Plan Review Details - Permit 04060959
Plan Review Stops For Permit 04060959
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-09-20 Cont ID  
Sent By rmcdouga Date 2005-09-20 Time 09:53 Rev Time 0.00
Received By rmcdouga Date 2005-09-20 Time 09:53 Sent To  
Notes
2005-09-20 00:00:00DENIED
  
 ENERGY CALCS. THAT WERE SUBMITTED FOR
 RESTAMP DO NOT CORRESPOND WITH THE ONES
 THAT WERE APPROVED WITH THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status N Date 2004-11-04 Cont ID  
Sent By rmcdouga Date 2004-11-04 Time 11:07 Rev Time 0.00
Received By rmcdouga Date 2004-11-04 Time 11:07 Sent To  
Notes
2004-11-04 00:00:00FORM BOARD SURVEYS THAT WERE SUBMITTED
 BY MISTAKE DO NOT REQUIRE A PLAN REVIEW
 AND HAVE BEEN RETURNED TO THE
 CONTRACTOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-09-15 Cont ID  
Sent By rmcdouga Date 2004-09-15 Time 11:09 Rev Time 0.00
Received By rmcdouga Date 2004-09-15 Time 11:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-08-04 Cont ID  
Sent By pkrauss Date 2004-09-14 Time 07:45 Rev Time 0.00
Received By rmcdouga Date 2004-08-04 Time 14:38 Sent To  
Notes
2004-08-04 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) NEW PLANS NEED TO BE RESTAMPED BY
 THE CITY HISTORIC PRESERVATION DEPT.
  
 3)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
 SUBMIT THE FLORIDA PRODUCT IDENTITY
 NUMBER FOR WINDOWS, DOORS, ROOFING, AND
 OTHER STRUCTURAL ITEMS LISTED IN RULE
 9B-72.
  
 4)THE PLANS SPECIFY ALL EXTERIOR GLAZING
 TO BE IMPACT RESISTANT. THE PRODUCT
 INFORMATION THAT WAS SUBMITTED IS FOR
 NON IMPACT RATED. PLEASE CORRECT.
  
 5) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS IN
 ADDITION TO THE STATE PRODUCT APPROVAL,
 IF GLAZING IS NOT IMPACT RESISTANT.
  
 6) SUBMIT STATE PRODUCT APPROVALS FOR
 THE FOLLOWING:
 - GLAZED DOUBLE AND SINGLE FRENCH DOORS
 (IMPACT RATED)
 - GLAZED DOUBLE OUTSWING DOORS WITH
 SIDELITES (IMPACT RATED)
 - SINGLE OUTSWING FIBERGLASS OR STEEL
 DOOR AT GARAGE (IMPACT RATED)
 - CASEMENT WINDOWS (IMPACT RATED)
 - STRUCTURAL MULLIONS (IMPACT RATED)
 - SINGLE OUTSWING ENTRY DOOR "PEC. WOOD"
 (IMPACT RATED)
  
 7) THE ENERGY CALCULATION FORMS SPECIFY
 A CEILING FAN CREDIT. THE PLANS DO NOT
 INDICATE ANY CEILING FANS IN THE FAMILY
 ROOM. THE FBC CHAPTER 13-607.1A.1
 REQUIRES 2 FANS (MINIMUM OF 48" EACH) IN
 THIS ROOM.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-08 Cont ID  
Sent By jleech Date 2004-07-01 Time 16:35 Rev Time 4.00
Received By rmcdouga Date 2004-07-08 Time 10:24 Sent To  
Notes
2004-07-08 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT TWO COPIES OF A RECENT SURVEY.
  
 4) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 5) PLANS DO NOT CLEARLY INDICATE THE
 PROTION OF THE STRUCTURE THAT IS EXIST-
 ING. PLEASE CLARIFY.
  
 6) THE FIRM LICENSE NUMBER IS NOT GIVEN
 IN THE TITLE BLOCK. SEE FAC 61G1-16.004.
  
 7) A SEPARATE PERMIT IS REQUIRED FOR THE
 SITE WALLS.
  
 8) THE FULL BATH ON THE FIRST FLOOR IS
 REQUIRED TO HAVE DOORS WITH 29" CLEAR
 OPENING PER FBC 11-4.22.2.
  
