Plan Review Details - Permit 04061350
Plan Review Stops For Permit 04061350
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-10-05 Cont ID  
Sent By lsmith Date 2004-10-05 Time 14:59 Rev Time 0.75
Received By lsmith Date 2004-10-05 Time 14:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-07-28 Cont ID  
Sent By csiegber Date 2004-10-05 Time 14:29 Rev Time 1.00
Received By lsmith Date 2004-07-28 Time 13:06 Sent To  
Notes
2004-07-28 00:00:00BUILDING PLAN REVIEW: PROVISO
  
 1. A SEPARATE PERMIT WILL BE REQUIRED
 FOR THE STORM PANELS.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-07-23 Cont ID  
Sent By dpalmer Date 2004-07-28 Time 11:34 Rev Time 0.75
Received By lsmith Date 2004-07-20 Time 08:24 Sent To  
Notes
2004-07-23 00:00:00BUILDING PLAN REVIEW: PROVISO
  
 1. SEE ELECTRICAL NOTES: REMOVE OLD
 SHEETS & INSERT NEW ONES IN PLANS.
 2. SEPARATE PERMITS REQUIRED FOR STORM
 PANELS
 3. NO BUTT GLASS WINDOWS IN THIS HOUSE
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-14 Cont ID  
Sent By dpalmer Date 2004-07-20 Time 14:39 Rev Time 4.00
Received By lsmith Date 2004-07-13 Time 15:15 Sent To  
Notes
2004-07-13 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT. THE COPY MUST BE SUBMITTED
 BEFORE A PERMIT IS ISSUED.
  
 2. SUBMIT ENGINEERING FOR THE BUTT GLASS
 ASSEMBLY WITH PRODUCT APPROVALS.THE
 ENGINEER MUST INSPECT THE WINDOWS AT
 TIME OF INSTALLATION AND SUBMIT A
 LETTER STATING THEY HAVE BEEN INSTALLED
 ACCORDING TO HIS CALCULATIONS.
 SUBMIT THE PROPER PRODUCT APPROVALS FOR
 THE WINDOWS. SUBMIT THE MFGRS. PRODUCT
 SHEET FOR THE SEALANT TO BE USED IN THE
 INSTALLATION.
  
 3. SUBMIT PRODUCT APPROVAL AND
 INSTALLATION SCHEDULE FOR THE STORM
 PANELS.
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2006-02-16 Cont ID  
Sent By dpalmer Date 2006-02-16 Time 10:43 Rev Time 0.00
Received By dpalmer Date 2006-02-16 Time 10:35 Sent To PC
Notes
2006-02-16 00:00:00REV #4

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2006-01-30 Cont ID  
Sent By dpalmer Date 2006-01-30 Time 19:27 Rev Time 0.00
Received By dpalmer Date 2006-01-30 Time 19:07 Sent To PC
Notes
2006-01-30 00:00:00******* UNSAT **********
  
 1)NOTE: PLEASE SEE POOL PANEL, PLEASE
 VERIFY ALL OCP SHOWN AS MANY CIRCUITS
 INDICATE 2-POLE CIRCUITS FOR ITEMS WHICH
 DO APPEAR THEY SHOULD BE 220V, GAS
 HEATER?, POOL CHROLINATOR ETC.
 PLEASE ALSO SEE 5 CIRCUITS ARE SHOWN FOR
 WHAT APPEARS TO BE ONE POOL LT??
 215.5
  
 2)NOTE: PLEASE SEE PLANS INDICATE A 240V
 RECEPT FOR DRYER. PLEASE SEE PANEL
 SCHEDULE SHOWS THIS AS 1.5 KW, 20A, #12
 CIRCUIT??
 PLEASE KNOW, IF THIS IS GAS PLEASE
 INDICATE. PLEASE KNOW, 240V RECEPT
 PROVIDED FOR POSSIBLE "FUTURE" ELEC
 DRYER SHOULD BE INDICATED IN LOAD.
 220.18, 215.5
  
 3)NOTE: PLEASE SEE COOK-TOP IS SHOWN
 WITH 7.5 KW LOAD ON A 1-POLE , 20A
 BRANCH CIRCUIT. PLEASE VERIFY AND ADJUST
 OCP, AWG ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2005-12-31 Cont ID  
Sent By dpalmer Date 2005-12-31 Time 19:11 Rev Time 0.00
Received By dpalmer Date 2005-12-31 Time 19:11 Sent To PC
Notes
2005-12-31 00:00:00REV FOR FINAL.

