Plan Review Details - Permit 04061031
Plan Review Stops For Permit 04061031
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-08-02 Cont ID  
Sent By kstevens Date 2004-08-02 Time 13:00 Rev Time 0.50
Received By lsmith Date 2004-08-02 Time 12:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-07-08 Cont ID  
Sent By dpalmer Date 2004-08-02 Time 11:50 Rev Time 0.50
Received By lsmith Date 2004-07-08 Time 07:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-08-02 Cont ID  
Sent By dpalmer Date 2004-08-02 Time 11:50 Rev Time 0.25
Received By dpalmer Date 2004-08-02 Time 11:49 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-06-25 Cont ID  
Sent By csiegber Date 2004-06-24 Time 08:56 Rev Time 0.25
Received By dpalmer Date 2004-06-25 Time 12:46 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-14 Cont ID  
Sent By csiegber Date 2004-07-14 Time 15:27 Rev Time 0.00
Received By csiegber Date 2004-07-14 Time 15:27 Sent To P
Notes
2004-07-14 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-24 Cont ID  
Sent By csiegber Date 2004-06-24 Time 08:56 Rev Time 0.00
Received By csiegber Date 2004-06-24 Time 08:56 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-23 Cont ID  
Sent By mmclean Date 2004-06-23 Time 15:00 Rev Time 0.00
Received By csiegber Date 2004-06-23 Time 09:02 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-07-02 Cont ID  
Sent By kstevens Date 2004-07-31 Time 12:59 Rev Time 1.00
Received By kstevens Date 2004-07-31 Time 12:59 Sent To B
Notes
2004-08-02 00:00:00PASSED/PROVISO
  
 SUCTION LINE SHALL CONNECT AT THE CENTER
 OF THE DRAINS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-07-07 Cont ID  
Sent By csiegber Date 2004-07-14 Time 15:27 Rev Time 1.00
Received By kstevens Date 2004-07-07 Time 16:01 Sent To B
Notes
2004-07-07 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
  
 1) SPA LAYOUT SHALL REFLECT THE DRAIN
 DETAIL. DRAIN DETAIL SHOWS PIPING FOR
 MAIN DRAINS AND SPA DEAINS CONNECTING AT
 THE CENTER OF THE DRAINS, BUT THE SPA
 LAYOUT SHOWS THE PIPING OFFSET FROM THE
 CENTER OF THE DRAINS. THESE SUCTION IN-
 LETS SHALL BE PLUMBED SUCH THAT WATER IS
 DRAWN THROUGH THEM SIMULTANEOUSLY. SEC.
 424.2.6.6.4. PLEASE CORRELATE DETAIL
 WITH SPA LAYOUT. SECTION 104.2.1.
 2) WHITE OUT AND HAND WRITTEN DETAILS OR
 NOTES ARE NOT APPROVED ON SIGNED & SEAL-
 ED PLANS. SECTION 104.2.1.3.
 3) PLEASE CHANGE NOTE #2 TO READ ANSI-
 NSPI-5 (STANDARD FOR RESIDENTIAL SWIMM-
 ING POOLS). HAS BEEN ANSI-NSPI 4.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-06-23 Cont ID  
Sent By csiegber Date 2004-06-23 Time 09:02 Rev Time 0.00
Received By mmclean Date 2004-06-23 Time 15:00 Sent To I
Notes
***NONE***