Plan Review Details - Permit 04061232
Plan Review Stops For Permit 04061232
Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2005-08-29 Cont ID  
Sent By shill Date 2005-08-29 Time 10:08 Rev Time 0.50
Received By shill Date 2005-08-29 Time 10:08 Sent To  
Notes
2005-08-29 00:00:00REVISED A2, 2.1, 3.2 DATED 8/17/05

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status F Date 2005-08-19 Cont ID  
Sent By shill Date 2005-08-19 Time 16:43 Rev Time 0.00
Received By shill Date 2005-08-19 Time 16:43 Sent To PC
Notes
2005-08-19 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)SEE FBC106.4.2.THIS WAS A PROVISO
 ON THE PLAN.PLEASE READ AND PROVIDE AN
 AFFIDAVIT AND COMPUTATIONS.
  
 2.)THE LETTER SUBMITTED STATES A
 DESIGN FLOOR LOAD OF 50PSF.SEE FBC
 TABLE 1604.1.THIS IS EITHER LIGHT OR
 HEAVY STORAGE, 125 OR 250 PSF.STATE
 WHETHER IT IS LIGHT OR HEAVY STORAGE,
 DESIGN LOAD, AND PROVIDE AN AFFIDAVIT
 AND CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2005-05-20 Cont ID  
Sent By shill Date 2005-05-20 Time 08:58 Rev Time 1.00
Received By shill Date 2005-05-20 Time 08:58 Sent To  
Notes
2005-05-20 00:00:00****PROVISO****
  
 ***PROVIDE AFFIDAVIT***FBC106.4.2 (RE
 STORAGE OCCUPANCY). IT SHALL BE THE
 RESPONSIBILITY OF THE OWNER, AGENT,
 PROPIETOR OR OCCUPANT OF GROUP S AND
 GROUP F OCCUPANCIES, OR ANY OCCUPANCY
 WHERE EXCESSIVE FLOOR LOADING IS LIKELY
 TO OCCUR, TO EMPLOY A COMPETENT
 ARCHITECT OR ENGINEER IN COMPUTING THE
 SAFE FLOOR LOAD CAPACITY. ALL SUCH
 COMPUTATIONS SHALL BE ACCOMPANIED BY AN
 AFFADAVIT FROM THE ARCHITECT OR ENGINEER
 STATING THE SAFE ALLOWABLE FLOOR LOADS
 ON EACH FLOOR IN POUNDS PER SQ FT.THE
 COMPUTATIONS & AFFADAVIT SHALL BE FILED
 AS A PERMANENT RECORD OF THE BLDG DEPT.
  
 ***PROVIDE SIGNAGE***FBC106.4.3.SIGNS
 REQUIRED. IN EVERY BUILDING OR PART OF A
 BUILDING USED FOR STORAGE, INDUSTRIAL OR
 HAZARDOUS PURPOSES, THE SAFE FLOOR
 LOADS, AS REVIEWED BY THE BUILDING
 OFFICIAL ON THE PLAN, SHALL BE MARKED ON
 PLATES OF APPROVED DE SIGN WHICH SHALL
 BE SUPPLIED & SECURELY AFFIXED BY THE
 OWNER OF THE BUILDING IN A CONSPICUOUS
 PLACE IN EACH STORY TO WHICH THEY
 RELATE. SUCH PLATES SHALL NOT BE REMOVED
 OR DEFACED, & IF LOST, REMOVED THE OWNER
 OF THE BUILDING SHALL REPLACE THEM.
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2005-05-19 Cont ID  
Sent By shill Date 2005-05-19 Time 13:11 Rev Time 2.00
Received By shill Date 2005-05-19 Time 11:42 Sent To PC
Notes
2005-05-19 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)TWO SETS OF PLANS SUBMITTED.
 PLEASE COLLATE SHEETS INTO ONE SET FOR
 REVIEW/ISSUANCE.
  
 2.)THE UL DETAIL REQUESTED HAS NOT
 BEEN INCORPORATED INTO THE PLAN AS
 REQUESTED BY THE PREVIOUS REVIEW.A
 PHOTOCOPY OF THE UL ASSEMBLY HAS BEEN
 PROVIDED FOR YOU; PLEASE STAPLE INTO THE
 PLAN.HOWEVER IN THE FUTURE A FIRE
 SEPARATION IS TO INCLUDE A DETAIL, NOT
 JUST A UL REFERENCE NUMBER.
  
  
  
 ****PROVISO****
  
 ***PROVIDE AFFIDAVIT***FBC106.4.2 (RE
 STORAGE OCCUPANCY). IT SHALL BE THE
 RESPONSIBILITY OF THE OWNER, AGENT,
 PROPIETOR OR OCCUPANT OF GROUP S AND
 GROUP F OCCUPANCIES, OR ANY OCCUPANCY
 WHERE EXCESSIVE FLOOR LOADING IS LIKELY
 TO OCCUR, TO EMPLOY A COMPETENT
 ARCHITECT OR ENGINEER IN COMPUTING THE
 SAFE FLOOR LOAD CAPACITY. ALL SUCH
 COMPUTATIONS SHALL BE ACCOMPANIED BY AN
 AFFADAVIT FROM THE ARCHITECT OR ENGINEER
 STATING THE SAFE ALLOWABLE FLOOR LOADS
 ON EACH FLOOR IN POUNDS PER SQ FT.THE
 COMPUTATIONS & AFFADAVIT SHALL BE FILED
 AS A PERMANENT RECORD OF THE BLDG DEPT.
  
 ***PROVIDE SIGNAGE***FBC106.4.3.SIGNS
 REQUIRED. IN EVERY BUILDING OR PART OF A
 BUILDING USED FOR STORAGE, INDUSTRIAL OR
 HAZARDOUS PURPOSES, THE SAFE FLOOR
 LOADS, AS REVIEWED BY THE BUILDING
 OFFICIAL ON THE PLAN, SHALL BE MARKED ON
 PLATES OF APPROVED DE SIGN WHICH SHALL
 BE SUPPLIED & SECURELY AFFIXED BY THE
 OWNER OF THE BUILDING IN A CONSPICUOUS
 PLACE IN EACH STORY TO WHICH THEY
 RELATE. SUCH PLATES SHALL NOT BE REMOVED
 OR DEFACED, & IF LOST, REMOVED THE OWNER
 OF THE BUILDING SHALL REPLACE THEM.
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2005-05-09 Cont ID  
Sent By shill Date 2005-05-09 Time 08:21 Rev Time 0.50
Received By shill Date 2005-05-09 Time 08:21 Sent To PC
Notes
2005-05-09 00:00:00REVISION PREPARED BY BIJAN PARSSI, PE,
 A/C CURB PLAN AND OPENING DETAIL FOR
 DOOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2005-05-05 Cont ID  
Sent By shill Date 2005-05-05 Time 09:59 Rev Time 3.00
Received By shill Date 2005-05-05 Time 09:59 Sent To PC
Notes
2005-05-05 00:00:00REVISION DATED 3/30/05
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) SHEET A1.1 SHOWS THE FREIGHT LIFT AS
 REMAINING, S1 SHOWS THE LIFT REMOVED.
 STRUCTURALS AND ARCHITECTURALS SHOULD BE
 CONSISTENT.
  
