Plan Review Details - Permit 04060859
Plan Review Stops For Permit 04060859
Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2005-11-30 Cont ID  
Sent By shill Date 2005-11-30 Time 09:58 Rev Time 0.50
Received By shill Date 2005-11-30 Time 09:58 Sent To PC
Notes
2005-11-30 00:00:00CHANGE WINDOWS TO IMPACT

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2005-09-07 Cont ID  
Sent By shill Date 2005-09-07 Time 16:54 Rev Time 0.50
Received By shill Date 2005-09-07 Time 16:22 Sent To PC
Notes
2005-09-07 00:00:00WINDOW REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2005-08-05 Cont ID  
Sent By shill Date 2005-08-05 Time 18:36 Rev Time 0.50
Received By shill Date 2005-08-05 Time 18:36 Sent To  
Notes
2005-08-05 00:00:00TRUSS ENGINEERING

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2005-07-19 Cont ID  
Sent By shill Date 2005-07-19 Time 19:32 Rev Time 0.00
Received By shill Date 2005-07-19 Time 19:32 Sent To PC
Notes
2005-07-19 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 STEEL SHOPS, CABANA
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)PLEASE SUBMIT UNDER THE CABANA
 PERMIT NUMBER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2005-07-08 Cont ID  
Sent By shill Date 2005-07-08 Time 15:49 Rev Time 1.00
Received By shill Date 2005-07-08 Time 15:49 Sent To  
Notes
2005-07-08 00:00:00STEEL SHOPS
  
 BLDGS 1 & 3, 2ND LIFT & 3RD FLOOR BEAMS
 BLDGS 1 & 3, 3RD LIFT & ROOF
  
 BLDGS 2 & 5, 2ND LIFT & 3RD FLOOR BEAMS
 BLDGS 2 & 5, 3RD LIFT & ROOF BEAMS
  
  
 BLDG 4, 2ND LIFT & 3RD FLOOR BEAMS
 BLDG 4, 3RD LIFT & ROOF BEAMS
  
 BLDG 6, 2ND LIFT & 3RD FLOOR BEAMS
 BLDG 6, 3RD LIFT & ROOF BEAMS
  
 BLDG 7, FOUNDATION
  
 BLDGS 7,8,9 1ST LIFT & 2ND FLOOR BEAMS
 BLDGS 7,8,9 2ND LIFT & 3RD FLOOR BEAMS
  
 BLDG 10, FTG AND COLUMNS
 BLDG 10, 1ST LIFT & 2ND FLOOR BEAMS
  
 BLDG 11, 1ST LIFT & 2ND FLOOR BEAMS
 BLDG 11, 2ND LIFT & 3RD FLOOR BEAMS
 BLDG 11, 3RD LIFT & ROOF BEAMS
  
 BLDG 12, 1ST LIFT & 2ND FLOOR BEAMS
 BLDG 12, 2ND LIFT & 3RD FLOOR BEAMS
 BLDG 12, 3RD LIFT & ROOF BEAMS

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2005-07-05 Cont ID  
Sent By shill Date 2005-07-05 Time 09:06 Rev Time 1.00
Received By shill Date 2005-07-05 Time 09:06 Sent To PC
Notes
2005-07-05 00:00:00****CORRECTIONS****
 TRUSS SUBMITTALS, BUILDINGS 1 - 12
 PREPARED BY MORRIS SHASHOUA, PE
  
 1.)THE DRAWINGS WERE NOT APPROVED BY
 EOR; HE HAS CHECKED THE BOX WHICH STATES
 "REVISE AND RESUBMIT".
  
 2.)DOCUMENTS PREPARED BY AND ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD ARE TO
 BE SIGNED, SEALED, DATED ORIGINALS
 FAC61G15-23.002.
  
 3.)BCLL IS TO COMPLY WITH FBC TABLE
 1605.1, MINIMUM OF 10# FOR ATTICS WITH
 NO STORAGE, 30# FOR ATTICS WITH STORAGE.
  
 4.)THE DESIGN CRITERIA ON THE TRUSS
 LAYOUT DRAWING AND THE TRUSS ENGINEERING
 IS NOT CONSISTENT WITH THE CRITERIA
 SPECIFIED BY EOR (SHEET S0.1).EITHER
 REVISE THE PLAN OR CHANGE THE TRUSS
 DESIGN CRITERIA.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-06-27 Cont ID  
Sent By shill Date 2005-06-27 Time 07:41 Rev Time 0.50
Received By shill Date 2005-06-27 Time 07:41 Sent To  
Notes
2005-06-27 00:00:00STEEL SHOPS, 2ND LIFT, 3RD FLOOR BEAMS
 BUILDINGS 1,2,3,5
  
