Plan Review Details - Permit 04061070
Plan Review Stops For Permit 04061070
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-08-02 Cont ID  
Sent By lsmith Date 2004-08-02 Time 10:33 Rev Time 0.75
Received By lsmith Date 2004-08-02 Time 10:33 Sent To E
Notes
2004-08-02 00:00:00BUIDING PLAN REVIEW: PROVISO
  
 1. SUBMIT THE FLORIDA PRODUCT APPROVAL
 FOR THE EXTERIOR DOOR #10 SHOWN ON
 PLANS BEFORE INSTALLATION.
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANSEXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-07-19 Cont ID  
Sent By pkrauss Date 2004-08-02 Time 09:27 Rev Time 0.50
Received By lsmith Date 2004-07-19 Time 11:19 Sent To  
Notes
2004-07-19 00:00:00BUILDING PLAN REVIEW: FAILED
  
  
  
 SEE NOTES FROM FIRST REVIEW NOT ANSWERED
 NEED FLORIDA PRODUCT APPROVALS FOR STORE
 FRONT SYSTEM.
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-08 Cont ID  
Sent By lsmith Date 2004-07-08 Time 08:39 Rev Time 0.75
Received By lsmith Date 2004-07-08 Time 08:39 Sent To  
Notes
2004-07-08 00:00:001.PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2. NEED SEPARATE PERMIT FOR MOVING
 RETURN AIR HANDLER.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-08-02 Cont ID  
Sent By dpalmer Date 2004-08-02 Time 16:35 Rev Time 0.50
Received By dpalmer Date 2004-08-02 Time 16:34 Sent To  
Notes
2004-08-02 00:00:00**** NOTES REDLINED **
  
 MISSING EQUIPMENT GRNDS. 250.122,250.110
  
 CORRELATE PANELS NEW AND EXSITING,
  
 REDLINE ABOVE, DOES NOT NEED TO REVISE
 PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-07-15 Cont ID  
Sent By lsmith Date 2004-08-02 Time 10:38 Rev Time 0.75
Received By dpalmer Date 2004-07-15 Time 15:56 Sent To  
Notes
2004-07-15 00:00:00************** UNSAT **************
  
 PLEASE SEE SOME NOTES FROM FIRST REVIEW
 HAVE NOT YET BEEN ADDRESSED.
  
 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULE.
  
 2)NOTE: PLEASE LIST/SHOW/INDICATE SIGN
 CIRCUIT AS REQUIRED PER 600.5
  
 3 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE SUBMIT LOAD CALCS FOR EXISTING
 SERVICE. PLEASE SEE WHAT WAS SUBMITTED
 FOR REFERENCE TO PREVIOUS PERMITS DOES
 NOT INDICATE LOAD CALCS.
  
 4)NOTE; PLEASE SEE RISER, STILL DOES NOT
 INDICATE ANY CONDUIT TO NEW SUB-PANELS,
 FEEDERS, EQUIPMENT GRNDS ETC.
 215.5,310.16,250.24,250.110,250.122 ETC
  
 5)NOTE: PLEASE SEE LETTER FROM FPL FOR
 AVAILABLE FAULT CURRENT IS NOW ATTACHED
 BUT THERE IS NO INDICATION FOR RATING
 OF MAINS. 110.9
  
 6)NOTE: PLEASE SEE SUB PANELS ARE NOTED
 ON PLANS AS BEING 125A AND 150A?
 PLEASE VERIFY AND CORRELATE.
  
 7)NOTE: PLEASE SEE TITLE BLOCK IS REQ'D
 TO HAVE THE PRINTED LICENSE # OF
 ENGINEER. FAC 61G15-23.002. FS 471.025
  
 PLEASE SEE ATTACHED COPY OF FS 553.80(2)
 (B) WITH RESPECT TO DESIGN PROFESSIONAL,
 THIS IS GIVEN AS A NOTICE FOR PLANS
 FAILED FOR THE SECOND REVIEW WHICH HAVE
 ONE OR MORE OF THE SAME CODE COMMETS.
 THIS IS A NOTICE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-22 Cont ID  
Sent By dpalmer Date 2004-06-22 Time 17:42 Rev Time 0.50
Received By dpalmer Date 2004-06-22 Time 17:42 Sent To  
Notes
2004-06-22 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SHOW ALL MIN CIRCUITING
 ON PLANS AND CORRELATE W/ PANEL SCHEDULE
 -S TO BE SUBMITTED.
 PLEASE ALSO SEE 700.12E FOR EM/EXT LTS.
 PLEASE PROVIDE ALL CIRCUITING TO
 SEPARATE TENANT SPACES.
  