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2005-12-29 Cont ID  
Sent By dpalmer Date 2005-12-29 Time 13:08 Rev Time 0.00
Received By dpalmer Date 2005-12-29 Time 12:58 Sent To  
Notes
2005-12-29 00:00:00***** UNSAT ****
  
  
 1)NOTE: PLEASE SEE FS 481.221 WHICH
 REQUIRES PLANS TO BE SAIGNED, DATED AND
 SEALED BY ARCHITECT.
 PLEASE SEE THE PLANS CONTAIN A"STAMPED"
 FOR THE REQUIRED "WET" SIGNATURE OF SAID
 ARCHITECT.
 PLEASE KNOW, THIS WAS DONE SOME TIME
 AGO, AND IS BEING DONE ONCE AGAIN.
 PLEASE KNOW, WE ARE RETAINING ONE COPY
 OF SAID PLANS FOR FILE AND SHALL BE
 PLACED WITH OTHER PREVIOUS PLANS WHICH
 WERE RETAINED FOR SAME COMMENT.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2005-12-07 Cont ID  
Sent By adarroug Date 2005-12-28 Time 11:29 Rev Time 0.50
Received By dpalmer Date 2005-12-07 Time 17:56 Sent To  
Notes
2005-12-07 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEE FOUNTAIN PUMP SHOWN
 WITH 20A OCP ON #14.
  
 2)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 FOR POOL PANEL AND PANEL "B"&"A"WITH
 RISER DIAGRAM.
 RISER SHOWS PANEL "B" FEEDING POOL
 PANEL, HOWEVER PANEL "A" SCHEDULE
 INDICATES POOL PANEL COMING FROM THIS
 LOCATION.
 PLEASE SEE PANEL "A" SHOWS 60A OCP AND
 #6 TO POOL PANEL. POOL PANEL ON RISER IS
 SHOWN AS 60A OCP AND #4.
 215.5
  
 3)NOTE: PLEASE SEE SD IN MASTER BEDRM
 AND OTHER LOCATIONS ARE ALL REQUIRED TO
 BE WITHIN 12"OF THE HIGHEST
 POINT OF A FLAT CEILING, AND WITHIN 3'
 OF THE PEAK ON A SLOPED CEILING.
 PLEASE KNOW, IF TRAY CEILING IS 12" OR
 MORE ABOVE OTHER CEILING IN RM, THE SD
 WILL BE REQUIRED TO BE LOCATED IN TRAY
 CEILING AREA.
 NFPA-72 11.8.3.5
  
 4)NOTE: PLEASE CORRELATE THE NUMBER OF
 RECESSED LTS ON PLANS WITH THE # IN LOAD
 CALCS ETC.
 PLEASE SEE LOAD CALCS INDICATE A TOTAL
 OF 90, HOWEVER THERE ARE MORE ON PLANS
 PLEASE ADJUST.
 220.3B4
  
 5)NOTE: PLEASE SEE AHU#2 ON PANEL
 SCHEDULE WHICH INDICATES A 10KW HEAT,
 YET OCP IS SHOWN AT 50A'S. PLEASE SEE
 424.3 WHICH REUIRES A MIN 125%.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2005-10-21 Cont ID  
Sent By dpalmer Date 2005-10-21 Time 16:36 Rev Time 0.75
Received By dpalmer Date 2005-10-21 Time 16:29 Sent To  
Notes
2005-10-21 00:00:00******* UNSAT *********
  
 1)NOTE: PLEASE CORRELATE ALL A/C
 MECHANICAL EQUIPMENT.
 PLEASE SEE PANEL SCHEDULES INDICATE FOUR
 A/C SYSTEMS, HOWEVER PLANS DO NOT SHOW
 FOUR COMPLETE SYSTEMS.
 PLEASE ALSO SEE A/C #3 IS NOTED FOR
 GARAGE, HOWEVER THIS SYSTEM IS SHOWN
 NEXT TO MASTER BR.
 PLEASE SEE OTHERS.
 PLEASE SEE LOADS FOR EACH PANEL THE
 LARGETS LOADS FOR A/C SYSTEMS ARE TO BE
 FIGURED USUALLY THE HEAT LOAD. IF ONLY
 THE COOLING LOAD IS INDICATED ON ONE
 PANEL, THEN COOLING LOAD MUST BE SHOWN.
 220
  
 2)NOTE: PLEASE SEE BOTH PANELS "A" AND
 "B" INDICATE BEING MLO.
 PLEASE SEE RISER SHOWS THESE AS MCB.
 PLEASE CORRELATE AND INDICATE MCB'S AS
 REQIRED 230.70
  
 3)NOTE: PLEASE SEE GROUNDING ELECTRODE
 IS NOW SHOWN GOING TO SLAB, HOWEVER THIS
 SHOULD BE NOTED AS FOOTER STEEL. 250.50
  