 2.)PROVIDE STAIR WIDTHS, FBC1004.
  
 3.)DECLARE AN OCCUPANT LOAD, FBC TABLE
 1003.1.
  
 4.)THE PRODUCT APPROVAL FOR THE
 EXTERIOR DOOR AND THE ENERGY CALC HAVE
 BEEN STAMPED AND A COPY RETAINED.
  
 5.)SEE PREVIOUS LIST IN REGARDS TO
 VERTICAL ACCESSIBILITY, FBC11-4.1.3.
 HOW IS THIS BEING ADDRESSED?
  
 6.)A 1 HR PROTECTED STAIR IS SHOWN
 A1.0.PLEASE EXPLAIN HOW 1 HR IS
 MAINTAINED THROUGH THE SECOND FLOOR.
 SEE FBC1006.1.3.1, 705.1.2.OPENINGS
 ARE SHOWN WITHOUT FIRE RESISTANCE
 INFORMATION.
  
 7.)A1.2, STAIR DETAILS HAS TWO DETAILS
 WHICH ARE ILLEGIBLE.
  
 8.)A HANDRAIL IN COMPLIANCE WITH
 FBC1007.5 IS REQUIRED ON BOTH SIDES OF
 THE STAIRS FBC1007.5.2.ONLY ONE IS
 SHOWN.
  
 9.)SHEET A1.2, AN EXIT CORRIDOR IS
 SHOWN.WHERE IS THIS ON THE PLAN?IT
 REFERS TO UL-U465; PROVIDE THIS DETAIL
 ON THE PLAN.
  
 10.) WHEN RESUBMITTING, PLEASE PROVIDE A
 TRANSMITTAL SHEET EXPLAINING HOW THESE
 ITEMS ARE BEING ADDRESSED.
  
 11.)NOTE - STRUCTURALS SUBMITTED
 SEPARATELY REVIEWED AGAIN AND PUT WITH
 ARCHITECTURAL REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2005-04-29 Cont ID  
Sent By shill Date 2005-04-29 Time 10:43 Rev Time 1.00
Received By shill Date 2005-04-29 Time 10:43 Sent To PC
Notes
2005-04-29 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE PREVIOUS REVISION WAS DENIED
 WITH COMMENTS REGARDING EGRESS, VERTICAL
 ACCESSIBILITY AND BUILDING TYPE. THERE
 IS A CONFLICT BETWEEN THE DENIED
 ARCHITECTURALS AND THE STRUCTURAL PLANS
 SUBMITTED.AS THESE STRUCTURALS DO NOT
 CORRELATE WITH ANYTHING APPROVED IN OUR
 FILE, PLEASE SUBMIT EITHER WITH THE
 REVISED ARCHITECTURALS OR AFTER THEY
 HAVE BEEN REVIEWED FOR CODE COMPLIANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2005-04-22 Cont ID  
Sent By shill Date 2005-04-22 Time 10:43 Rev Time 0.50
Received By shill Date 2005-04-22 Time 10:43 Sent To PC
Notes
2005-04-22 00:00:00SEALED LETTER FROM JIM PAYNE; BOTKIN
 PARSSI IS EOR FOR JOB (ONLY ONE COPY
 SUBMITTED)

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2005-04-06 Cont ID  
Sent By shill Date 2005-04-06 Time 10:25 Rev Time 0.50
Received By shill Date 2005-04-06 Time 10:25 Sent To PC
Notes
2005-04-06 00:00:00****CORRECTIONS****
 VARIOUS DETAILS PREPARED BY BIJAN
 PARSSI, PE
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE FORMER ARCHITECT AND ENGINEER
 HAVE SUBMITTED LETTERS STATED THAT THEY
 ARE NO LONGER DOR/EOR OF THE PROJECT.
 JIM PAINE, ARCHITECT, HAS SUBMITTED NEW
 PLANS.IS BIJAN PARSSI, PE THE NEW EOR
 FOR THIS PROJECT?OR IS THIS DELEGATED
 ENGINEERING?IF THIS IS DELEGATED
 ENGINEERING, THE DETAILS ARE TO BE
 REVIEWED BY DOR.IF HE IS THE NEW EOR,
 SUBMIT A LETTER STATING THIS AS ALL
 STRUCTURALS TO DATE HAVE BEEN SUBMITTED
 BY JIM PAINE.
  
 2.)THE COLUMN CONNECTION PLAN IS NOT
 SEALED.
  
 3.)AS PER CONVERSATION WITH THE
 CONTRACTOR, THE COLUMN CONNECTION PLAN
 IS SHOWING A C CHANNEL AND A STEEL
 COLUMN.THE DIMENSION 4X4X4 IS
 CONFUSING, IMPLIES A HEIGHT OF 4" RATHER
 THAN A COLUMN THE FULL HEIGHT.THE C
 CHANNEL IS SHOWN GRAPHICALLY BUT NOT
 SPECIFIED, WHAT SIZE?THE ANCHORING OF
 THE STEEL COLUMN AND C CHANNEL IS NOT
 SPECIFIED.ANCHORING AT THE BOTTOM OF
 THE COLUMN IS SPECIFIED, ASSUMING TO
 EXISTING SLAB ON 1ST FLOOR AS A CONCRETE
 ANCHOR IS SPECIFIED.IS THERE A BASE
 PLATE FOR THE COLUMN?SPECIFY WHERE
 THIS DETAIL IS TO BE USED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-03-24 Cont ID  
Sent By shill Date 2005-03-24 Time 13:26 Rev Time 5.00
Received By shill Date 2005-03-23 Time 15:15 Sent To P
Notes
2005-03-24 00:00:00PERMIT #04061232
  
 ****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)TYPE IV IS DECLARED ON THE COVER
 SHEET.WOOD COLUMNS ARE SHOWN ON A1.0.
 ALSO A1.0 STATES THAT THE FLOOR FINISH
 IS WOOD, BUT A1.1 NOTES AN EXISTING WOOD
 DECK.IS THE WOOD FLOOR NOTED A FLOOR
 FINISH OR THE FLOOR FRAMING?OUR PLANS
 CURRENTLY ON FILE SHOW WOOD JOISTS FOR
 THE FLOOR FRAMING.SEE FBC606 REGARDING
 DEFINITION OF TYPE IV BUILDING.
  
 2.)THE COVER SHEET SHOWS 5739 SF FOR
 FIRST FLOOR TWICE.PLEASE NOTE SECOND
 FLOOR SQUARE FOOTAGE.
  
 3.)SHEET A1.0 HAS A NOTE REGARDING A 1
 HOUR SEPARATION.WHAT IS THE PURPOSE OF
 THIS SEPARATION?HOW WILL THE 1 HOUR
 SEPARATION BE MAINTAINED WHERE THE WOOD
 COLUMNS MEET THE BOTTOM OF THE FLOOR
 CEILING ASSEMBLY?A FREIGHT LIFT IS
 SHOWN ON A1.0; PROVIDE 1 HR FIRE RATING
 INFORMATION.
  
