By alange Date 2004-09-16 Time 08:39 Sent To  
Notes
2004-09-16 00:00:00DENIED
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2.SEE ELECTRICAL REVIEW NOT #4 FROM
 LAST REVIEW. RE: PLANS ARE REQUIRED TO
 HAVE AN ORIGONAL SIGNATURE PER
 FS.471.025
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 TEL: (561)805-6672
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-26 Cont ID  
Sent By alange Date 2004-07-26 Time 08:54 Rev Time 1.00
Received By alange Date 2004-07-26 Time 08:53 Sent To  
Notes
2004-07-26 00:00:00BUILDING REVIEW OK
  
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 TEL: (561)805-6672
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-10-18 Cont ID  
Sent By dpalmer Date 2004-10-18 Time 11:24 Rev Time 0.50
Received By dpalmer Date 2004-10-15 Time 15:27 Sent To  
Notes
2004-10-18 00:00:00** STAMPED ELECTRICAL ***
  
 PLEASE SEE "S" SHEETS ARE NOW SEALED
 PHOTO COPIES OF ORIGINAL SIGNATURE.
 NOTICE WILL BE GIVEN TO RETAIN ONE SET
 OF PLANS.
 FS 471.025.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-09-17 Cont ID  
Sent By dpalmer Date 2004-09-17 Time 06:52 Rev Time 0.33
Received By dpalmer Date 2004-09-17 Time 06:45 Sent To  
Notes
2004-09-17 00:00:00*********** UNSAT 2ND REVIEW ***********
  
 PLEASE SEE NOTES FROM PREVIOUS REVIEW.
  
 1)NOTE: PLEASE SEE NOTE #4 FROM FIRST
 REVIEW. PLEASE SEE FS 471.025 WHICH
 REQUIRES PLANS TO HAVE ORIGINAL
 SIGNATURE. PLEASE SEE NEW SHEETS ARE
 ALSO SEALED COPIES. ONE OF THE ORIGINAL
 SETS WERE RETAINED FOR SAME COMMENT.
 61G15-23.002
 ONE SET OF NEW SHEETS ARE ALSO NOW BEING
 RETAINED AND SETS WILL NOW BE TURNED
 INTOFBPE'S FOR REVIEW.
  
 2)NOTE: PLEASE ALSO SEE ATTACHED COPY OF
 FS 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL. PLANS WITH REPEATED
 COMMENTS. THIS IS ONLY A NOTICE GIVEN
 AT THIS TIME.*****
  
 3)NOTE: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS AND INSERT NEW SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SEE THERE ARE NO FULL COMPLETED
 SETS SUBMITTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-07-02 Cont ID  
Sent By dpalmer Date 2004-07-02 Time 17:45 Rev Time 0.50
Received By dpalmer Date 2004-07-02 Time 17:42 Sent To  
Notes
2004-07-02 00:00:00************* UNSAT *************
  
 1)NOTE: PLANS DO NOT INDICATE EXISTING
 SERVICE AND/OR LOCATION FOR GROUPING OF
 MAINS. 230.72
 ADDTIONAL SERVICE AS SHOWN IS NOT PERMIT
 -TED. 230.2
  
