Plan Review Details - Permit 04060721
Plan Review Stops For Permit 04060721
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-10-06 Cont ID  
Sent By shill Date 2005-10-06 Time 08:44 Rev Time 0.00
Received By shill Date 2005-10-06 Time 08:44 Sent To  
Notes
2005-10-06 00:00:00WINDOW REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-04-04 Cont ID  
Sent By shill Date 2005-04-04 Time 14:41 Rev Time 0.00
Received By shill Date 2005-10-04 Time 13:44 Sent To  
Notes
2005-04-04 00:00:00HOLLOW CORE ENGINEERING, SEE 04060859

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-01-20 Cont ID  
Sent By shill Date 2005-01-20 Time 09:52 Rev Time 0.00
Received By shill Date 2005-01-20 Time 09:52 Sent To PC
Notes
2005-01-20 00:00:00PROVISO - AT RISK PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-12-06 Cont ID  
Sent By shill Date 2004-12-06 Time 07:23 Rev Time 1.00
Received By shill Date 2004-12-06 Time 07:23 Sent To PC
Notes
2004-12-06 00:00:00SEE 04060754

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-22 Cont ID  
Sent By shill Date 2004-07-22 Time \0:58 Rev Time 1.00
Received By shill Date 2004-07-22 Time 10:58 Sent To  
Notes
2004-07-22 00:00:00SEE 04060887

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-10-28 Cont ID  
Sent By dpalmer Date 2004-10-28 Time 06:14 Rev Time 0.25
Received By dpalmer Date 2004-10-28 Time 06:13 Sent To  
Notes
2004-10-28 00:00:00NOTED 2002 NEC

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-24 Cont ID  
Sent By dpalmer Date 2004-06-24 Time 13:02 Rev Time 0.50
Received By dpalmer Date 2004-06-24 Time 13:01 Sent To  
Notes
2004-06-24 00:00:00************ UNSAT **************
 BLDG # 4
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE.
  
 2)NOTE: PLEASE SEE NFPA-72 FOR SD
 LOCATIONS. 3' FROM BATHS/KITCHENS AND
 20' FROM COOKING APPLIANCES W/ EXCEPTION
 -S. 8-1.4.2
  
 3)NOTE: PLEASE INDICATE/SHOW AC, CU
 DISCONNECTS PER 440.11
  
 4)NOTE: PLEASE SEE E-8 FOR MISPRINT OF
 210.12 FOR ARC FAULT ART. 2002 NEC.
  
 5)NOTE: PLEASE SEE OCP SHOWN FOR AHU
 IS MUCH LARGER THAN OCP FOR CU, YET
 LOAD FOR CU IS SHOWN ON LOAD CALCS?
 PLEASE VERIFY AND CORRELATE WITH
 MECH PLANS.
  
 6)NOTE: PLEASE SEE FS 471.023, FAC
 61G15-23.002 FOR REQUIRED LICENSE #'S
 ON TITLE BLOCK.PLEASE SEE ATTACHED
 PRINT-OUT FROM DBPR WHICH INDICATES
 FIRM AS SHOWN ON TITLE BLOCK AS LICENSE
 BEING "CLOSED"?
 PLEASE NOTE, THIS # WAS NOT ON TITLE
 BLOCK.
 PLEASE ALSO SEE THE ABOVE IS REQUIRED
 OF ALL SHEETS AND TRADES WHEATHER OR
 NOT COMMENT IS MADE FROM OTHER REVIEWERS
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-01-06 Cont ID  
Sent By nmccray Date 2005-01-06 Time 10:56 Rev Time 0.00
Received By nmccray Date 2005-01-06 Time 10:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-11-23 Cont ID  
Sent By nmccray Date 2004-11-23 Time 16:06 Rev Time 0.00
Received By nmccray Date 2004-11-23 Time 16:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-06-24 Cont ID  
Sent By mcarsill Date 2004-06-24 Time 12:24 Rev Time 0.00
Received By mcarsill Date 2004-06-24 Time 12:24 Sent To  
Notes
2004-06-24 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 2) BUILDING ADDRESSES REQUIRED.
  
 3) PRESCRIPTIVE STRENGTH REQUIREMENTS
 SHALL BE SHOWN ON PLANS FOR ALL
 HANDRAILS AND GUARDRAILS.
  