 4.)SHEET A1.0 BOTTOM RIGHT CORNER OF
 PLAN SHOWS 1HR ENCLOSURE (SEE DETAIL).
 NO DETAIL PROVIDED AND IT IS UNCLEAR HOW
 THE 1 HR SEPARATION IS MAINTAINED
 BETWEEN THE FIRST AND SECOND FLOORS AS
 THE FLOOR PLAN SHOWS A WALL WHICH DOES
 NOT ENCLOSE THE STAIRS.
  
 5.)THERE IS A NOTE ON SHEET A1.3 THAT
 ALL EXTERIOR OPENINGS ARE EXISTING.
 OPENINGS AFFECTED BY THE SCOPE OF WORK
 ON THIS PERMIT ARE TO BE CODE COMPLIANT
 AND SHOW COMPLIANCE ON THE PLAN.ALSO
 THERE IS A NEW DOOR SHOWN.
  
 6.)PLEASE SEE FBC1006.1.3.2.IF THIS
 BUILDING IS A TYPE V, THE STAIRWAY AT
 THE TOP LEFT IS TO HAVE 3 HR PROTECTION.
  
 7.)BASED ON PROPERTY APPRAISER?S
 VALUATION, THIS IS AN OVER 50%
 IMPROVEMENT, FBC3401.7.2.6.
  
 8.)OPENINGS IN THE EXIT STAIR ARE
 PROHIBITED EXCEPT AS NOTED IN
 FBC1006.1.3.1 (WINDOW SHOWN IN
 STAIRWAY).
  
 9.)SHOW OPENING PROTECTIVES FOR THE
 STAIRS AS REQUIRED BY FBC TABLE 705.1.2.
  
 10.)DOOR 2, 1ST FLOOR, DOES NOT APPEAR
 TO LEAD ANYWHERE.IF IT IS AN OPENING
 INTO THE STAIR, INDICATE OPENING
 PROTECTIVE REQUIREMENT.
  
 11.) PROVIDE TEST REPORTS AND FLORIDA
 STATE OR LOCAL PRODUCT APPROVAL FOR THE
 NEW EXTERIOR DOOR.
  
 12.) PROVIDE GUARDRAIL AND HANDRAIL
 DETAILS.NOTE DESIGN CRITERIA IN
 COMPLIANCE WITH FBC1608.1.1 (HANDRAIL)
 AND FBC 1608.2.2 (GUARDRAIL).COMPLY
 WITH ALL REQUIREMENTS OF FBC CHAPTERS 10
 AND 11.
  
 13.) PROVIDE ACCESSIBILITY DETAILS;
 ACCESSIBLE ENTRY, BATHROOM DETAILS
 INCLUDING DIMENSIONS FOR GRAB BARS, LAV,
 WC FBC CHAPTER 11.
  
 14.) PROVIDE LOADING INFORMATION FOR
 ROOFTOP MECHANICAL EQUIPMENT, DESIGN
 LOAD LIMITATIONS OF EXISTING ROOF.
  
 15.) ENERGY CALCS REQUIRED, FBC13.
  
 16.) VERTICAL ACCESSIBILITY REQUIRED,
 FBC11-4.1.3.
  
 17.) PROVIDE DESIGN PRESSURES FOR THE
 EXTERIOR DOOR AND DESIGN CRITERIA
 FBC1606.1.7.
  
 18.) DMP REVIEW REQUIRED.WHEN
 RESUBMITTING, PLEASE INDICATE THAT A
 ZONING REVIEW IS REQUIRED ON THE
 RESUBMITTAL SHEET TO HELP EXPEDITE PLAN
 REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-12-23 Cont ID  
Sent By lsmith Date 2004-12-23 Time 09:57 Rev Time 1.00
Received By lsmith Date 2004-12-23 Time 09:57 Sent To  
Notes
2004-12-23 00:00:00BUILDING PLAN REVIEW: PROVISO
  
 1. SUBMIT MFGRS. SPECS ON STAIR SYSTEM.
  
 2. SUBMIT MFGRS. SPECS. ON ELEVATOR
  
 3. THE NOTICE OF COMMENCEMENT HAS
 EXPIRED. A NEW NOTICE OF COMMENCEMENT
 MUST BE FILED AT THE COUNTY CLERK OFFICE
 & SUBMITTED BEFORE A PERMIT CAN BE
 ISSUED.
  
 NOTE: DRAWING SHEET INDEX SHOWS SHEETS
 S1, S2, & S3.THESE PLANS ARE NOT
 ATTACHED.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLAN REVIEWER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-11-19 Cont ID  
Sent By lsmith Date 2004-11-19 Time 08:12 Rev Time 1.50
Received By lsmith Date 2004-11-19 Time 08:11 Sent To  
Notes
2004-11-19 00:00:00BUILDING PLAN REVIEW FAILED:
  
 1. SUBMIT MFGRS. SPECS ON STAIR
 SYSTEMS.
  
 2. SUBMIT MFGRS. SHEETS ON ELEVATOR.
  
 3. SUBMIT FLORIDA PRODUCT APPROVAL FOR
 THE NEW DOOR ON THE WEST ELEVATION OF
 BUILDING.
  
 4. PER SEC. 481.221 ALL PLANS SIGNED BY
 ARCHITECT MUST BE DATED.
  
 5.
 SUBMIT DETAIL FOR PENATRATIONS THROUGH
 2ND FLOOR & ROOF FOR EXHAUST SYSTEM.
 SEE MECHANICAL COMMENTS.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-08-30 Cont ID  
Sent By lsmith Date 2004-08-30 Time 13:38 Rev Time 1.50
Received By lsmith Date 2004-08-30 Time 13:38 Sent To  
Notes
2004-08-30 00:00:00BUILDING PLAN REVIEW: PROVISO
  
 1. SUBMIT MFGRS. SHEETS ON STAIR SYSTEM
  
 2. SUBMIT MFGRS. SHEETS ON ELEVATOR
  
 3. SUBMIT DETAIL FOR PENATRATIONS THROUG
 H 2ND FLOOR & ROOF FOR EXHAUST SYSTEM.
 SEE SHEETS M1 & M2 & MECHANICAL NOTES.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-15 Cont ID  
Sent By lsmith Date 2004-06-30 Time 14:41 Rev Time 1.50
Received By lsmith Date 2004-06-30 Time 14:41 Sent To  
Notes
2004-07-15 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. SEE ELEC & MECH NOTES ON SIGNATURE
 ON PLANS.
  
 2. SUBMIT PRODUCT APPROVALS FOR SKYLIGHT
 (FLORIDA & DADE COUNTY)
  
 3. SUBMIT SHOP DRAWINGS FOR METAL STAIRS
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2005-08-18 Cont ID  
Sent By dpalmer Date 2005-08-18 Time 19:16 Rev Time 0.60
Received By dpalmer Date 2005-08-18 Time 18:47 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2005-05-18 Cont ID  
Sent By dpalmer Date 2005-05-18 Time 10:02 Rev Time 0.30
Received By dpalmer Date 2005-05-18 Time 10:02 Sent To  
Notes
2005-05-18 00:00:00REDLINED 250.122 FOR SIZING OF EQUIPMENT
 GROUNDS.

