Plan Review Details - Permit 04061317
Plan Review Stops For Permit 04061317
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-02-08 Cont ID  
Sent By lsmith Date 2005-02-08 Time 08:25 Rev Time 0.50
Received By lsmith Date 2005-02-08 Time 08:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-08-02 Cont ID  
Sent By dpalmer Date 2004-08-17 Time 08:46 Rev Time 0.50
Received By lsmith Date 2004-08-02 Time 07:49 Sent To  
Notes
2004-08-02 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. SEE ELECTRICAL NOTES:ONLY ONE SET O
 F PLANS SIGNED & SEALED. NEED TWO.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-01-24 Cont ID  
Sent By dpalmer Date 2005-01-24 Time 19:12 Rev Time 0.20
Received By dpalmer Date 2005-01-24 Time 19:12 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-08-27 Cont ID  
Sent By dpalmer Date 2004-08-27 Time 07:32 Rev Time 0.50
Received By dpalmer Date 2004-08-27 Time 07:14 Sent To  
Notes
2004-08-27 00:00:00**************** UNSAT 3RD REVIEW *****
  
 1)NOTE: PLEASE SEE SAME NOTES AS THE
 TWO PREVIOUS REVIEWS. PLEASE SEE THE
 SAME PLANS HAVE COME BACK IN W/ NO
 CHANGES MADE.
 PLEASE SEE A 4X FEE FOR PLAN REVIEW AS
 PER FS 553.80(2)(B). THIS WAS GIVEN AS
 A NOTICE ON PREVIOUS REVIEW.
 PLEASE SEE BZ # 245400 $864.00 MUST BE
 PAID BEFORE PLANS ARE RE-SUBMITTED FOR
 NEXT REVIEW.
 PLANS ARE BEING SENT TO"B" BOX OUTFRONT
 AND WILL NOT BE PROCESSED ANY FURTHER
 UNTIL PREVIOUS RE-SUB IS PAID.
 CALLED AND LEFT MESSAGE ON PETER'S VM.
 ONCE RE-SUB FEE IS PAID THEN PLANS CAN
 BE PROCESSED TO OTHER TRADES.
  
 PLEASE SEE NOTES ON PREVIOUS REVIEW,IF
 PLANS COME BACK IN W/OUT COMMENTS
 ADDRESSED, AN ADDTIONAL 4X FEE WILL BE
 ACCESED AND PLANS/PACKAGE WILL BE SENT
 TO STATE FBPE'S.
 PLEASE SEE ONE SET OF PLANS ARE NOW
 BEING RETAINED FOR FILE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-08-17 Cont ID  
Sent By csiegber Date 2004-08-24 Time 15:51 Rev Time 0.25
Received By dpalmer Date 2004-08-17 Time 08:42 Sent To B
Notes
2004-08-17 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE SEE NOTES FROM PREVIOUS
 REVIEW.
 BOTH NOTES WERE NOT ADDRESSED.
 PLEASE SEE ONE SET STILL BEING SUBMITTED
 NOT SIGNED AND SEALED. IF THIRD SET IS
 NOT DESIRED TO BE STAMPED, PLEASE DO NOT
 SUBMIT.
 FAC 61G15-23.002 REQUIRES ALL SETS TO BE
 SIGNED DATED AND SEALED.
 THERE WERE NO CHANGES FROM NOTE #2 FROM
 FIRST REVIEW?
  
 2)NOTE: PLEASE NOW SEE ATTACHED COPY OF
 FS 553.80(2)(B) WITH RESPECT TO PLAN
 REVIEWS AND DESIGN PROFESSIONAL.
 THIS IS ONLY A NOTICE GIVEN AT THIS TIME
 IF PLANS COME BACK WITH ANY OF THE SAME
 COMMENTS FROM PREVIOUS REVIEWS NOT
 BEING ADDRESSED, A 4X FEE SHALL BE ADDED
 PER FS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-07-19 Cont ID  
Sent By kstevens Date 2004-08-16 Time 17:50 Rev Time 0.33
Received By dpalmer Date 2004-07-19 Time 13:43 Sent To P
Notes
2004-07-19 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002.
 PLEASE SEE ONLY ONE SET OF SIGNED AND
 SEALED PLANS SUBMITTED.
  