 FORM BOARD SURVEY, BLDGS 7 - 12 AND
 GAZEBO
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-05-12 Cont ID  
Sent By shill Date 2005-05-12 Time 17:47 Rev Time 0.50
Received By shill Date 2005-05-12 Time 17:47 Sent To  
Notes
2005-05-12 00:00:00STEEL SHOPS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-03-29 Cont ID  
Sent By shill Date 2005-03-29 Time 15:29 Rev Time 2.00
Received By shill Date 2005-03-29 Time 15:27 Sent To PC
Notes
2005-03-29 00:00:00PRECAST SHOPS PREPARED BY BRAD CASH, PE
 ALL BUILDING ON ONE SUBMITTAL, FILED
 WITH 04060859

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-01-18 Cont ID  
Sent By shill Date 2005-01-18 Time 11:50 Rev Time 1.00
Received By shill Date 2005-01-12 Time 16:01 Sent To PC
Notes
2005-01-18 00:00:00PROVISO - AT RISK PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-12-06 Cont ID  
Sent By shill Date 2004-12-06 Time 11:32 Rev Time 2.00
Received By shill Date 2004-12-06 Time 11:32 Sent To PC
Notes
2004-12-06 00:00:00SEE 04060897

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-22 Cont ID  
Sent By shill Date 2004-07-22 Time 09:03 Rev Time 1.00
Received By shill Date 2004-07-22 Time 09:02 Sent To  
Notes
2004-07-22 00:00:00SEE 04060887

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-10-28 Cont ID  
Sent By dpalmer Date 2004-10-28 Time 07:02 Rev Time 0.33
Received By dpalmer Date 2004-10-28 Time 06:51 Sent To  
Notes
2004-10-28 00:00:00NOTED 2002 NEC

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-24 Cont ID  
Sent By dpalmer Date 2004-06-24 Time 15:03 Rev Time 0.75
Received By dpalmer Date 2004-06-24 Time 15:03 Sent To  
Notes
2004-06-24 00:00:00*************** UNSAT ************
 BLDG. #1
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE.
  
 2)NOTE: PLEASE SEE NFPA-72 FOR SD
 LOCATIONS. 3'FROM BATHS/KITCHENS, 5'
 FROM RA GRILLES, 3' SUPPLY, 20'
 FROM COOKING APPLIANCES W/ EXCEPTIONS.
 8-1.4.2
  
 3)NOTE: PLEASE SHOW DISC'S FOR A/C CU'S.
 440.11
  
 4)NOTE: PLEASE SEE MISPRINT FOR 210.12
 ARC FAULT IS UNDER 2002 NEC.
  
 5)NOTE: PLEASE SEE OCP FOR AHU IS SHOWN
 MUCH LARGER THAN OCP FOR CU, YET LOAD
 ON LOAD CALCS REFER TO CU LOAD?
 PLEASE CORRELATE WITH MECH PLANS FOR
 A HOUSE THIS SIZE.
  
 6)NOTE: PLEASE SEE FAC 61G15-23.002 AND
 FS 471.023. PLEASE INCLUDE ALL REQUIRED
 LICENSE #'S ON TITLE BLOCK.
 PLEASE SEE FIRM SHOWN ON TITLE BLOCK
 NOW IS SHOWN AS HAVING A "CLOSED"
 LICENSE WITH STATE DBPR.
 SEE ATTACHED PRINT OUT.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-06-21 Cont ID  
Sent By mamini Date 2004-06-21 Time 09:45 Rev Time 0.50
Received By mamini Date 2004-06-21 Time 09:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-01-06 Cont ID  
Sent By nmccray Date 2005-01-06 Time 13:38 Rev Time 0.00
Received By nmccray Date 2005-01-06 Time 13:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-06-23 Cont ID  
Sent By mcarsill Date 2004-06-23 Time 10:47 Rev Time 0.00
Received By mcarsill Date 2004-06-23 Time 10:47 Sent To  
Notes
2004-06-23 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 2) BUILDING ADDRESSES REQUIRED.
  
 3) PRESCRIPTIVE STRENGTH REQUIREMENTS
 SHALL BE SHOWN ON PLANS FOR ALL
 HANDRAILS AND GUARDRAILS.
  
 4) IS THE DOOR BETWEEN THE GARAGE AND
 THE LAUNDRY RATED. NO RATING SHOWN ON
 DOOR SCHEDULE.
  
 5) SMOKE DETECTORS SHALL BE PLACED
 A MINIMUM OF THREE FEET FROM AIR
 CONDITIONER DIFFUSERS.
  
 6) NO FIRE SPRINKLER PLANS PROVIDED
 WITH PLANS. PAGE A.1 INDICATES THAT
 THE BUILDING WILL BE FIRE SPRINKLER
 PROTECTED.
  
 7) NO INFORMATION PROVIDED REGARDING
 MONITORING OF THE FIRE SPRINKLER
 SYSTEM.
  
 8) SITE PLAN DOES NOT DISPLAY ANY
 FIRE HYDRANTS.
  