 9) FBC MECHANICAL CODE 304.6 REQUIRES
 HEAT PRODUCING APPLIANCES TO MAINTAIN
 CLEARANCES TO COMBUSTABLE CONSTRUCTION,
 INCLUDING SHUTTERS AND DRAPES. LOCATION
 OF WINDOW ABOVE COOKTOP IN KITCHEN.
  
 10) AT LEAST ONE WINDOW IN SECOND FLOOR
 BEDROOMS MUST COMPLY WITH EGRESS. SEE
 FBC 1005.4. THE (F) WINDOWS IN THE
 SCHEDULE ON SHEET 2 SHOULD BE MARKED
 EGRESS.
  
 11) SPECIFY FIREBLOCKING AT CONCEALED
 SPACES BETWEEN STAIR STRINGERS AT THE
 TOP AND BOTTOM OF RUNS AS REQUIRED BY
 FBC 2305.1.4.
  
 12) SPECIFY THE REQUIRED CLEARANCES OF
 EXISTING CHIMNEY FROM ROOF AND NEW
 CONSTRUCTION. SEE FBC 2804.2.4.
  
 13) SHOW COMPLIANCE WITH FBC 1503.4.4
 WHICH REQUIRES DOWNSPOUTS TO DISCHARGE
 AT LEAST 12" FROM SIDEWALLS OF THE
 STRUCTURE AND GUTTERS WITH DOWNSPOUTS ON
 BUILDINGS WITH EAVES OF LESS THAN 6"
 PROJECTIONS.
  
 14) THE POSITIVE AND NEGATIVE SIGNS ARE
 MISSING FROM THE INTERNAL PRESSURE
 COEFFICENT ON SHEET 5.
  
 15)TWO DIFFERENT SOIL BEARING CAPACITIES
 ARE GIVEN ON SHEET 5. PLEASE CORRECT.
  
 16) TWO DIFFERENT STRENGTHS OF CONCRETE
 ARE SPECIFIED ON SHEET5. THE FOOTING
 SCHEDULE HAS 2500 PSI AND THE FOUNDATION
 PLAN LISTS 3000 PSI CONCRETE. PLEASE
 CORRECT.
  
 17) SPECIFY HOW THE SECTION OF THE
 SECOND FLOOR BLOCK WALL AND CONC. COLUMN
 ABOVE THE EXISTING MASTER BEDROOM WILL
 BE SUPPORTED FROM BELOW.
  
 18) REVISE THE DIAGRAM OF THE HIP ROOF
 NAILING ZONES ON SHEET 7. THE OUTSIDE
 CORNERS OF HIP ROOFS ARE ALSO ZONE 3.
 SEE CITY OF WPB AMENDMENTS TO FBC TABLE
 2306.1.
  
 19)SPECIFY FIREBLOCKING ON WALL SECTIONS
 FBC 2305.1.4 REQUIRES CONCEALED SPACES
 OF STUD WALLS AND PARTITIONS INCLUDING
 FURRED SPACES TO BE FIREBLOCKED AT
 CEILING AND FLOOR LEVELS AND WHERE WALLS
 AND FLOORS OR TRUSSES MEET.
  
 20) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
 SUBMIT PRODUCT APPROVALS FOR EXTERIOR
 WINDOWS, DOORS, MULLIONS, OVERHEAD
 GARAGE DOORS, ETC.
  
 21) SUBMIT A KEY PLAN, INSTALLATION
 SCHEDULE AND PRODUCT APPROVAL FOR STORM
 PANELS (UNLESS IMPACT GLAZING IS USED).
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2006-09-30 Cont ID  
Sent By dpalmer Date 2006-09-30 Time 19:25 Rev Time 0.00
Received By dpalmer Date 2006-09-30 Time 19:06 Sent To PC
Notes
2006-09-30 00:00:00REV OK, STAMPED.

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2006-09-08 Cont ID  
Sent By dpalmer Date 2006-09-08 Time 11:07 Rev Time 0.00
Received By dpalmer Date 2006-09-08 Time 10:52 Sent To PC
Notes
2006-09-08 00:00:00**** UNSAT ***
  
 1) NOTE: PLEASE SEE THAT ELECTRICAL
 SERVICE SIZE HAS NOW BEEN INCREASED TO
 325A'S, PLEASE SHOW AND INDICATE THE
 SIZE OF THE METER CAN ON RISER.
 PLEASE ALSO CLARIFY THE SEC'S, IF THESE
 ARE BY FPL, PLEASE DO NOT INCLUDE ON
 RISER AND NOTE BY FPL. IF THESE ARE
 BEING INSTALLED BY THE EELECTRICAL
 CONTRACTOR TO AN FPL HAND HOLE, THEN
 SIZE SHALL BE DONE IN ACCORDNACE WITH
 NEC. 310.15B6.
 PREVIOUS SIZE WAS 3/0'S AND NOW GOING
 DOWN TO 2/0'S.
 PLEASE SEE LOADS SHOWN.
  