 2)NOTE: PLEASE SEE RISER INDICATES A
 NEW SUB-PANEL. PLEASE SHOW SIZE OF OCP,
 AWG AND CONDUIT FEEDING NEW PANEL.
 PLEASE INDICATE #AND SIZE OF CONDUCTORS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-01-24 Cont ID  
Sent By mjacobs Date 2005-01-24 Time 07:02 Rev Time 0.00
Received By mjacobs Date 2005-01-24 Time 07:02 Sent To E
Notes
2005-01-24 00:00:00TO "DP" DESK/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-08-24 Cont ID  
Sent By csiegber Date 2004-08-24 Time 15:51 Rev Time 0.00
Received By csiegber Date 2004-08-24 Time 15:51 Sent To E
Notes
2004-08-24 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-08-06 Cont ID  
Sent By csiegber Date 2004-08-06 Time 14:20 Rev Time 0.00
Received By csiegber Date 2004-08-06 Time 14:20 Sent To P
Notes
2004-08-06 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-07-19 Cont ID  
Sent By csiegber Date 2004-07-19 Time 12:35 Rev Time 0.00
Received By csiegber Date 2004-07-19 Time 12:35 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-14 Cont ID  
Sent By mmclean Date 2004-07-19 Time 11:40 Rev Time 0.00
Received By csiegber Date 2004-07-14 Time 14:40 Sent To Z
Notes
2004-07-14 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-08 Cont ID  
Sent By mmclean Date 2004-07-12 Time 10:51 Rev Time 0.00
Received By csiegber Date 2004-07-08 Time 16:33 Sent To Z
Notes
2004-07-08 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-29 Cont ID  
Sent By csiegber Date 2004-06-29 Time 13:50 Rev Time 0.00
Received By csiegber Date 2004-06-29 Time 13:50 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-02-05 Cont ID  
Sent By pschmitz Date 2005-02-05 Time 13:02 Rev Time 0.00
Received By pschmitz Date 2005-02-05 Time 13:02 Sent To B
Notes
2005-02-05 00:00:00BACK FLOW PREVENTER INSTALLED PRIOR TO
 STARTING WORK ON POOL.

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-08-16 Cont ID  
Sent By kstevens Date 2004-08-16 Time 17:50 Rev Time 0.33
Received By kstevens Date 2004-08-16 Time 17:49 Sent To E
Notes
2004-08-16 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A) COMMENTS FROM PREVIOUS REVIEW HAVE
 NOT BEEN ADDRESSED. SEE ATTACHED SHEET
 OF COMMENTS FROM FIRST REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-07-31 Cont ID  
Sent By csiegber Date 2004-08-06 Time 14:21 Rev Time 1.00
Received By kstevens Date 2004-07-31 Time 17:32 Sent To B
Notes
2004-07-31 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) POOL LAYOUT SHOWS 8 INLETS, BUT POOL
 SPECIFICATIONS CALLS FOR 3 INLETS. ALSO
 WATER FEATURES INDICATE A 24" SPILLWAY,
 BUT SPA INFORMATION AT POOL LAYOUT DOES
 NOT INDICATE SPILLWAY. PLEASE CORRELATE
 PLANS AND SPECIFICATIONS.
 2) SECOND SET OF POOL PLANS ARE NOT
 SIGNED, SEALED, AND DATED AS REQUIRED IN
 FS 471.025 AND FAC 62G25-34.002(1)(2).
 3) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 A) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 C) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2004-07-19 Cont ID  
Sent By mmclean Date 2004-07-19 Time 11:40 Rev Time 0.00
Received By mmclean Date 2004-07-19 Time 11:40 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2004-07-12 Cont ID  
Sent By csiegber Date 2004-07-14 Time 14:41 Rev Time 0.00
Received By mmclean Date 2004-07-12 Time 10:51 Sent To I
Notes
2004-07-12 00:00:00DENIED, DECK MUST BE 2FT ON ZERO SIDE
 CALLED PETER FILE UNDER B FOR P/U MM

Review Stop Z ZONING
Rev No 1 Status F Date 2004-06-30 Cont ID  
Sent By csiegber Date 2004-07-08 Time 16:33 Rev Time 0.00
Received By mmclean Date 2004-06-30 Time 16:50 Sent To  
Notes
2004-06-30 00:00:00DENIED, DECK MUST BE 2FT ON ZERO SIDE.
 CALLED PETER AND LEFT MSG ON VOICE MAIL
 FILE UNDER B FOR P/U MM