 4)NOTE: PLEASE SEE LARGEST MOTOR LOADS
 AND CONTINUOUS LOADS IN POOL PANEL NEED
 TO BE SHOWN AT 125%.
 215.3,230.42
  
  
  
 ** NOTE ALL SD'S ARE TO BE INSTALLED
 WITH IN THE HIGHEST POINT OF A FLAT
 CEILING.
 PLEASE SEE THAT ALL SD'S ARE TO BE
 INSTALLED WITHIN 3' OF A SLOPED CEILING
 PEAK.
 PLEASE SEE MASTER BEDRM.
 PLEASE SEE BEDRM #4.
 PLEASE BE SURE TO VERIFY INSTALLATION IN
 FIELD.
 NFPA-72 8-1
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-05-16 Cont ID  
Sent By dpalmer Date 2005-05-16 Time 06:48 Rev Time 0.30
Received By dpalmer Date 2005-05-16 Time 06:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-04-20 Cont ID  
Sent By dpalmer Date 2005-04-20 Time 07:43 Rev Time 0.40
Received By dpalmer Date 2005-04-20 Time 07:43 Sent To  
Notes
2005-04-20 00:00:00**** UNSAT ****
  
  
  
 1)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 ** PLEASE SEE MISSING SD LEADING TO FLR
 ABOVE IN FIRST LEVEL IN THE VICINITY OF
 STAIRS.
 PLEASE SEE MISSING SD IN BEDRM #3.
  
 2)NOTE: PLEASE SEE MISSING PANEL "C"
 FROM PLANS.
  
 3)NOTE: PLEASE SEE "NOTE #2" ON GEN
 NOTES, IF SD'S ARE WIRED TO KIT/BATH
 LIGHTING CIRCUIT, THEN AFCI PROTECTION
 WOULD BE REQUIRED FOR THOSE CIRCUITS
 ALSO .210.12 2002 NEC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-07-28 Cont ID  
Sent By dpalmer Date 2004-07-28 Time 11:30 Rev Time 0.50
Received By dpalmer Date 2004-07-28 Time 11:30 Sent To B
Notes
2004-07-28 00:00:00 
 PLANS SENT TO BLDG FOR PROCESSING.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-07-20 Cont ID  
Sent By csiegber Date 2004-07-26 Time 09:55 Rev Time 0.55
Received By dpalmer Date 2004-07-20 Time 14:10 Sent To B
Notes
2004-07-20 00:00:00************ UNSAT ***********
  
 PLEASE SEE PLANS HAVE HAD CHANGES MADE
 WHICH HAVE GENERATED SOME NEW COMMENTS.
  
 1)NOTE: PLEASE SEE A COMPLETELY NEW
 RISER DIAGRAM IS NOW BEING SUBMITTED
 SHOW NEW MCB PANEL BEING MOUNTED NEXT TO
 METER CAN W/ MAIN DISCONNECTS REMOVED.
 PLEASE SEE PLANS INDICATE MCB INSIDE
 GARAGE WHICH IS OK, HOWEVER MAY NOT BE
 FED FROM THE SIDE OR OVERHEAD.
 PLEASE SEE 230.70 WHICH REQUIRES MAIN
 DISC'S AT NEAREST POINT OF ENTRANCE
 INTO BLDG. LOCAL AMEND 230.70 LIMITS TO
 NO MORE THAN 8' OF UNPROTECTED CONDUCTOR
 -S "INSIDE" BLDG. THIS MUST BE SHOWN AS
 SLAB FED/UNDERGROUND.
 PLEASE ALSO SEE EQUIPMENT GROUNDING
 CONDUCTORS SHOWN FROM METER TO FIRST
 MENAS OF DISC ARE NOT PERMITTED.
 PLEASE SEE 250.24,250.6. EQP GRNDS ARE
 ONLY INSTALLED AFTER THE FIRST MEANS OF
 DISC.
 PLEASE SHOW LOCATION OF METER.
  
 2)NOTE: PLEASE SEE OCP WAS CORRECTED FOR
 AHU#3, YET AWG IS STILL SHOWN AS #10?
  
 3)NOTE: PLEASE SEE RECEPTS HAVE BEEN
 MOVED UPSTAIRS FROM ORIG PLANS.
 PLEASE SEE 210.52/LOFT 6'FROM DOOR AND
 2' OF WALL IN BEDRM #3. WHICH WAS ON
 FIRST SET.
  
 4)NOTE: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-07-06 Cont ID  
Sent By csiegber Date 2004-07-19 Time 12:05 Rev Time 0.50
Received By dpalmer Date 2004-07-06 Time 16:42 Sent To M
Notes
2004-07-06 00:00:00************* UNSAT *************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANELS. RISER SHOWS PANELS AS 150A'S
 AND FED W/ 200A BRKRS. PANEL SCHEDULE
 INDICATES 200A PANELS.
 215.5
  
 2)NOTE: PLEASE SEE 250.66 FOR SIZING
 OF GROUNDING ELECTRODE CONDUCTOR.
 400A SERVICE INDICATED.
  