 2) NOTE: PLEASE SEE NOW THE GROUNDIGN
 ELECTRODE CONDUCTOR IS BEING DOWN SIZED
 TO #4, WHEN 250.66 REQUIRES A #2 MIN.
 PLEASE SEE THAT ALL PREVIOUS PLANS
 SHOWED A #2 AND A #2 WILL BE REQUIRED.
 310.15B6, 250.66
  
 3) NOTE: PLEASE SEE PREVIOUS PLANS WHICH
 WERE REDLINED FOR MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN HOUSE TO
 DETACHED BLDG. THIS IS STILL MISSING AND
 NOT BEING SHOWN.
 PLEASE SEE 250.122 AS THE SIZE OF THE
 FEED FROM THE MAIN IS NOW CHANGED,.
 PLEASE ALSO SEE MISSIGN GROUNDING
 ELECTRODE CONDUCTOR SIZE IS MISSIGN AT
 THE DETACHED BLDG. THIS WAS REDLINED ON
 ALL PREVIOUS PLANS, HOWEVER ALSO IS
 STILL NOT SHOWN. PLEASE SEE 250.66 FOR
 MIN SIZE REQUIRED.
  
 4) NOTE: PLEASE CORRLELATE ALL PLANS,
 RISER AND PANEL SCHEDULES AS PANEL "A"
 IS NOW BEING SHOWN AS 125A'S ONRISER.
 PLEASE SEE PLANS AND PANEL SCHEDULE DOES
 NOT SHOW THE SAME.
 215.5,408.4, 230.90 ETC
 FBC 106.1.2
 PLEASE SEE PLANS ALSO STILL INDICATE A
 METER/MAIN COMBO?
  
 ** PLEASE CORRELATE ALL EQUIPMENT ON
 SITE WITH PLANS AND BE SURE ALL IS CODE
 COMPLIANT.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-06-30 Cont ID  
Sent By dpalmer Date 2006-06-30 Time 19:20 Rev Time 0.00
Received By dpalmer Date 2006-06-30 Time 19:09 Sent To PC
Notes
2006-06-30 00:00:00**** REDLINED ****
  
  
 MISSING EQUIPMENT GROUNDING CONDUCTOR
 FROM MAIN DISCONNECT TO THE GARAGE
 PANEL.
 250.32,250.122
 MISSING THE SIZE OF THE GEC AT THE
 DETACHED GARAGE.250.66,250.32
 LABLED THE DISCONNECT AT MAIN HOUSE
 WHICH MENTIONS PANEL "A" WHEN IT SHOULD
 READ PANEL "B".
  
 THE ABOVE ITEMS ARE REDLINED ON PLANS
 AND SHOULD BE REVISED IF OTHER REVISIONS
 ARE MADE TO PLANS.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-06-18 Cont ID  
Sent By dpalmer Date 2006-06-18 Time 12:47 Rev Time 0.00
Received By dpalmer Date 2006-06-18 Time 12:47 Sent To PC
Notes
2006-06-18 00:00:00REV, REDLINED 250.66, 250.32 FOR
 GROUNDING ELECTRODE CONDUCTOR AT
 DETACHED GARAGE.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-06-12 Cont ID  
Sent By dpalmer Date 2006-06-12 Time 15:45 Rev Time 0.00
Received By dpalmer Date 2006-06-12 Time 15:16 Sent To PC
Notes
2006-06-12 00:00:00********* UNSAT ************
  
 1) NOTE: PLEASE SEE PLANS INDICATE TWO
 MAIN DISC'S AND A MCB PANEL "B".
 PLEASE SEE RISER DOES NOT CORRELATE WITH
 THIS.
 IF PANEL "B' IS LOCATED OUTSIDE AT
 METER, THEN AN ADDTIONAL MAIN DISCONNECT
 IS NOT REQUIRED, HOWEVER MAY BE
 INSTALLED.
 PLEASE SEE THE MAIN ON PLANS FOR PANEL
 "A" IS MISSING FROM RISER.
 PLEASE CORRELATE AND GROUP PER 230.72.
  
