Plan Review Details - Permit 04060866
Plan Review Stops For Permit 04060866
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2005-11-30 Cont ID  
Sent By shill Date 2005-11-30 Time 13:55 Rev Time 0.50
Received By shill Date 2005-11-30 Time 13:54 Sent To PC
Notes
2005-11-30 00:00:00REVISION - CHANGE WINDOWS

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-08-11 Cont ID  
Sent By shill Date 2005-08-11 Time 09:22 Rev Time 0.00
Received By shill Date 2005-08-11 Time 09:22 Sent To  
Notes
2005-08-11 00:00:00TRUSS ENGINEERING

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-05-18 Cont ID  
Sent By shill Date 2005-05-18 Time 16:32 Rev Time 0.50
Received By shill Date 2005-05-18 Time 16:32 Sent To PC
Notes
2005-05-18 00:00:00REVISED FF EL IN LAUNDRY ROOM

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-04-04 Cont ID  
Sent By shill Date 2005-04-04 Time 14:56 Rev Time 0.00
Received By shill Date 2005-04-04 Time 14:56 Sent To  
Notes
2005-04-04 00:00:00HOLLOW CORE ENGINEERING, SEE 04060866

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-01-20 Cont ID  
Sent By shill Date 2005-01-20 Time 11:40 Rev Time 0.00
Received By shill Date 2005-01-20 Time 11:40 Sent To PC
Notes
2005-01-20 00:00:00PROVISO - AT RISK PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-12-09 Cont ID  
Sent By shill Date 2004-12-09 Time 16:02 Rev Time 0.00
Received By shill Date 2004-12-09 Time 16:02 Sent To PC
Notes
2004-12-09 00:00:00SEE 04060897

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-23 Cont ID  
Sent By shill Date 2004-07-23 Time 18:48 Rev Time 1.00
Received By shill Date 2004-07-23 Time 18:48 Sent To  
Notes
2004-07-23 00:00:00SEE 04060887

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-10-27 Cont ID  
Sent By dpalmer Date 2004-10-27 Time 13:14 Rev Time 0.50
Received By dpalmer Date 2004-10-27 Time 13:14 Sent To  
Notes
2004-10-27 00:00:00ADDED 2002 NEC TO NOTES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-24 Cont ID  
Sent By dpalmer Date 2004-06-24 Time 16:30 Rev Time 0.25
Received By dpalmer Date 2004-06-24 Time 16:30 Sent To  
Notes
2004-06-24 00:00:00PLEASE SEE NOTES UNDER 04060861

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-01-06 Cont ID  
Sent By nmccray Date 2005-01-06 Time 16:11 Rev Time 0.00
Received By nmccray Date 2005-01-06 Time 16:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-11-23 Cont ID  
Sent By nmccray Date 2004-11-23 Time 14:05 Rev Time 0.00
Received By nmccray Date 2004-11-23 Time 14:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-06-23 Cont ID  
Sent By mcarsill Date 2004-06-23 Time 13:39 Rev Time 0.00
Received By mcarsill Date 2004-06-23 Time 13:39 Sent To  
Notes
2004-06-23 00:00:00PLEASE SEE PERMIT # 04060861 FOR
 COMMENTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-18 Cont ID  
Sent By adarroug Date 2005-05-18 Time 15:32 Rev Time 0.00
Received By adarroug Date 2005-05-18 Time 15:32 Sent To B
Notes
2005-05-18 00:00:00TO "SHILL" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-12-30 Cont ID  
Sent By mjacobs Date 2004-12-30 Time 10:34 Rev Time 0.00
Received By mjacobs Date 2004-12-30 Time 10:34 Sent To B
Notes
2004-12-30 00:00:00TO "SH" DESK/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-18 Cont ID  
Sent By csiegber Date 2004-10-18 Time 16:29 Rev Time 0.00
Received By csiegber Date 2004-10-18 Time 16:29 Sent To  
Notes
2004-10-18 00:00:00TO COMM BD#21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-23 Cont ID  
Sent By shill Date 2004-07-23 Time 18:48 Rev Time 0.00
Received By shill Date 2004-06-18 Time 10:24 Sent To  
Notes
2004-06-18 00:00:00TO COMM BD#24

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-10-20 Cont ID  
Sent By tgordon Date 2005-10-20 Time 08:32 Rev Time 0.30
Received By tgordon Date 2005-10-20 Time 08:32 Sent To  
Notes
2005-10-20 00:00:00MECH. REV. PLANS AND E. CAL.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-12-01 Cont ID  
Sent By pkrauss Date 2004-12-01 Time 17:06 Rev Time 0.10
Received By pkrauss Date 2004-12-01 Time 17:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-11-19 Cont ID  
Sent By pkrauss Date 2004-11-19 Time 10:15 Rev Time 0.40
Received By pkrauss Date 2004-11-19 Time 10:15 Sent To  
Notes
2004-11-19 00:00:00DENIED:BUILDING 6 UNIT 28
 MONACO END UNIT
 RETURN AIR FROM THE MASTER BEDROOM IS
 NOT SIZED IN ACCORDANCE WITH THE MINIMUM
 REQUIREMENT OF 2001 FBC(M)601.4
 EXCEPTION #1 AND 3.ALL SUPPLY AIR INTO
 THE MASTER SUITE IS TO BE INCLUDED FOR
 THE TOTAL SUPPLY AIR INTO THAT SPACE.
 RETURN AIR JUMPER IS TO BE 1 1/2 TIMES
 THE TOTAL SQAURE INCHES OF THE TOTAL
 SUPPLY.PLEASE REVISE.
  
 PLEASE NOTE, THE EXHAUST FAN SCHEDULE ON
 PLAN M-2 SHOWS EF-2 & EF-3 FOR THE
 KITCHEN AND GARAGE EXHAUST WHICH ARE NOT
 INDICATED ON THE PLAN.PLEASE CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-07-19 Cont ID  
Sent By pkrauss Date 2004-07-19 Time 10:41 Rev Time 0.40
Received By pkrauss Date 2004-07-19 Time 10:40 Sent To  
Notes
2004-07-19 00:00:00DENIED:"MONACO MODEL"
 1.PROVIDE OUTSIDE AIR CALCULATIONS PER
 2001 FBC(M) 402.2, 402.2.1 OR 403.3.
  
 2.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 3.PLANS ARE TO BE SIGNED AND DATED BY
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE HVAC SYSTEM IN ACCORDANCE WITH THE
 FLORIDA STATUTES AND THE FLORIDA
 ADMINISTRATIVE CODE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-11-12 Cont ID  
Sent By kstevens Date 2004-11-12 Time 16:47 Rev Time 0.25
Received By kstevens Date 2004-11-12 Time 16:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-07-17 Cont ID  
Sent By kstevens Date 2004-07-17 Time 15:15 Rev Time 0.25
Received By kstevens Date 2004-07-17 Time 15:15 Sent To  
Notes
2004-07-17 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-10-25 Cont ID  
Sent By eschneid Date 2004-10-25 Time 15:00 Rev Time 0.25
Received By eschneid Date 2004-10-25 Time 15:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-06-30 Cont ID  
Sent By mmclean Date 2004-06-30 Time 14:24 Rev Time 0.00
Received By mmclean Date 2004-06-30 Time 14:24 Sent To  
Notes
2004-06-30 00:00:00DENIED, NEED TO PROVIDE PLAT WITH 41
 LOTS WITH ENGINEERING PLANS (2 SETS).
 NEED TO PROVIDE LANDSCAPE PLANS. CALL
 ERIC SCHNEIDER, SENIOR PLANNER AT 659-
 8031 FOR ANY QUESTIONS.