Plan Review Details - Permit 04061155
Plan Review Stops For Permit 04061155
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-24 Cont ID  
Sent By csiegber Date 2004-06-24 Time 11:44 Rev Time 0.00
Received By csiegber Date 2004-06-24 Time 11:44 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-06-29 Cont ID  
Sent By csiegber Date 2004-06-24 Time 11:44 Rev Time 0.35
Received By pkrauss Date 2004-06-29 Time 07:46 Sent To  
Notes
2004-06-29 00:00:00PROVISO:
 RETURN AIR REQUIRED FROM THE 2ND FLOOR
 LIBRARY AREA.RETURN AIR ALSO REQUIRED
 FROM ALL ROOMS ON THE 1ST FLOOR THAT ARE
 SEPARATED BY A DOOR FROM THE RETURN AIR
 PLENUM. REVISED 2001 FBC(M) 601.4.
  
 AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 DUCTWORK UNDER THE HOUSE SHALL NOT BE
 IN OR WITHIN 6" OF THE GROUND.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.