Plan Review Details - Permit 04060563
Plan Review Stops For Permit 04060563
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-07-26 Cont ID  
Sent By alange Date 2004-07-26 Time 09:19 Rev Time 0.50
Received By alange Date 2004-07-26 Time 09:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-01 Cont ID  
Sent By alange Date 2004-07-01 Time 14:30 Rev Time 1.66
Received By alange Date 2004-07-01 Time 14:29 Sent To  
Notes
2004-07-01 00:00:00DENIED
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2.PRINTED NAME OF THE ARCHITECT IS
 REQUIRED ON THE TITLE BLOCK OF ALL
 PAGES.FAC 61G1-16.004(6) & FS 481.2055
  
 3.DOOR #6 NEEDS 18" CLEAR AT THE
 LATCHED SIDE OF THE DOOR.SHOW ON PLANS
  
 4.SAFTEY GLAZING REQUIRED IN STORE
 FRONT WINDOWS PLEASE SHOW ON PLAN.
 FBC2405.2.1
  
 5.KITCHEN SINK SHALL COMPLY WITH
 FBC 11.4.24
  
 6.DOOR #9 NOT DRAWN TO SCALE OF 36"
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2005-02-23 Cont ID  
Sent By dpalmer Date 2005-02-23 Time 06:35 Rev Time 0.10
Received By dpalmer Date 2005-02-23 Time 06:35 Sent To  
Notes
2005-02-23 00:00:00REV TO FA SHEETS NOT APPLICABLE TO ELEC
 REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-07-23 Cont ID  
Sent By dpalmer Date 2004-07-23 Time 08:39 Rev Time 0.33
Received By dpalmer Date 2004-07-23 Time 08:39 Sent To  
Notes
2004-07-23 00:00:00REDLINED PLANS.
  
 EM/EXT LTS TO BE CIRCUITED PER 700.12E
 W/LOCAL LT BRANCH CIRCUIT.
 MAY NOT BE ON SEPARATE CIRCUIT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-07-01 Cont ID  
Sent By jleahy Date 2004-07-01 Time 15:00 Rev Time 1.30
Received By jleahy Date 2004-06-15 Time 13:54 Sent To  
Notes
2004-06-15 00:00:00LOAD CALCULATION TO ALSO BE DONE ON
 SERVICE.
  
 LOAD CALCULATIONS IS OK BUT WHEN THE
 NUMBER OF OUTLETS IS KNOWN THEN 180 VA
 EACH IS USED THEN 220.13
  
 RISER SHOWS EAST PANEL TO BE 100A FED
 BY 200A MAIN!
  
 AHU CLOSET ON WEST SIDE NEEDS LIGHT AND
 OUTLET.
  
 NEDD TO SHOW BRASNCH CIRCUIT NUMBERS ON
 THE PLANS FOR THE OUTLETS AND LIGHTS.
  
 PANEL SCHEDULES ARE IDENTICAL SPACES
 ARE OT!!!!!
  
 PAGE E-2 SHOW A SATELITE OUTLET OUTSIDE!
  
 ANY QUESTIONS CALL JAKE LEAHY 805-6740

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-07-28 Cont ID  
Sent By mcarsill Date 2004-07-28 Time 15:08 Rev Time 0.00
Received By mcarsill Date 2004-07-28 Time 15:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-06-16 Cont ID  
Sent By nmccray Date 2004-06-16 Time 13:17 Rev Time 0.00
Received By nmccray Date 2004-06-16 Time 13:17 Sent To  
Notes
2004-06-16 00:00:00*************DENIED*********************
 1) WHAT ARE THE WALLS AND CEILINGS
 INTERIOR FINISH CLASSIFICATION? CLASS "A
 "B" OR "C".
  
 2) IT APPEARS THAT ADDITIONAL EXIT SIGN
 AND EMERGENCY LIGHT ARE NEEDED FOR THE
 CORRIDOR LEADING FROM OFFICE #4 TO THE
 RECEPTION AREA.
  
 3) WILL THESE ALTERATIONS AFFECT FIRE
 SPRINKLER COVERAGE AND FIRE ALARM SYSTEM
  
 4) SEPARATE PLANS AND PERMIT APPLICATION
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEM REMODEL.
  