 3)NOTE: PLEASE SEE OCP SHOWN FOR 7.5KW
 HEAT ON AHU #3,
  
 4)NOTE: PLEASE SEE PLANS DO NOT SHOW
 GFI RECEPT FOR WHIRLPOOL TUB AS SHOWN
 ON PANEL SCHEDULE.
  
 5)NOTE: PLEASE SEE 210.52C1-5 FOR RECEPT
 REQUIRED ALONG COUNTERSPACE. ?
  
 6)NOTE: PLEASE SEE 210.52 FOR RECEPT IN
 BEDRM #2
  
 7) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 8)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2006-02-15 Cont ID  
Sent By adarroug Date 2006-02-15 Time 11:48 Rev Time 0.00
Received By adarroug Date 2006-02-15 Time 11:48 Sent To E
Notes
2006-02-15 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-01-22 Cont ID  
Sent By adarroug Date 2006-01-22 Time 12:52 Rev Time 0.00
Received By adarroug Date 2006-01-22 Time 12:52 Sent To E
Notes
2006-01-22 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-12-30 Cont ID  
Sent By ptjomsto Date 2005-12-30 Time 13:41 Rev Time 0.00
Received By ptjomsto Date 2005-12-30 Time 13:41 Sent To  
Notes
2005-12-30 00:00:00REV/ELEC GIVEN TO DEWEY

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-12-28 Cont ID  
Sent By adarroug Date 2005-12-28 Time 11:29 Rev Time 0.00
Received By adarroug Date 2005-12-28 Time 11:29 Sent To E
Notes
2005-12-28 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-11-28 Cont ID  
Sent By adarroug Date 2005-11-28 Time 15:51 Rev Time 0.00
Received By adarroug Date 2005-11-28 Time 15:51 Sent To E
Notes
2005-11-28 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-10-12 Cont ID  
Sent By adarroug Date 2005-10-12 Time 13:06 Rev Time 0.00
Received By adarroug Date 2005-10-12 Time 13:06 Sent To E
Notes
2005-10-12 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-05-10 Cont ID  
Sent By adarroug Date 2005-05-10 Time 12:16 Rev Time 0.00
Received By adarroug Date 2005-05-10 Time 12:16 Sent To E
Notes
2005-05-10 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-04-14 Cont ID  
Sent By adarroug Date 2005-04-14 Time 17:48 Rev Time 0.00
Received By adarroug Date 2005-04-14 Time 17:48 Sent To E
Notes
2005-04-14 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-03-09 Cont ID  
Sent By adarroug Date 2005-03-09 Time 14:53 Rev Time 0.00
Received By adarroug Date 2005-03-09 Time 14:53 Sent To M
Notes
2005-03-09 00:00:00TO PKRAUSS BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-05 Time 14:29 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 14:29 Sent To B
Notes
2004-10-05 00:00:00TO LS DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-26 Cont ID  
Sent By csiegber Date 2004-07-26 Time 09:55 Rev Time 0.00
Received By csiegber Date 2004-07-26 Time 09:55 Sent To E
Notes
2004-07-26 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-19 Cont ID  
Sent By csiegber Date 2004-07-19 Time 12:05 Rev Time 0.00
Received By csiegber Date 2004-07-19 Time 12:05 Sent To E
Notes
2004-07-19 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-14 Cont ID  
Sent By mmclean Date 2004-07-06 Time 12:27 Rev Time 0.00
Received By lsmith Date 2004-06-30 Time 15:03 Sent To  
Notes
2004-07-06 00:00:00TO SFD RACK/E
2004-06-30 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-03-21 Cont ID  
Sent By pkrauss Date 2005-03-21 Time 06:53 Rev Time 0.30
Received By pkrauss Date 2005-03-17 Time 16:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-07-07 Cont ID  
Sent By dpalmer Date 2004-07-06 Time 16:43 Rev Time 0.35
Received By pkrauss Date 2004-07-07 Time 16:00 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-07-10 Cont ID  
Sent By pkrauss Date 2004-07-07 Time 16:26 Rev Time 0.75
Received By jleech Date 2004-07-10 Time 07:14 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-07-14 Cont ID  
Sent By mmclean Date 2004-07-06 Time 12:27 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
2004-07-06 00:00:00GRACE IS OUT ON VACATION.PLEASE PASS
 ON & RETURN TO ZONING FOR LAST TO REVIEW