 2)NOTE: PLEASE SEE 250.6,250.24, EQUIP-
 -MENT GROUNDING IS ONLY INSTALLED AFTER
 FIRST MEANS OF DISCONNECT.
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 4)NOTE: PLEASE SEE PLANS ARE SEALED
 COPIES. PLANS ARE REQUIRED TO HAVE AN
 ORIGINAL SIGNATURE PER FS 471.025
 PLEASE ALSO SEE FS REQUIRE A SIGNATURE
 AS SHOWN ON LICENSE/SEAL. INITIALS
 ARE NOT ACCEPTABLE.
 PLEASE SEE ONE SET OF PLANS ARE BEING
 RETAINED FOR FILE FOR ABOVE REFERENCE.
 FAC 61G15-23.002
 PLEASE SEE BOTH SETS ARE COPIES OF SIG-
 -NATURE WITH RAISED SEAL. ONLY ONE SET
 IS BEING RETURNED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-09-20 Cont ID  
Sent By nmccray Date 2004-09-20 Time 12:31 Rev Time 0.00
Received By nmccray Date 2004-09-20 Time 12:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-07-14 Cont ID  
Sent By nmccray Date 2004-07-14 Time 14:59 Rev Time 0.00
Received By nmccray Date 2004-07-14 Time 14:59 Sent To  
Notes
2004-07-14 00:00:00********DENIED**************************
 1) THE SMOKE DETECTORS INSIDE THIS
 UNMANNED BUILDING ON TOP OF THE ROOF
 SHALL BE CONNECTED TO THE BUILDING FIRE
 ALARM SYSTEM.
  
 2) NO SMOKING SIGNS SHALL BE POSTED
 INSIDE AND OUTSIDE OF THE UNMANNED
 BUILDING.
  
 3) SEPARATE PLAN AND PERMIT APPLICATION
 ARE REQUIRED FOR FIRE ALARM SYSTEM
 REMODEL.
  
 NATE MCCRAY, CAPTAIN
 835-2910 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-03-31 Cont ID  
Sent By adarroug Date 2006-03-31 Time 13:05 Rev Time 0.00
Received By adarroug Date 2006-03-31 Time 13:05 Sent To B
Notes
2006-03-31 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-03-23 Cont ID  
Sent By dpalmer Date 2006-03-23 Time 09:54 Rev Time 0.00
Received By dpalmer Date 2006-03-23 Time 09:54 Sent To B
Notes
2006-03-23 00:00:00TO AL'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-11-16 Cont ID  
Sent By adarroug Date 2005-11-16 Time 13:29 Rev Time 0.00
Received By adarroug Date 2005-11-16 Time 13:29 Sent To B
Notes
2005-11-16 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-10-06 Cont ID  
Sent By csiegber Date 2004-10-06 Time 14:29 Rev Time 0.00
Received By csiegber Date 2004-10-06 Time 14:29 Sent To  
Notes
2004-10-06 00:00:00TO COMM BD#14

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-09-14 Cont ID  
Sent By csiegber Date 2004-09-14 Time 11:16 Rev Time 0.00
Received By csiegber Date 2004-09-14 Time 11:16 Sent To  
Notes
2004-09-14 00:00:00TO COMM BD#25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-26 Cont ID  
Sent By mmclean Date 2004-07-07 Time 12:38 Rev Time 0.00
Received By alange Date 2004-06-30 Time 14:51 Sent To  
Notes
2004-06-30 00:00:00TO COMM BD#44

Review Stop Z ZONING
Rev No 3 Status P Date 2004-10-18 Cont ID  
Sent By jroach Date 2004-10-18 Time 10:11 Rev Time 0.00
Received By jroach Date 2004-10-18 Time 10:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2004-09-21 Cont ID  
Sent By mmclean Date 2004-09-21 Time 16:05 Rev Time 0.00
Received By mmclean Date 2004-09-21 Time 16:05 Sent To  
Notes
2004-09-21 00:00:00DENIED, TO ADDRESS THE INFO FAXED FOR
 INFORMAL SITE PLAN REVIEW AND PROVIDE A
 UNITY OF TITLE.CALLED BART FOR P/U
 FILE R.JOHN ROACH, PLANNER 822-1448 MM

Review Stop Z ZONING
Rev No 1 Status F Date 2004-07-07 Cont ID  
Sent By mmclean Date 2004-07-07 Time 12:38 Rev Time 0.00
Received By mmclean Date 2004-07-07 Time 12:38 Sent To I
Notes
2004-07-07 00:00:00DENIED, NEED TO HAVE AN INFORMAL SITE
 PLAN REVIEW.CALLED CONTRACTOR