 NATE MCCRAY, CAPTAIN
 835-2910 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-03-03 Cont ID  
Sent By adarroug Date 2005-03-03 Time 15:32 Rev Time 0.00
Received By adarroug Date 2005-03-03 Time 15:32 Sent To E
Notes
2005-03-03 00:00:00TO DPALMER DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-02-18 Cont ID  
Sent By adarroug Date 2005-02-18 Time 16:47 Rev Time 0.00
Received By adarroug Date 2005-02-18 Time 16:47 Sent To  
Notes
2005-02-18 00:00:00TO "COMM" BD#5

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-17 Cont ID  
Sent By csiegber Date 2004-08-17 Time 15:57 Rev Time 0.00
Received By csiegber Date 2004-08-17 Time 15:57 Sent To P
Notes
2004-08-17 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-22 Cont ID  
Sent By csiegber Date 2004-07-22 Time 08:22 Rev Time 0.00
Received By csiegber Date 2004-07-22 Time 08:22 Sent To  
Notes
2004-07-22 00:00:00TO COMM BD#23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-07-01 Cont ID  
Sent By alange Date 2004-07-01 Time 14:43 Rev Time 0.00
Received By alange Date 2004-06-14 Time 14:28 Sent To  
Notes
2004-06-14 00:00:00TO COMM BD #16

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-07-31 Cont ID  
Sent By hmoser Date 2004-07-31 Time 10:57 Rev Time 0.75
Received By hmoser Date 2004-07-31 Time 10:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-07-31 Cont ID  
Sent By pkrauss Date 2004-06-30 Time 16:54 Rev Time 1.00
Received By hmoser Date 2004-06-30 Time 16:41 Sent To  
Notes
2004-07-01 00:00:00DENIED:
 1.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) 403.3.
  
 2.INDCIATE OUTSIDE AIR INTAKE, DUCT
 SIZE, MATERIAL & LAYOUT.
  
 3.DUCT SMOKE DETECTORS IN SYSTEMS THAT
 HAVE THE DESIGN CAPACITY GREATER THAN
 2,000 CFM.2001 FBCF(M) 606.2.1.
  
 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS PER NFPA 90A
 6.4.4.3.
  
 5.PLEASE INDICATE CONDENSATE
 TERMINATION SND LINE SIZE.
  
 6.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-08-23 Cont ID  
Sent By kstevens Date 2004-08-23 Time 13:36 Rev Time 0.60
Received By kstevens Date 2004-08-23 Time 13:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-07-31 Cont ID  
Sent By csiegber Date 2004-08-17 Time 15:57 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2004-07-31 00:00:00PLUMBING PLAN REVIEW, DENIED FBC 2001
 PREVIOUS NOTES DATED 06-23-04
 COMMENT #7 WATER RISER DIAGRAM,
 IS REQUIRED SEC 104.3.1.1
 WHA TO BE LOCATED WITHIN THE WATER
 RISER DIAGRAM.
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-23 Cont ID  
Sent By kstevens Date 2004-06-23 Time 12:29 Rev Time 0.75
Received By kstevens Date 2004-06-23 Time 12:29 Sent To  
Notes
2004-06-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) ALL SHEETS A SPACE FOR THE PRINTED
 NAME OF THE PERSON SEALING THE PLANS IS
 REQUIRED. FAC 61G1-16.004(6) & FS 481.
 2055.
 2) SHT A1 SHOW CLEAR FLOOR SPACE FOR ALL
 ACCESSIBLE FIXTURES. W/C'S 11-4.16.2,
 LAV'S 11-4.19.3, & KIT. SINK 11-4.24.5.
 3) SHT A1 DOORS SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACE REQUIRED FOR ANY FIX-
 TURE. 11-4.22.2.
 4) SHT A1 A DRINKING FOUNTAIN IS REQUIR-
 ED. TABLE 403.1. (SEE SECTION 410.1)
 5) SHT A2 DETAIL D, SHOW SINK HEIGHT AT
 34" MAX. 11-4.24.2, KNEE CLEARANCE 11-4.
 24.3, DEPTH OF SINK 11-4.24.4 AND EX-
 POSED PIPES AND SURFACES 11-4.24.6.
 6) SHT A2 DETAIL "B" SHOW EXPOSED PIPES
 AND SURFACES 11-4.19.4.
 7) SHT P1 WATER RISER DIAGRAM REQUIRED
 SECTION 104.3.1.1. SHOW WATER HAMMER
 ARRESTORS WHERE REQUIRED BY SECTION
 604.9. W.H.A'S SHALL BE LOCATED NEAR THE
 FIXTURES, NOT IN THE CEILING PER PDI-WH
 201.
 8) SHT P1 GENERAL PLUMBING NOTES #17,
 AIR CHAMBERS ARE NOT APPROVED. DELETE
 FROM REFERENCE. SECTION 604.9 & SECTION
 104.2.1
 9) ALL SHEETS, PRINTED NAME OF THE ARCH-
 ITECT IS REQUIRED ON TITLE BLOCK. FAC
 61G1-16.004(6) & FS 481.2055
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]