 2)NOTE: PLEASE SEE PLANS AND PERMIT
 APPLICATION INDICATE TWO NEW SUB PANELS
 BEING INSTALLED , YET NO INFORMATION IS
 PROVIDED ON A RISER DIAGRAM ETC?
 ADDTIONAL SERVICES ARE NOT PERMITTED,
 MUST COME FROM EXSITING SERVICE.
 MAY HAVE ADDTIONAL METERS.
  
 3 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE PROVIDE LOAD CALCS FOR EXSITING
 SERVICE.
  
 4)NOTE: PLEASE INDICATE REQUIRED CIRCUIT
 PER 600.5
  
 5)NOTE: PLEASE PROVIDE USEAGE AND OR
 NEW/ EXSITING SHOW WINDOW RECEPTS REQ'D
 PER 210.62.
  
 6)NOTE: PLEASE VERIFY A/C SYSTEMS AND
 WHICH SYSTEM IS FEEDING WHICH AREA.
 PLANS ONLY SHOW ONE AHU?
 PLEASE SHOW ALL, AND DISC'S PER 440.11
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-07-14 Cont ID  
Sent By mcarsill Date 2004-07-14 Time 15:14 Rev Time 0.00
Received By mcarsill Date 2004-07-14 Time 15:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-06-24 Cont ID  
Sent By mcarsill Date 2004-06-24 Time 09:16 Rev Time 0.00
Received By mcarsill Date 2004-06-24 Time 09:16 Sent To  
Notes
2004-06-24 00:00:001) PLANS DISPLAY A PROPOSED STORAGE
 AREA UNDERNEATH EXIT STAIRS WITH NO
 FIRE RATING. PLEASE REVIEW NFPA 101,
 THE LIFE SAFETY CODE, SECTION 7.2.2.5.3,
 2000 EDITION.
  
 2) NO EMERGENCY LIGHTING SHOWN IN
 ONE OF THE SECOND FLOOR TENANT
 SPACES.
  
 3) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENT FOR NEW ALUMINUM RAILING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-02 Cont ID  
Sent By pkrauss Date 2004-08-02 Time 09:14 Rev Time 0.00
Received By pkrauss Date 2004-08-02 Time 09:13 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-12 Cont ID  
Sent By csiegber Date 2004-07-12 Time 16:45 Rev Time 0.00
Received By csiegber Date 2004-07-12 Time 16:45 Sent To  
Notes
2004-07-12 00:00:00TO COMM BD#52

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-22 Cont ID  
Sent By mjacobs Date 2004-06-22 Time 16:11 Rev Time 0.00
Received By mjacobs Date 2004-06-22 Time 16:11 Sent To  
Notes
2004-06-22 00:00:00TO COMM BD INTERIOR PARTITION

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-08-02 Cont ID  
Sent By pkrauss Date 2004-08-02 Time 09:26 Rev Time 0.35
Received By pkrauss Date 2004-08-02 Time 09:13 Sent To B
Notes
2004-08-02 00:00:00RELOCATING AH-2 TO NEW SPACE.OUTSIDE
 AIR IS EXISTING AND WILL NOT CHANGE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2004-07-16 Cont ID  
Sent By pkrauss Date 2004-07-16 Time 10:43 Rev Time 0.20
Received By pkrauss Date 2004-07-16 Time 10:43 Sent To  
Notes
2004-07-16 00:00:00PLAN SHEET 3 OF 4 INDICATES NO
 MECHANICAL WORK.ALL SPACES ARE
 OCCUPIED WITH NO CHANGES TO THE
 EXISTING O.A. OR HVAC SYTEM.
 NO MECHANICAL CONTRACTOR INDICATED ON
 PERMIT APPLICATION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-07-06 Cont ID  
Sent By pkrauss Date 2004-07-06 Time 10:36 Rev Time 0.40
Received By pkrauss Date 2004-07-06 Time 10:17 Sent To  
Notes
2004-07-06 00:00:00DENIED:
 PERMIT APPLICATION INDICATES INTERIOR
 PARTITION & 2 ELEC SUB-PANELS.PLEASE
 CLARIFY.IS THIS AN INTERIOR BUILD
 OUT?IS THIS SPACEOCCUPIED?
  
 1. INDICATE EQUIPMENT SCHEDULE. NEW OR
 EXISTING.
  
 2. PROVIDE DUCT & GRILLE SIZE, MATERIAL,
 AND LAYOUT FOR ALL NEW DUCTWORK.
 INDICATE EXISTING DUCTWORK.
  
 3. PROVIDE OUTSIDE AIR CALCULATIONS PER
 2001 FBC(M) 403.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-07-10 Cont ID  
Sent By kstevens Date 2004-07-10 Time 06:23 Rev Time 0.25
Received By kstevens Date 2004-07-10 Time 06:23 Sent To  
Notes
2004-07-10 00:00:00NO PLUMBING PLANS/WORK SUBMITTED