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2005-05-17 Cont ID  
Sent By dpalmer Date 2005-05-17 Time 07:04 Rev Time 0.25
Received By dpalmer Date 2005-05-17 Time 07:04 Sent To B
Notes
2005-05-17 00:00:00********* UNSAT ************
  
 1)NOTE: PLEASE SEE ELECTRICAL REVSIONS
 SUBMITTED WITHOUT ANY REVSIONS BEING
 MADE.
 PLEASE SEE THESE PLANS ARE THE SAME
 ELECTRICAL PLANS REVIEWED AND STAMPED ON
 PREVIOUS SUBMITTAL WHICH WERE REVIEWED
 AND STAMPED ON MAY 11TH.
 IF REVISIONS ARE TO BE MADE, PLEASE
 REVISE,IDENTIFY WITH CLOUDS/TRIANGKE AND
 CORRELATE WITH REV'S DATED AND SHOWN IN
 TITLE BLOCK AREA.
  
 *** NOTE**
 PLEASE SEE EQUIPMENT GROUNDING CONDUCTOR
 FROM MAIN DISCONNECT TO PANEL STILL
 BEING SHOWN AS 1/0?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2005-05-11 Cont ID  
Sent By dpalmer Date 2005-05-11 Time 11:40 Rev Time 0.30
Received By dpalmer Date 2005-05-11 Time 11:37 Sent To I
Notes
2005-05-11 00:00:00PLANS REMOVED FROM INCOMING, REVIEWED
 FOR ELECTRICAL , STAMPED ELECTRICAL AND
 SENT BACK TO INCOMING.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2005-04-05 Cont ID  
Sent By dpalmer Date 2005-04-05 Time 08:50 Rev Time 0.50
Received By dpalmer Date 2005-04-05 Time 08:50 Sent To  
Notes
2005-04-05 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEE NOTES FROM PREVIOUS
 REVIEW AND REVIEW ON 11/29/04
  
 2)NOTE: PLEASE SEE AS REQUESTED ON
 PREVIOUS REVIEW: LETTERS FROM BOTH THE
 ORIGINAL ARCHITECT AND ENGINEER WERE
 REQUESTED TO RELEASE THEM FROM DESIGNERS
 OF RECORD. THIS REQUEST WAS TO EACH HAVE
 SIGNED, DATED, SEALED AND NOTORIZED
 LETTERS.
 PLEASE SEE ENGINEER'S LETTER WAS NOT
 NOTORIZED AND ARCH'S LETTER WAS NOT
 SEALED, DATED OR NOTORIZED.
  
 3)NOTE: PLEASE SEE THE FOLLOWING EXCERPT
 TAKEN DIRECTLY FROM NOTES ON 11/29/04
 FOR REDLINED PLANS.
  
 ***** PLANS REDLINED ******
  
 1)NOTE: PLEASE SEE GROUNDING ELECTRODE
 CONDUCTOR STILL NOT SHOWN PER 250.66.
 TWO SETS OF 3/0'S,,,, 1/0 MIN GEC.
  
  
 2)NOTE: PLEASE ALSO SEE AN EQUIPMENT
 GROUNDING CONDUCTOR IS NOW ADDED FROM
 METER TO MAIN? AN EQUIPMENT GRND IS NOT
 INSTALLED UNTIL AFTER THE FIRST MEANS OF
 DISCONNECT.
 250.6, 250.24
  
  
 ** BOTH OF THE ABOVE WERE REDLINED ON
 PLANS. IF ANY REV'S ARE MADE TO PLANS,
 PLEASE ALSO CORRECT THE ABOVE AT THAT
 TIME. ***
  
 4)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EM/EXT LTS. THIS WAS NOTED
 ON ALL PREVIOUS REVIEWS AND SOME
 CIRCUITING IS STILL NOT SHOWN AND SOME
 NOT PER 700.12E.
  
 PLEASE SEE FS 553.80(2)(B) WITH RESPECT
 TO DESIGN PROFESSIONAL. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
 PLEASE MAKE THE ABOVE CORRECTIONS AND
 SUBMIT REVISED PLANS FOR REVIEW. ONCE
 AGAIN, IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL TO GO
 OVER ANY COMMENTS.
 THIS WAS STATED ON ALL 5 PREVIOUS
 REVIEWS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2005-03-16 Cont ID  
Sent By dpalmer Date 2005-03-01 Time 06:20 Rev Time 0.50
Received By dpalmer Date 2005-03-01 Time 06:14 Sent To  
Notes
2005-03-01 00:00:00*********UNSAT*******
  
 PLEASE SEE PREVIOUS REVIEW NOTES FOR
 ITEMS REDLINED REQUESTING," IF THERE ARE
 ANY REVISIONS, PLEASE MAKE CORRECTIONS
 TO PLANS AT THAT TIME". PLEASE SEE NOTES
 FROM PREVIOUS REVIEW BELOW.
  
  
  
 1)NOTE: PLEASE SEE PLANS NOW HAVE A NEW
 ARCHITECT OF RECORD.
 PLEASE SUBMIT A SIGNED/SEALED NOTORIZED
 LETTER FOR CHANGING ARCH AND ENGINEER
 FROM EACH PERSON.
 PLEASE SEE NEW ARCHITECT MUST SUBMIT
 COMPLETE SETS OF PLANS SIGNED AND SEALED
 FOR COMPLETE SCOPE OF WORK.
  
  
 PLEASE SEE BELOW WAS REDLINED ON
 ORIGINAL PLANS AND SHOULD BE ADDRESSED
 AT THIS TIME WHEN PLANS ARE DONE.
  
 1)NOTE: PLEASE SEE GROUNDING ELECTRODE
 CONDUCTOR STILL NOT SHOWN PER 250.66.
 TWO SETS OF 3/0'S,,,, 1/0 MIN GEC.
  
  
 2)NOTE: PLEASE ALSO SEE AN EQUIPMENT
 GROUNDING CONDUCTOR IS NOW ADDED FROM
 METER TO MAIN? AN EQUIPMENT GRND IS NOT
 INSTALLED UNTIL AFTER THE FIRST MEANS OF
 DISCONNECT.
 250.6, 250.24
  
  
 3)NOTE: PLEASE SEE REDLINED EM/EXT LT
 PER
 700.12E.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-11-29 Cont ID  
Sent By dpalmer Date 2004-11-29 Time 06:36 Rev Time 0.33
Received By dpalmer Date 2004-11-29 Time 06:28 Sent To  
Notes
2004-11-29 00:00:00***** PLANS REDLINED ******
  
 1)NOTE: PLEASE SEE GROUNDING ELECTRODE
 CONDUCTOR STILL NOT SHOWN PER 250.66.
 TWO SETS OF 3/0'S,,,, 1/0 MIN GEC.
  