 2) NOTE: PLEASE SEE NOW THAT THE
 GROUNDING ELECTRODE SYSTEM IS REVISED, A
 #6 IS NOW BEING SHOWN TO FOOTER STEEL
 WHICH IS WAY TOO SMALL AND DOES NOT MEET
 250.66. PLEASE SEE MIN SIZE REQUIRED IS
 A #2 AS SHOWN ON THE REST OF THE
 GROUNDING ELECTRODE SYSTEM.
  
  
 3) NOTE: PLEASE SEE A SD IS REQUIRED AT
 FIRST FLR LEVEL IN THE IMMEDIATE
 VICINITY OF THE FLR LEADING TO THE FLR
 ABOVE. NFPA-72 8-1.4.6.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-05-16 Cont ID  
Sent By dpalmer Date 2006-05-16 Time 17:55 Rev Time 0.00
Received By dpalmer Date 2006-05-16 Time 17:45 Sent To PC
Notes
2006-05-16 00:00:00*********** UNSAT *********
  
 ** PLEASE SEE NOW PLANS ARE COMING IN
 REVISING RISER ETC FROM ORIGINAL AND
 PREVIOUS PLANS. PLEASE SEE NOTES BELOW.
  
 1) NOTE: PLEASE SEE MAINS ARE NOW NO
 LONGER GROUPED PER 230.72
 PLEASE SEE PANEL "A" IS SHOWN AS A MCB
 LOCATED AT GARAGE???
 PLEASE SEE ORIG PLANS SHOWED THE SERVICE
 AT THE GARAGE AND THE PANEL "B" WAS AT
 HOUSE??
  
 2) NOTE: PLEASE SEE CIRCUITS FEEDING
 GARAGE ARE NOW BEING SHOWN COMING FROM
 THE MAIN HOUSE PANEL?
 THIS IS NOT PERMIITED AS THE GARAGE
 CIRCUITS MUST COME FROM THE GARAGE
 PANEL.
 PLEASE ALSO SEE PANEL SCHEDULE FOR GAR,
 DOES NOT SEEM TO INDICATE THE ACURATE
 CIRCUITS NEED. (LT, GDO ETC).
 215.5, 225.31-225.39 ETC.
  
 3) NOTE: PLEASE SEE PANEL SCHEDULES
 SHALL BE ACCURATE. PANEL SCHEDULES MAY
 NOT JUST MENTION "GEN LTS AND RECEPTS".
 IE: MASTER BEDRM LTS, KTICHEN LTS, NW
 BEDRM RECEPTS ,,,, ETC.
 408.4, 215.5
  
 4) NOTE: PLEASE KNOW, IF PANEL "A" IS
 NOW AT THE GARAGE AND THE SERVICE IS AT
 THE MAIN HOUSE, PLEASE RELOCATE THE
 GROUNDING ELECTRODE SYSTEM FOR THE
 GARAGE BLDG PER 250.32. THIS SHOWN FOR
 PANEL "B"?, HOWEVER SHOULD BE SHOWN ON
 PANEL "A", AS PANEL "B" IS NOW LOCATED
 ON THE SAME STRUCTURE AS SERVICE.
  
 5) NOTE: PLEASE LABEL ALL SWITCHES
 ACCORDINGLY. IF A 3-WAY, SW, LABEL.
  
 6) NOTE: PLEASE SEE SD FOR FOYER SEEMS
 TO MISSING OR RATHER NOT LOCATED IN THE
 CORRECT VICINITY AS SHOWN ON PLANS.
 PLEASE SEE NFPA-72, 8-1.4.6.2 WHICH
 REQUIRES THE SD IN THE IMMEDIATE
 VICINITY LEADING TO THE FLOOR ABOVE. (
 FOYER, MAY REQUIRE SD TO BE WALL MOUNTED
 ID NO CEILING IS PRESENT. SD AS SHOWN ON
 PLANS, IS SHOWN IN ANOTHER ROOM.
  