 9) NO MENTION OF ANY FIRE EXTINGUISHERS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-09-26 Cont ID  
Sent By adarroug Date 2005-09-26 Time 10:44 Rev Time 0.00
Received By adarroug Date 2005-09-26 Time 10:44 Sent To M
Notes
2005-09-26 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-09-07 Cont ID  
Sent By adarroug Date 2005-09-07 Time 14:14 Rev Time 0.00
Received By adarroug Date 2005-09-07 Time 14:14 Sent To B
Notes
2005-09-07 00:00:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-07-01 Cont ID  
Sent By adarroug Date 2005-07-01 Time 15:50 Rev Time 0.00
Received By adarroug Date 2005-07-01 Time 15:50 Sent To B
Notes
2005-07-01 00:00:00TO "SHILL" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-06-23 Cont ID  
Sent By adarroug Date 2005-06-23 Time 10:12 Rev Time 0.00
Received By adarroug Date 2005-06-23 Time 10:12 Sent To B
Notes
2005-06-23 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-05-05 Cont ID  
Sent By adarroug Date 2005-05-05 Time 08:54 Rev Time 0.00
Received By adarroug Date 2005-05-05 Time 08:54 Sent To B
Notes
2005-05-05 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-04-04 Cont ID  
Sent By adarroug Date 2005-04-04 Time 16:06 Rev Time 0.00
Received By adarroug Date 2005-04-04 Time 16:06 Sent To B
Notes
2005-04-04 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-03-29 Cont ID  
Sent By adarroug Date 2005-03-29 Time 09:59 Rev Time 0.00
Received By adarroug Date 2005-03-29 Time 09:59 Sent To B
Notes
2005-03-29 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-12-30 Cont ID  
Sent By mjacobs Date 2004-12-30 Time 12:59 Rev Time 0.00
Received By mjacobs Date 2004-12-30 Time 12:59 Sent To B
Notes
2004-12-30 00:00:00TO "SH" DESK/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-14 Cont ID  
Sent By csiegber Date 2004-10-14 Time 11:20 Rev Time 0.00
Received By csiegber Date 2004-10-14 Time 11:20 Sent To  
Notes
2004-10-14 00:00:00TO COMM BD#21/PLANS ON RACK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-22 Cont ID  
Sent By shill Date 2004-07-22 Time 09:03 Rev Time 0.00
Received By shill Date 2004-06-18 Time 11:15 Sent To  
Notes
2004-06-18 00:00:00TO COMM BD#24

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-10-18 Cont ID  
Sent By tgordon Date 2005-10-18 Time 10:30 Rev Time 0.30
Received By tgordon Date 2005-10-18 Time 10:30 Sent To  
Notes
2005-10-18 00:00:00MECH. REV. PLANS .

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-10-04 Cont ID  
Sent By tgordon Date 2005-10-04 Time 13:47 Rev Time 0.30
Received By tgordon Date 2005-10-04 Time 13:47 Sent To  
Notes
2005-10-04 00:00:00MECH. REV.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-11-24 Cont ID  
Sent By pkrauss Date 2004-11-24 Time 07:20 Rev Time 0.35
Received By pkrauss Date 2004-11-24 Time 07:07 Sent To  
Notes
2004-11-24 00:00:00BUILDING I UNIT 1/GENEVA END UNIT
 PLEASE NOTE, ON PLAN SHEET M-4 THE
 EXHAUST FAN SCHEDULE INDICATES EF-2 &
 EF-3 WHICH ARE NOT IDENTIFIED ON THE
 PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-07-20 Cont ID  
Sent By pkrauss Date 2004-07-20 Time 09:30 Rev Time 0.35
Received By pkrauss Date 2004-07-20 Time 09:30 Sent To  
Notes
2004-07-20 00:00:00DENIED:"GENEVA MODEL" END-UNIT
 1.PROVIDE OUTSIDE AIR CALCUALTIONS PER
 2001 FBC(M) 402.2, 402.2.1 OR 403.3.
  
 2.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 3.PLANS ARE TO BE SIGNED AND DATED BY
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE HVAC SYSTEM IN ACCORDANCE WITH THE
 FLORIDA STATUTES AND THE FLORIDA
 ADMINISTRATIVE CODE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-11-12 Cont ID  
Sent By kstevens Date 2004-11-12 Time 17:06 Rev Time 0.25
Received By kstevens Date 2004-11-12 Time 17:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-07-17 Cont ID  
Sent By kstevens Date 2004-07-17 Time 16:16 Rev Time 0.25
Received By kstevens Date 2004-07-17 Time 16:16 Sent To  
Notes
2004-07-17 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-10-25 Cont ID  
Sent By eschneid Date 2004-10-25 Time 14:47 Rev Time 0.25
Received By eschneid Date 2004-10-25 Time 14:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-06-30 Cont ID  
Sent By mmclean Date 2004-06-30 Time 13:36 Rev Time 0.00
Received By mmclean Date 2004-06-30 Time 13:36 Sent To  
Notes
2004-06-30 00:00:00DENIED, NEED TO PROVIDE PLAT WITH 41
 LOTS WITH ENGINEERING PLANS (2 SETS).
 NEED TO PROVIDE LANDSCAPE PLANS. CALL
 ERIC SCHNEIDER, SENIOR PLANNER AT 659-
 8031 FOR ANY QUESTIONS.