  
 2)NOTE: PLEASE ALSO SEE AN EQUIPMENT
 GROUNDING CONDUCTOR IS NOW ADDED FROM
 METER TO MAIN? AN EQUIPMENT GRND IS NOT
 INSTALLED UNTIL AFTER THE FIRST MEANS OF
 DISCONNECT.
 250.6, 250.24
  
  
 ** BOTH OF THE ABOVE WERE REDLINED ON
 PLANS. IF ANY REV'S ARE MADE TO PLANS,
 PLEASE ALSO CORRECT THE ABOVE AT THAT
 TIME. ***
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-10-25 Cont ID  
Sent By dpalmer Date 2004-10-25 Time 12:02 Rev Time 0.75
Received By dpalmer Date 2004-10-25 Time 12:02 Sent To  
Notes
2004-10-25 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEE NOTE#4 FROM PREVIOUS
 REVIEW. A GROUNDING ELECTRODE SYSTEM
 IS NOW SHOWN, HOWEVER SIZING OF GEC IS
 TO BE SIZED FOR THE PARALLEL 4/0'S
 PER 250.66. SHOWS A #3, WHICH IS NOT
 LARGE ENOUGH.
  
 2)NOTE : PLEASE SEE NOTE # 5FROM
 PREVIOUS REVIEW. PLEASE SEE MISSING
 LICENSE # FOR FIRM ONA-SHEETS.
 PLEASE SEE FAC 61G1-16.004 AND FS 481.-
 .219.
 THIS IS REQUIRED, WHEATHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 3)NOTE: PLEASE SEE LOAD FOR WASHER/DRYER
 IS SHOWN AS 7KW ON A 2P-30A BRKR FOR
 OCP.
 PLEASE ALSO SEE 11KW LOAD SHOWN ON A
 2P-30A BRKR FOR ELEVATOR.
  
 4)NOTE: PLEASE CLARIFY MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM MAIN TO PANEL
 AND FROM PANEL A TO B.
 250.110,250.122
  
 5)NOTE: PLEASE SEE MAIN DISCONNECT IS
 SHOWN AS MLO. APPEARS TO BE A MISPRINT??
  
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND INSERT NEW SHEETS INTO COMPLETED
 SETS FOR REVIEW AND STAMPING.
 ONE COPY OF OLD SHEETS SHOULD BE SUBMITT
 -ED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-09-01 Cont ID  
Sent By dpalmer Date 2004-09-01 Time 12:57 Rev Time 1.00
Received By dpalmer Date 2004-09-01 Time 12:43 Sent To  
Notes
2004-09-01 00:00:00********* UNSAT *************
  
 PLEASE SEE THE FOLLOWING FOR SOME NOTES
 FROM FIRST REVIEW WERE NOT ADDRESSED.
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATEW/ PANEL SCHEDULE.
 PLEASE SEE EM LTS/700.12E
  
 2)NOTE: PLEASE SEE 210.63 AND VERIFY
 GFI LOCATION FOR RTU.
  
 3)NOTE: PLEASE SEE LOAD CALCS ARE NOW
 SUBMITTED HOWEVER, ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125%.
 215.3,230.42,ETC
  
 4)NOTE: PLEASE SEE 250.50 FOR GROUNDING
 ELECTRODE SYSTEM.
 NOT SHOWN.
  
 5)NOTE: PLEASE SEE FS 481.219 AND FAC
 61G1-16.004.
 PLEASE INCLUDE ALL REQUIRED LICENSE
 #'S ON TITLE BLOCKS.
 THIS IS REQUIRED ON ALL SHEETS WHEATHER
 OR NOT COMMENT IS MADE BY OTHER REVIEWER
 'S.
  
 6)NOTE: PLEASE SEE ATTACHED COPY OF
 FS553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL.
 THIS IS ONLY A NOTICE AT THIS TIME.
  
 ***PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 DO NOT ATTACH OLD SHEETS TO PLANS.
 THESE MAY BE PLACE IN A SEPARATE ROLL
 FOR REFERENCE ONLY.
  
 PLEASE SEE OTHER COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-25 Cont ID  
Sent By dpalmer Date 2004-06-25 Time 16:02 Rev Time 0.50
Received By dpalmer Date 2004-06-25 Time 16:02 Sent To  
Notes
2004-06-25 00:00:00************* UNSAT *************
  
 1)NOTE: PLEASE SEE ELECTRICAL PLANS
 APPEAR TO BE SHOWN ON A-SHEETS LABELED
 AS REFLECTED CEILING PLANS??
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 4)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE. 215.5
 PLEASE ALSO SEE 700.12E
  
 5)NOTE: PLEASE SEE PLANS MUST CONTAIN
 LEGAL SIGNATURE AS SHOWN ON SEAL.
 PLANS APPEAR TO CONTAIN INITIALS.
 IF THIS IS INDEED "LEGAL" SIGNATURE,
 PLEASE PROVIDE A COMPLETED SIGNED, DATED
 AND SEALED NOTORIZED LETTER. PLEASE BE
 SURE NOTORY INCLUDES ALL INFORMATION AS
 REQUIRED.
 PLEASE SEE FS 481.221, WHICH REQUIRES
 SIAGNTURE.
  
 6)NOTE: PLEASE SEE FAC 61G1-16.004,
 AND FS 481.219.
 PLEASE INCLUDE ALL LICENSE #'S ON TITLE
 BLOCK AS REQUIRED PER ABOVE.
  
 7)NOTE: PLEASE INCLUDE GROUNDING ELEC-
 -TRODE SYSTEM. 250.50. NO DETAIL GIVEN.
  
 8)NOTE: PLEASE SHOW A/C EQUIPMENT ON
 PLANS AND DISC'S PER 440.11
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 AS THEY MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status N Date 2005-09-01 Cont ID  
Sent By mwennerg Date 2005-09-01 Time 14:12 Rev Time 0.00
Received By mwennerg Date 2005-09-01 Time 14:12 Sent To P
Notes
2005-09-01 00:00:00NO REVISIONS FOR FIRE OR LIFE SAFETY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2005-05-02 Cont ID  
Sent By shill Date 2005-05-19 Time 13:08 Rev Time 0.00
Received By nmccray Date 2005-05-02 Time 16:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2005-03-23 Cont ID  
Sent By mwennerg Date 2005-03-23 Time 14:51 Rev Time 0.00
Received By mwennerg Date 2005-03-23 Time 14:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status N Date 2004-12-23 Cont ID  
Sent By lmartine Date 2004-12-23 Time 16:06 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2004-12-23 00:00:00SEE NOTES FROM PREVIOUS REVIEWLM

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-11-05 Cont ID  
Sent By mcarsill Date 2004-11-05 Time 15:57 Rev Time 0.00
Received By mcarsill Date 2004-11-05 Time 15:57 Sent To  
Notes
2004-11-05 00:00:001) SEPARATE PLANS AND PERMITS
 FOR FIRE SPRINKLER REMODEL.
  
 2) FIRE ALARM SYSTEM MUST BE UL
 LISTED FOR CENTRAL STATION SERVICE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-09-15 Cont ID  
Sent By mcarsill Date 2004-09-15 Time 15:21 Rev Time 0.00
Received By mcarsill Date 2004-09-15 Time 15:21 Sent To  
Notes
2004-09-15 00:00:001) DOOR # 31 IS NOT LABELED PER THE
 DOOR SCHEDULE. THIS DOOR IS LOCATED
 IN A RATED ENCLOSURE. PLEASE REVISE
 DOOR SCHEDULE AS NECESSARY.
  