 PLEASE SUBMIT TEH ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-07-26 Cont ID  
Sent By dpalmer Date 2004-07-26 Time 08:40 Rev Time 0.33
Received By dpalmer Date 2004-07-26 Time 08:27 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-25 Cont ID  
Sent By csiegber Date 2004-07-21 Time 10:15 Rev Time 0.50
Received By dpalmer Date 2004-06-25 Time 15:29 Sent To M
Notes
2004-06-25 00:00:00********* UNSAT ************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW MAIN DISC. IT IS NOTED FOR OTHER
 PANELS.
  
 2)NOTE: PLEASE SEE OCP FOR 4.5 KW
 COOKTOP, PLEASE VERIFY.
  
 3)NOTE: PLEASE SEE ARC FAULT PROTECTION
 NOTE SHOULD MEET 2002 NEC. 210.12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2004-06-21 Cont ID  
Sent By spalmer Date 2004-06-21 Time 11:05 Rev Time 0.25
Received By spalmer Date   Time   Sent To  
Notes
2004-06-21 00:00:00APPROVED EMILY STILLINGS 6/21/04

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-09-28 Cont ID  
Sent By adarroug Date 2006-09-28 Time 10:22 Rev Time 0.00
Received By adarroug Date 2006-09-28 Time 10:22 Sent To E
Notes
2006-09-28 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-08-26 Cont ID  
Sent By adarroug Date 2006-08-26 Time 16:03 Rev Time 0.00
Received By adarroug Date 2006-08-26 Time 16:03 Sent To E
Notes
2006-08-26 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-06-26 Cont ID  
Sent By adarroug Date 2006-06-26 Time 16:25 Rev Time 0.00
Received By adarroug Date 2006-06-26 Time 16:25 Sent To E
Notes
2006-06-26 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-06-16 Cont ID  
Sent By adarroug Date 2006-06-16 Time 15:18 Rev Time 0.00
Received By adarroug Date 2006-06-16 Time 15:18 Sent To E
Notes
2006-06-16 00:00:00TO "DPALMER' DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-06-09 Cont ID  
Sent By adarroug Date 2006-06-09 Time 10:48 Rev Time 0.00
Received By adarroug Date 2006-06-09 Time 10:48 Sent To E
Notes
2006-06-09 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-05-15 Cont ID  
Sent By adarroug Date 2006-05-15 Time 16:13 Rev Time 0.00
Received By adarroug Date 2006-05-15 Time 16:13 Sent To E
Notes
2006-05-15 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-08-30 Cont ID  
Sent By adarroug Date 2005-08-30 Time 11:17 Rev Time 0.00
Received By adarroug Date 2005-08-30 Time 11:17 Sent To M
Notes
2005-08-30 00:00:00TO "M" BOX/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-29 Cont ID  
Sent By adarroug Date 2005-06-29 Time 14:54 Rev Time 0.00
Received By adarroug Date 2005-06-29 Time 14:54 Sent To I
Notes
2005-06-29 00:00:00TO "PKRAUSS" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-11-04 Cont ID  
Sent By csiegber Date 2004-11-04 Time 10:13 Rev Time 0.00
Received By csiegber Date 2004-11-04 Time 10:12 Sent To B
Notes
2004-11-04 00:00:00TO RM DESK/SUBMITTAL
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-20 Cont ID  
Sent By csiegber Date 2004-08-20 Time 10:03 Rev Time 0.00
Received By csiegber Date 2004-08-20 Time 10:03 Sent To M
Notes
2004-08-20 00:00:00TO PK DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-21 Cont ID  
Sent By csiegber Date 2004-07-21 Time 10:15 Rev Time 0.00
Received By csiegber Date 2004-07-21 Time 10:15 Sent To E
Notes
2004-07-21 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-08 Cont ID  
Sent By mmclean Date 2004-07-08 Time 10:24 Rev Time 0.00
Received By rmcdouga Date 2004-06-22 Time 08:01 Sent To  
Notes
2004-06-24 00:00:006/22 TO Z
 6/24/04 TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2005-09-20 Cont ID  
Sent By pkrauss Date 2005-09-01 Time 09:42 Rev Time 0.40
Received By pkrauss Date 2005-09-01 Time 09:42 Sent To B
Notes
2005-09-01 00:00:00DENIED:
 ENERGY CALCS SUBMITTED FOR RE-STAMP -
 CALLED JIM PAYNE (ARCH) CALCS DO NOT
 REFLECT THOSE SUBMITTED & APPROVED WITH
 THE BUILDING PERMIT.
  