 4) IS THE DOOR BETWEEN THE GARAGE AND
 THE STAIRS RATED. NO RATING SHOWN ON
 DOOR SCHEDULE.
  
 5) SMOKE DETECTORS SHALL BE PLACED A
 MINIMUM OF THREE FEET FROM AIR
 CONDITIONER DIFFUSERS.
  
 6) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS. PAGE A.1 INDICATES THAT
 THE BUILDING WILL BE FIRE SPRINKLER
 PROTECTED.
  
 7) NO INFORMATION PROVIDED REGARDING
 THE MONITORING OF THE FIRE SPRINKLER
 SYSTEM.
  
 8) SITE PLAN DOES NOT DISPLAY ANY
 FIRE HYDRANTS.
  
 9) NO MENTION OF ANY FIRE EXTINGUISHERS.
  
 COURTESY REVIEW PERFORMED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-12-30 Cont ID  
Sent By mjacobs Date 2004-12-30 Time 12:51 Rev Time 0.00
Received By mjacobs Date 2004-12-30 Time 12:51 Sent To B
Notes
2004-12-30 00:00:00TO "SH" DESK/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-14 Cont ID  
Sent By csiegber Date 2004-10-14 Time 11:50 Rev Time 0.00
Received By csiegber Date 2004-10-14 Time 11:50 Sent To  
Notes
2004-10-14 00:00:00TO COMM BD#21/PLANS ON RACK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-22 Cont ID  
Sent By shill Date 2004-07-22 Time 10:58 Rev Time 0.00
Received By shill Date 2004-06-18 Time 11:53 Sent To  
Notes
2004-06-18 00:00:00TO COMM BD#24

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-10-04 Cont ID  
Sent By tgordon Date 2005-10-04 Time 13:44 Rev Time 0.30
Received By tgordon Date 2005-10-04 Time 13:44 Sent To  
Notes
2005-10-04 00:00:00MECH. REV.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-11-17 Cont ID  
Sent By pkrauss Date 2004-11-17 Time 17:24 Rev Time 0.40
Received By pkrauss Date 2004-11-17 Time 17:04 Sent To  
Notes
2004-11-17 00:00:00BUILDING 4 UNIT 19 GENEVA-END UNIT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-07-20 Cont ID  
Sent By pkrauss Date 2004-07-20 Time 10:55 Rev Time 0.35
Received By pkrauss Date 2004-07-20 Time 10:55 Sent To  
Notes
2004-07-20 00:00:00DENIED:"GENEVA MODEL" END-UNIT
 1.PLEASE NOTE, PER 2001 FBC(M) 104.2.1
 EACH PERMIT APPLICATION REQUIRES 2
 COPIES OF PLANS AND SPECIFICATIONS.
 PLEASE PROVIDE ADDITIONAL COPIES.
  
 2.PROVIDE OUTSIDE AIR CALCULATIONS PER
 2001 FBC(M) 402.2, 402.2.1 OR 403.3.
  
 3.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 4.PLANS ARE TO BE SIGNED AND DATED BY
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE HVAC SYSTEM IN ACCORDANCE WITH THE
 FLORIDA STATUTES AND THE FLORIDA
 ADMINISTRATIVE CODE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-11-12 Cont ID  
Sent By kstevens Date 2004-11-12 Time 11:46 Rev Time 0.50
Received By kstevens Date 2004-11-12 Time 11:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-07-19 Cont ID  
Sent By kstevens Date 2004-07-19 Time 10:19 Rev Time 0.25
Received By kstevens Date 2004-07-19 Time 10:19 Sent To  
Notes
2004-07-19 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-10-25 Cont ID  
Sent By eschneid Date 2004-10-25 Time 13:56 Rev Time 0.25
Received By eschneid Date 2004-10-25 Time 13:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-06-30 Cont ID  
Sent By mmclean Date 2004-06-30 Time 10:29 Rev Time 0.00
Received By mmclean Date 2004-06-30 Time 10:46 Sent To  
Notes
2004-06-30 00:00:00DENIED, NEED TO PROVIDE PLAT WITH 41
 LOTS WITH ENGINEERING PLANS (2 SETS).
 NEED TO PROVIDE LANDSCAPE PLANS.CALL
 ERIC SCHNEIDER, SENIOR PLANNER AT 659-
 8031 FOR ANY QUESTIONS.