 2) NEW FIRE ALARM SYSTEM SHALL BE
 UL LISTED FOR "CENTRAL STATION
 SERVICE" AND BE THIRD PARTY
 CERTIFICATED.
  
 3) DUCT SMOKE DETECTORS SHALL CAUSE
 AN ALARM NOT A SUPERVISORY SIGNAL
 AS NOTED IN 2 C) ON PAGE FA3-3.
 SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE NEW FIRE ALARM SYSTEM.
  
 4) SEPARATE PLANS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER REMODEL.
 THE NEW FDC IS TO BE LOCATED WITHIN
 150 FEET OF A FIRE HYDRANT.
  
 5) COULD NOT LOCATE ANY FIRE
 EXTINGUISHER LOCATIONS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-07-22 Cont ID  
Sent By mwennerg Date 2004-07-22 Time 09:43 Rev Time 0.00
Received By mwennerg Date 2004-07-22 Time 09:43 Sent To  
Notes
2004-07-22 00:00:001) ADDRESS NUMBER MUST BE AT LEAST 6"
 IN HEIGHT AND CONTRAST WITH BACKGROUND.
 2) PLEASE SUBMIT SEPERATE SHOP DRAWINGS
 FOR FIRE SPRINKLER AND ALARM SYSTEM.
 3) PLEASE SUBMIT DETAILS ON STAIRS.
 4) PLEASE SUBMIT INTERIOR FINISH
 INFORMATION.
 5) PLEASE PROVIDE INFORMATION REGARDING
 FIRE DEPARTMENT ACCESS AND HYDRANT
 LOCATION.
  
 A/CAPT. MIKE WENNERGREN
 WPBFR (561) 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2005-09-28 Cont ID  
Sent By adarroug Date 2005-09-28 Time 18:56 Rev Time 0.00
Received By adarroug Date 2005-09-28 Time 18:56 Sent To  
Notes
2005-10-03 00:00:00TO "COMM" BD#21
2005-09-28 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2005-08-22 Cont ID  
Sent By adarroug Date 2005-08-22 Time 08:17 Rev Time 0.00
Received By adarroug Date 2005-08-22 Time 08:17 Sent To  
Notes
2005-08-22 00:00:00TO "COMM" BD#35

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2005-08-19 Cont ID  
Sent By adarroug Date 2005-08-19 Time 08:41 Rev Time 0.00
Received By adarroug Date 2005-08-19 Time 08:41 Sent To B
Notes
2005-08-19 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-05-13 Cont ID  
Sent By adarroug Date 2005-05-13 Time 15:59 Rev Time 0.00
Received By adarroug Date 2005-05-13 Time 15:59 Sent To E
Notes
2005-05-13 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-05-10 Cont ID  
Sent By adarroug Date 2005-05-10 Time 10:46 Rev Time 0.00
Received By adarroug Date 2005-05-10 Time 10:46 Sent To  
Notes
2005-05-10 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-05-05 Cont ID  
Sent By adarroug Date 2005-05-05 Time 12:33 Rev Time 0.00
Received By adarroug Date 2005-05-05 Time 12:33 Sent To B
Notes
2005-05-05 00:00:00TO "SHILL" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-04-22 Cont ID  
Sent By adarroug Date 2005-04-22 Time 10:46 Rev Time 0.00
Received By adarroug Date 2005-04-22 Time 10:46 Sent To B
Notes
2005-04-22 00:00:00TO "SHILL" DESK/REVISION
 TO "SHILL" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-04-21 Cont ID  
Sent By adarroug Date 2005-04-21 Time 14:13 Rev Time 0.00
Received By adarroug Date 2005-04-21 Time 14:13 Sent To B
Notes
2005-04-21 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-04-05 Cont ID  
Sent By adarroug Date 2005-04-05 Time 10:12 Rev Time 0.00
Received By adarroug Date 2005-04-05 Time 10:12 Sent To B
Notes
2005-04-05 00:00:00TO "LSMITH" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-03-31 Cont ID  
Sent By adarroug Date 2005-03-31 Time 14:09 Rev Time 0.00
Received By adarroug Date 2005-03-31 Time 14:09 Sent To  
Notes
2005-03-31 00:00:00TO "COMM" BD#2

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-02-28 Cont ID  
Sent By adarroug Date 2005-02-28 Time 12:34 Rev Time 0.00
Received By adarroug Date 2005-02-28 Time 12:34 Sent To  
Notes
2005-02-28 00:00:00TO "COMM" BD#4

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-11-24 Cont ID  
Sent By mjacobs Date 2004-11-24 Time 16:37 Rev Time 0.00
Received By mjacobs Date 2004-11-24 Time 16:36 Sent To  
Notes
2004-11-24 00:00:00SENT TO COMM BD#23

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-10-19 Cont ID  
Sent By csiegber Date 2004-10-19 Time 16:27 Rev Time 0.00
Received By csiegber Date 2004-10-19 Time 16:27 Sent To  
Notes
2004-10-19 00:00:00TO COMM BD#35

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-23 Cont ID  
Sent By csiegber Date 2004-08-23 Time 15:30 Rev Time 0.00
Received By csiegber Date 2004-08-23 Time 15:30 Sent To  
Notes
2004-08-23 00:00:00TO COMM BD#63

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-23 Cont ID  
Sent By lmartine Date 2004-07-23 Time 09:54 Rev Time 0.00
Received By lmartine Date 2004-06-25 Time 15:14 Sent To  
Notes
2004-06-25 00:00:00TO COMM BD#18

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2005-11-15 Cont ID  
Sent By pkrauss Date 2005-11-15 Time 08:29 Rev Time 0.55
Received By pkrauss Date 2005-11-15 Time 08:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2005-05-04 Cont ID  
Sent By pkrauss Date 2005-05-04 Time 14:25 Rev Time 0.55
Received By pkrauss Date 2005-05-04 Time 14:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2005-03-16 Cont ID  
Sent By pkrauss Date 2005-03-16 Time 07:24 Rev Time 0.45
Received By pkrauss Date 2005-03-16 Time 06:43 Sent To  
Notes
2005-03-16 00:00:00DENIED:
 1. REVISION SHEET SUBMITTED INDICATES A
 CHANGE IN ARCHITECT.PROVIDE A
 CERTIFIED LETTER FROM THE FORMER
 ARCHITECT OR OWNER STATING THE RELEASE
 OF THE FORMER ARCHITECT AND THE
 ASSIGNING OF THE NEW ARCHITECT.PLEASE
 NOTE, MECHANICAL PLANS WERE PREVIOUSLY
 DONE BY AN ENGINEER.WILL HE NO LONGER
 BE RESPONSIBLE FOR THE PLANS?
  
