Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-06 Cont ID  
Sent By csiegber Date 2004-10-06 Time 14:34 Rev Time 0.00
Received By csiegber Date 2004-10-06 Time 14:34 Sent To P
Notes
2004-10-06 00:00:00TO GAS

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-10-21 Cont ID  
Sent By kstevens Date 2004-10-21 Time 07:59 Rev Time 0.50
Received By kstevens Date 2004-10-21 Time 07:59 Sent To  
Notes
2004-10-21 00:00:00 
  
  
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.
  
  
  
  
 IF DRYER ROOM IS A CONFINED SPACE,
 OPENINGS REQUIRED PER SECTION 304.3.1 0R
 SECTION 304.3.2 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
 WATER HEATER ROOM 4,500 CU. FT. REQUIRED
  
  
  
  
  
 B

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-07-29 Cont ID  
Sent By csiegber Date 2004-10-06 Time 14:34 Rev Time 0.50
Received By kstevens Date 2004-07-29 Time 11:53 Sent To  
Notes
2004-10-21 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1) SECTION 404.6 PIPING SHALL NOT BE IN-
 STALLED UNDER THE SLAB. ALTERNATIVE
 METHOD (PE AROUND HOUSE) AVAILABLE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]