 NEW ENERGY CALCULCATIONS ARE
 INSUFFICIENT FOR THE SQUARE FOOTAGE
 INDICATED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2005-07-05 Cont ID  
Sent By pkrauss Date 2005-07-05 Time 10:03 Rev Time 0.35
Received By pkrauss Date 2005-07-05 Time 10:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-09-17 Cont ID  
Sent By pkrauss Date 2004-09-17 Time 12:51 Rev Time 0.10
Received By pkrauss Date 2004-09-17 Time 12:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2004-09-14 Cont ID  
Sent By pkrauss Date 2004-09-14 Time 07:20 Rev Time 0.30
Received By pkrauss Date 2004-09-14 Time 07:20 Sent To B
Notes
2004-09-14 00:00:00DENIED:3RD REQUEST
 PLEASE PROVIDE MANUAL J CALCULATIONS PER
 2001 FBC CHAPTER 13. PLANS ARE OTHERWISE
 CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-07-30 Cont ID  
Sent By csiegber Date 2004-08-20 Time 10:03 Rev Time 0.25
Received By hmoser Date 2004-07-30 Time 13:41 Sent To  
Notes
2004-07-30 00:00:00PLAN DENIED
 SAME AS LAST REVIEW
 NO MANUAL (J) OR ENERGY CALCULATIONS
 RETURN AIR'S ARE THE WRONG SIZE.
 PLAN REVIEW BY HAROLD MOSER

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-07-30 Cont ID  
Sent By jleech Date 2004-07-27 Time 16:32 Rev Time 0.40
Received By hmoser Date 2004-06-29 Time 11:30 Sent To P
Notes
2004-06-29 00:00:00DENIED:
 1.RETURN AIR JUMPERS ARE NOT SIZED
 PROPERLY.PER THE REVISED 2001 FBC(M)
 601.4 EXCEPTION #1, RETURN AIR TRANSFER
 DUCTS ARE TO BE SIZED 1 1/2 TIMES THE
 SUPPLY AIR TO THAT AREA.THE MASTER
 SUITE IS TO INCLUDE ALL SUUPLY AIR TO
 THE SUITE (BATHROOMS, CLOSET, DRESSING
 ROOM, ETC).PLEASE SEE THE ATTACHED
 SCHEDULE FOR PROPER SIZING OF THE RETURN
 AIR JUMPERS.
  
 2.PLEASE PROVIDE ENERGY AND MANUAL J
 CALCULATIONS PER 2001 FBC CHAPTER 13
 SUB-CHAPTER 6.
  
 3.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED, 2001 FBC(M) 307.2.3
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-07-27 Cont ID  
Sent By hmoser Date 2004-07-30 Time 13:39 Rev Time 0.33
Received By jleech Date 2004-07-27 Time 16:32 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-07-01 Cont ID  
Sent By dpalmer Date 2004-07-26 Time 08:40 Rev Time 0.75
Received By jleech Date 2004-07-01 Time 16:35 Sent To B
Notes
2004-07-01 00:00:00DENIED;
 1.NOTE 6. SHOULD READ, SHOCK ARRESTORS
 TO BE INSTALLED PER SEC. 604.9.
 2.RISER DIAGRAM AND FLOOR PLAN FLAT LINE
 DRAWING NOT TO CODE.
 A.2ND FL TUB BATH, TUB IS NOT VENTED
 B.L/T NOT SHOWN ON RISER DIAGRAM.
 C.1ST FLOOR MASTER BATH W/M MUST TIE
 IN DOWN STREAM OF THE BATHROOM
 GROUP. SEE SEC. 909.1.
 D.SIZE ALL PIPE ON FLAT DRAWING OR
 RISER DIAGRAM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2004-06-23 Cont ID  
Sent By mjacobs Date 2004-06-22 Time 08:02 Rev Time 0.00
Received By mmclean Date 2004-06-23 Time 12:02 Sent To I
Notes
2004-06-23 00:00:00MUST PULL A SEPARATE PERMIT FOR POOL &
 WALL.AN UTILITY EASEMENT APPROVAL
 SHOULD BE ATTACHED WITH 2 COPY OF SURVEY
 AND CAN ONLY BE 4FT IN THE FIRST 25FT
 FRONT SET BACK.POOL MUST BE 10FT ON
 THE SIDE.