 2. PROVIDE A COMPLETE SET OF PLANS.
  
 3. INDICATE CONDENSATE. NOTE ON PLAN
 SHEET A3.3 THE CONDENSATE P-TRAP DETAIL
 (A) SLOPE TO NEAREST STORM DRAIN.
 PLEASE INDICATE CONDENSATE LINE SIZE,
 MATERIAL AND LAYOUT ON THE PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-12-06 Cont ID  
Sent By pkrauss Date 2004-12-06 Time 07:36 Rev Time 0.45
Received By pkrauss Date 2004-12-06 Time 07:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2004-11-16 Cont ID  
Sent By pkrauss Date 2004-11-16 Time 10:17 Rev Time 0.40
Received By pkrauss Date 2004-11-16 Time 08:38 Sent To  
Notes
2004-11-16 00:00:00DENIED:
 PROVISO ON REVIEW DATED 8-30-04 WAS NOT
 ADDRESSED.PLEASE PROVIDE A DETAIL FOR
 PENETRATIONS THROUGH THE FIRE RATED
 ASSEMBLIES INDICATED ON PLAN SHEET
 A4-01.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS @ (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-09-01 Cont ID  
Sent By pkrauss Date 2004-08-30 Time 10:39 Rev Time 0.45
Received By pkrauss Date 2004-08-30 Time 10:05 Sent To  
Notes
2004-08-30 00:00:00DENIED:
 PLEASE NOTE, TITLE BLOCK INDICATES
 "METRO DESIGN GROUP" WHICH REQUIRES A
 CERTIFICATE OF AUTHORIZATION #.PLEASE
 CORRECT TITLE BLOCK FOR COMPLIANCE WITH
 61G15-23.002 OF THE FAC.
  
 PROVISO:
 PLEASE NOTE, PLANS SHEET M-1 & M-1.1
 INDICATE 8" EXHAUST FROM THE FIRST FLOOR
 THROUGH THE ROOF. THE ARCHITECTURAL
 PLANS DO NOT ADDRESS PENETRATIONS
 THROUGH THE RATED FLOOR/CEILNG ASSEMBLY
 INDICATED ON PLAN SHEET A4-01.PLEASE
 PROVIDE A DETAIL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-07-15 Cont ID  
Sent By pkrauss Date 2004-07-15 Time 08:25 Rev Time 0.55
Received By pkrauss Date 2004-07-15 Time 07:59 Sent To  
Notes
2004-07-15 00:00:00DENIED:
 PROVIDE SIGNATURE NOT INITIALS ON PLANS
 FOR COMPLIANCE WITH FS 471.025 & FAC
 61G15-23.002.PLAN ARE OTHERWISE CODE
 COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 9 Status F Date 2005-10-15 Cont ID  
Sent By pschmitz Date 2005-10-15 Time 07:28 Rev Time 0.00
Received By pschmitz Date 2005-10-15 Time 06:11 Sent To  
Notes
2005-10-15 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY PLAN REVIEW
 DENIED
 1)PREVIOUS NOTE:
 SHT A0-00 DRINK FOUNTAIN NOTE.
  
 *****NEW COMMENT*****
 SHT AO-00 INDICATES THAT A WATER COOLER
 AND CUPS ARE PROVIDED IN THE LAUNDRY
 ROOM. PLEASE SHOW LOCATION OF WATER
 COOLER ON THE PLANS. SECTION 104.2.1
 A SINK IS NOT ACCEPTABLE EXCHANGE FOR A
 DRINKING FOUNTAIN, OR WATER COOLER.
 END OF COMMENTS, QUESTION 561-805-6692

Review Stop P PLUMBING
Rev No 8 Status P Date 2005-09-10 Cont ID  
Sent By kstevens Date 2005-09-10 Time 08:28 Rev Time 0.50
Received By kstevens Date 2005-09-10 Time 08:28 Sent To  
Notes
2005-09-10 00:00:00REVISION OR - ADDED ONE LAV IN EACH
 TOILET ROOM

Review Stop P PLUMBING
Rev No 7 Status P Date 2005-05-24 Cont ID  
Sent By kstevens Date 2005-05-24 Time 08:14 Rev Time 0.50
Received By kstevens Date 2005-05-24 Time 08:14 Sent To  
Notes
2005-05-24 00:00:00PASSED/PROVISO
  
  
 REV REQD FOR SUPPORTS FOR CONDENSATE ON
 ROOF SHOWING 4' ON CENTER SUPPORTS. -
 CONTRACTOR SAID HE WILL SUBMIT WHEN
 ARCHITECT IN TOWN.

Review Stop P PLUMBING
Rev No 6 Status F Date 2005-04-23 Cont ID  
Sent By kstevens Date 2005-04-23 Time 17:53 Rev Time 0.50
Received By kstevens Date 2005-04-23 Time 17:53 Sent To  
Notes
2005-04-23 00:00:00REVISION DENIED
  
 FROM PREVIOUS REVIEW:
 5) CONDENSATE PIPING SUPPORTS ON SHEET
 A4.0 SHOWN AS EVERY 10 FEET. TABLE 408.5
 INDICATES THAT PVC WILL BE SUPPORTED
 EVERY 4 FEET. - ALSO INDICATE THAT PVC
 SHALL BE PROTECTED FROM U.V. RAYS PER
 MANUF. INSTRUCTIONS. SECTION 104.2.1.
 6) LETTERS FROM ARCHITECT AND ENGINEER
 SHALL BE SIGNED/SEALED/DATED/NOTOIZED
 AND HAVE TITLE BLOCK INFORMATION
 REQUIRED BY FLORIDA ADMINISTRATIVE CODE
 AND FLORIDA STATUTES.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status F Date 2005-03-17 Cont ID  
Sent By kstevens Date 2005-03-17 Time 11:36 Rev Time 3.25
Received By kstevens Date 2005-03-17 Time 11:36 Sent To  
Notes
2005-03-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FBC-2001 BUILDING
  
 1) SUBMIT A DETAIL FOR ACCESSIBLE BATH-
 ROOMS PER SECTIONS 11-4.16, 11-4.19, 11-
 4.21, 11-4.22 AND ALL SUBSECTIONS.
 2) SHT A3.2 THE SANITARY RISER DIAGRAM
 DOES NOTMEET CODE REQUIREMENTS. THE
 SERVICE SINK SHALL DISCHARGE DOWNSTREAM
 OF THE BATHROOM FIXTRUES. SECTION 909.1
 3) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2.
 4) A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1. SUBMIT DETAIL SHOWING
 COMPLIANCE WITH 11-4.15 AND ALL
 SUBSECTIONS.
 5) SUBMIT DETAIL FOR CONDENSATE PIPING.
 SHOW PIPE SIZE, MATERIAL, SUPPORT DETAIL
 & TERMINATION POINT. SECTION 104.3.1.1.
 6) PLANS NOT HAVE A NEW ARCHITECT OF
 RECORD, AND PLANS PREVIOUSLY SUBMITTED
 FOR PLUMBING WERE SIGNED/SEALED/DATED BY
 AN ENGINEER. PLEASE SUBMIT A
 SIGNED/SEALED/DATED NOTORIZED LETTER FOR
 CHANGING ARCHITECTS AND REMOVING THE
 ENGINEER OF RECORD FROM THIS JOB. PLEASE
 SUBMIT TWO COMPLETE SETS OF PLANS FOR
 REVIEW AND FOR PUBLIC RECORD.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-12-13 Cont ID  
Sent By kstevens Date 2004-12-13 Time 18:55 Rev Time 0.50
Received By kstevens Date 2004-12-13 Time 18:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-11-08 Cont ID  
Sent By kstevens Date 2004-11-08 Time 10:42 Rev Time 0.66
Received By kstevens Date 2004-11-08 Time 10:42 Sent To  
Notes
2004-11-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A) FROM PREVIOUS REVIEW:
 1) FAC 61G1-16.00E THE SIGNATURE AND
 DATE ARE REQUIRED ON THE PERSONAL SEAL
 OF THE ARCHITECT. - NO DATE SHOWN. FS
 481.2055
 2) FAC 61G1-16.004(2) THE FIRM LICENSE
 (CERTIFICATE OF AUTHORIZATION) NUMBER IS
 REQUIRED IN THE TITLE BLOCK OF EACH
 SHEET. FS 481.219
 *****NEW COMMENT*****
 SHT AO-00 INDICATES THAT A WATER COOLER
 AND CUPS ARE PROVIDED IN THE LAUNDRY
 ROOM. PLEASE SHOW LOCATION OF WATER
 COOLER ON THE PLANS. SECTION 104.2.1
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-10-09 Cont ID  
Sent By kstevens Date 2004-10-09 Time 05:28 Rev Time 1.50
Received By kstevens Date 2004-10-08 Time 19:02 Sent To  
Notes
2004-10-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FBC-2001 CHAPTER 1
  
 1) FAC 61G1-16.003 THE SIGNATURE AND
 DATE ARE REQUIRED ON THE PERSONAL SEAL
 OF THE ARCHITECT. - NO DATE SHOWN. FS
 481.2055
 2) FAC 61G1-16.004(2) THE FIRM LICENSE
 (CERTIFICATE OF AUTHORIZATION) NUMBER IS
 REQUIRED IN THE TITLE BLOCK OF EACH
 SHEET. FS 481.219
 3) ARE BOTH FLOORS A SINGLE OCCUPANCY OF
 ONE TENANT? IF NOT A DRINKING FOUNTAIN
 OR BOTTLED WATER COOLER SHALL BE REQUIR-
 ED IN EACH SPACE. TABLE 403.1
 4) REMOVE ALL VOIDED SHEETS AND SUBMIT
 TWO COMPLETE SETS OF PLANS FOR REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-07-14 Cont ID  
Sent By kstevens Date 2004-07-14 Time 10:46 Rev Time 2.50
Received By kstevens Date 2004-07-10 Time 17:25 Sent To  
Notes
2004-07-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FBC-2001 BUILDING
  
 1) SUBMIT CALCULATIONS FOR MINIMUM FAC-
 ILITIES FOR FIXTURES PER TABLES 1103.1
 (BLDG.) AND 403.1 (PLUMB.) SHOW SQUARE
 FOOTAGE FOR EACH OCCUPANCY, BUSINESS,
 INDUSTRIAL, & STORAGE.
 2) INDICATE TYPE AND AMOUNT OF MATERIALS
 TO BE STORED. RESPONSE MAY CREATE NEW
 COMMENTS. SECTION 104.2.1
 3) WHAT TYPE OF BUSINESS/WORK WILL BE
 DONE IN THIS SPACE?
 4) PRIVATE BATHROOM SHALL BE ADAPTABLE.
 SUBMIT A DETAIL SHOWING BACKING FOR W/C
 GRAB BARS, SIZE OF OPENING FOR W/C, THE
 BACKING FOR GRAB BARS FOR THE SHOWER,
 CONTROL AREA FOR SHOWER, HEIGHT OF SEAT
 AND BACKING FOR SEAT, & CURB HEIGHT.
 SECTION 11-4.1.3(11).- ALSO INDICATE
 TURNING AREA IN ADAPTABLE BATHROOM.
 5) SUBMIT A DETAIL FOR ACCESSIBLE BATH-
 ROOMS PER SECTIONS 11-4.16, 11-4.19, 11-
 4.21 AND ALL SUBSECTIONS.
 6) DOORS REQUIRED TO BE ACCESSIBLE SHALL
 COMPLY WITH THE REQUIREMENTS OF 11-4.13.
 AND 11-4.13.5. THE CLEAR WIDTH OF 32"
 CAN NOT BE ACHIEVED WITH A 2'8" DOOR.
 7) LUNCH ROOM SINK SHALL BE ACCESSIBLE
 PER SECTION 11-4.24. SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH THIS SECTION AND
 ALL SUBSECTIONS.
 8) SHT PO-01 WATER RISER DIAGRAM & NOTES
 AIR CHAMBERS ARE NOT APPROVED. DELETE
 FROM RISER AND NOTES. WATER HAMMER ARR-
 ESTORS REQUIRED BY SECTION 604.9, (AT
 ICE MAKERS, WASH MACHINES, & DISHWASHERS
 SHALL BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE PER PDI-WH 201 AND
 MANUF. - RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN. THERE ARE FIXTURES NOT
 SHOWN ON FLOOR PLAN, (TUB & LAV).
 9) SHT P0-01 THE SANITARY RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN, NOT
 DOES IT MEET CODE REQUIREMENTS. W/C'S
 (A) W/C'S SHALL NOT BE DOUBLE TRAPPED.
 SECTION 1002.1. W/C'S HAVE AN INTEGRAL
 TRAP. SEE EXCEPTION (1).
 (B) SANITARY CROSS FITTINGS ARE NOT
 APPROVED FOR UNDERGROUND USE. SECTION
 706.3.
 (C) HORIZONTAL DRY VENTS ARE NOT APPRO-
 VED PER SECTION 905.3
 (D) TEE FITTINGS ARE NOT APPROVED FOR
 USE AS SHOWN AT THE TOP OF RISER WITH
 DRAINAGE FROM BOTH DIRECTIONS. TABLE
 706.3.
 (E) NO BATH TUB IN ROOM 206 SHOWN ON
 THE FLOOR PLAN. SECTION 104.2.1
 (F) 2 LAVS SHOWN ON RISER, BUT ONLY ONE
 SHOWN ON FLOOR PLAN. SECTION 104.2.1.
 (G) WASH MACHINE REQUIRES A TRAP AND A
 STANDPIPE. SECTIONS 1002.1, & 802.4.
 (H) DISHWASHERS REQUIRE AN AIR GAP FIT-
 TING ABOVE THE FLOOR RIM LEVEL OF THE
 SINK.
 (I) WHAT IS THE FIXTURE BETWEEN THE
 DISHWASHER AND THE SINK IN THE LUNCHROOM
 WHAT IS THE USAGE OF THIS FIXTURE. SECT-
 ION 104.2.1.
 (J) THE RISER DIAGRAM SHALL REFLECT THE
 LAYOUT OF THE FIXTURES ON THE FLOOR PLAN
 AND THE ACTUAL INSTALLATION OF THE PIP-
 ING. SEE RED LINE CORRECTIONS AND EXAMP-
 LE.
 10) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2
 11) THERMAL EXPANSION CONTROL IS REQUIR-
 ED PER SECTION 607.3.2
 12) A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AND AFFIX HIS SEAL TO ALL PLANS
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2005-05-05 Cont ID  
Sent By shill Date 2005-05-05 Time 09:58 Rev Time 0.00
Received By shill Date 2005-05-05 Time 09:58 Sent To PC
Notes
2005-05-05 00:00:00OK PER AA (RE: DMP REVIEW)


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved