Plan Review Details - Permit 04060344
Plan Review Stops For Permit 04060344
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-01-05 Cont ID  
Sent By jwitmer Date 2005-01-05 Time 13:05 Rev Time 0.45
Received By jleahy Date 2005-03-23 Time 11:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-12-23 Cont ID  
Sent By jwitmer Date 2004-12-23 Time 16:12 Rev Time 0.75
Received By jwitmer Date 2004-12-23 Time 16:12 Sent To  
Notes
2004-12-23 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04060344
 ADD: 531 25TH ST
 CONT: STUART LEDIS LLC
 TEL: (201)388-7769
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
  
 1)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC TABLE 600
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
 THE FORM PROVIDED IS NOT THE CITY OF
 WEST PALM BEACH UNITY OF TITLE, SEE THE
  
 PLANNING AND ZONING DEPARTMENT , 5TH
 FLOOR OF CITYHALL, THE CITY FORM ONCE
 PLANNING HAS APPROVED IT, THE OWNER
 SHALL HAVE THE DOCUMENT RECORDED AT THE
  
 CLERK OF THE COURT, THE RECORDED
 DOCUMENT IS SUBMITTED BACK TO WPB
 PLANNNING DEPARTMENT AND ANOTHER
 SUBMITTED WITH PERMIT DOCUMENTS.
  
 3) COMMENT3 4 FROM THE PREVIOUS REVIEW,
 A-2 EGRESS DOORS/ 32" CLEAR: 1003.2.1
 THE WIDTH OF THE MEANS OF EGRESS SHALL
 BE DETERMINED FROM THE OCCUPANTS SERVED
 IN ACCORDANCE WITH TABLE 1004.A-2
 MINIMUM CLEAR OPENING OF EXIT DOOR IS
 32". 1012.1.1 EGRESS DOORS USED IN THE
 EXIT ACCESS SHALL PROVIDE A CLEAR
 OPENING OF NOT LESS THAN 32" WIDE.
 SEE ELECTRICAL PLAN WITH EXIT SIGN
 ABOVE A 32" DOOR PROVIDING A 30" NET
 OPENING.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-24 Cont ID  
Sent By mjacobs Date 2004-06-24 Time 14:03 Rev Time 2.00
Received By mjacobs Date 2004-06-24 Time 14:03 Sent To PC
Notes
2004-06-24 00:00:00BUILDING PLAN REVIEW
 PERMIT:04060344
 ADD:531 25TH ST. WEST PALM BEACH,FL
 CONT:STUART M.LEDIS,LLC
 TEL: (561)478-0486
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW:
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)11-4.1.2 VERTICAL ACCESSIBILITY,
 NOTHING IN THIS CODE SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF ANY BUILDING,
 SSTRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE OR BELOW THE OCCUPIAABLE
 GRADE LEVEL.
  
 3) PLEASE SUBMIT ADDITIONAL DETAILS TO
 SHOW ATTATCHMENT AND FASTENING OF
 MATERIALS TO FLOOR AND CEILING DECK.
  
 4) A-2 EGRESS DOOR/ 32" CLEAR:
 1003.2.1. THE WIDTH OF THE MEANS OF
 EGRESS SHALL BE DETERMINED FROM THE
 OCCUPANTS SERVED IN ACCORDANCE WITH
 TABLE 1004.A-2 MINIMUM CLEAR OPENING OF
 EXIT DOOR IS 32". 1012.1.1 EGRESS DOORS
 USED IN THE EXIT ACCESS SHALL PROVIDE A
 CLEAR OPENING OF NOT LESS THAN 32" WIDE.
  
 5) NEW HANDICAP TOILET: PLEASE PROVIDE
 UNISEX SIGN. SEE ACCESSIBILITY CODE
 SEC:11-4.1.6(2) (III)
  
 6) PLEASE INDICATE HANDICAP DINING AREA.
 REFER TO FLORIDA ACCESSIBILITY CODE
 SEC.11-5.4
  
 7) NEW H.C.TOILET DOOR AND EXISTING MEN
 TOILET DOOR NEED TO BE ADDRESS DUE TO
 HALLWAY WIDTH. HALLWAY SHOULD BE AT
 LEAST 58". FBC SEC.1012.1.4
  
 8)EXIT LIGHTING AND SIGNS SHALL
 COMPLY WITH FBC SEC.1016.1.1
  
 9) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 REFER TO SECTION AT EXISTING PARKING.
 PLEASE GIVE SPECIFIC DETAILS.(COOLER/
 FREEZER)
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2005-06-29 Cont ID  
Sent By dpalmer Date 2005-06-29 Time 13:42 Rev Time 1.50
Received By dpalmer Date 2005-06-29 Time 13:42 Sent To I
Notes
2005-06-29 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE ALL CIRCUTIING IS TO
 BE SHOWN ON PLANS AND CORRELATE WITH THE
 SUBMITTED PANEL SCHEDULES.
 215.5
  
 2)NOTE:PLEASE INCLUDE ALL REVISED LOAD
 CALCULATIONS FOR EACH PANEL AND SERVICE.
 PLEASE SEE ALL TRACK LIGHTING AND SHOW
 WINDOW RECEPTS PER 220.12A,B
 220,215.5
  
 3)NOTE: PLEASE SEE RISER SUBMITTED WAS
 UNDER A SEPARATE PERMIT AND IF REVISION
 TO RISER IS MADE, PLEASE SUBMIT UNDER
 THAT PERMIT.
  
 4)NOTE: PLEASE SEE ALL PLANS ARE
 REQUIRED TO HAVE A TITLE BLOCK BY THE
 ENGINEER OF RECORD, AND PLANS ARE ALSO
 REQUIRED TO BE SIGNED DATED AND SEALED.
 FAC 61G15-23.002,FS 471.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
 PLANS SENT TO INCOMING, NEEDDS TO GO ON
 COMM BOARD.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-03-23 Cont ID  
Sent By jleahy Date 2005-03-23 Time 11:07 Rev Time 0.45
Received By jleahy Date 2005-03-23 Time 11:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2005-01-24 Cont ID  
Sent By dpalmer Date 2005-01-24 Time 19:16 Rev Time 0.25
Received By dpalmer Date 2005-01-24 Time 19:16 Sent To  
Notes
2005-01-24 00:00:00************ UNSAT ******************
  
 1)NOTE: PLEASE SEE ALL PLANS SUBMITTED
 UNDER THIS PERMIT MUST BE REVISED BY THE
 ENGINEER OF RECORD.
 PLEASE ALSO SEE "PROVISO" SET-FORTH ON
 PREVIOUS REVIEW WHICH HAS NOT BEEN
 SUBMITTED.
  
 PLEASE REVISE PLANS AND COMPLETE RISER
 FOR 2002 NEC
 NOT COMPLETE AT THIS TIME.
 215.5
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-01-05 Cont ID  
Sent By dpalmer Date 2005-01-05 Time 08:39 Rev Time 0.50
Received By dpalmer Date 2005-01-05 Time 08:39 Sent To  
Notes
2005-01-05 00:00:00********* PROVISO/ REVISION *********
  
 PLEASE REVISE ALL CIRCUITING ON PLANS
 AND CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULE ON A CLEAN SET OF PLANS BEFORE
 FINAL.
  
 IF THERE ARE ANY QUESTIONS, PLEASE
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-12-27 Cont ID  
Sent By dpalmer Date 2004-12-27 Time 09:18 Rev Time 0.25
Received By dpalmer Date 2004-12-27 Time 09:18 Sent To  
Notes
2004-12-27 00:00:00*** UNSAT ***
  
  
 1)NOTE: PLEASE SEE NOTES FROM PREVIOUS
 REVIEW. PLEASE PROVIDE CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE.
 PLEASE SEE CIRCUITING FOR EM/EXT LTS IS
 PER 700.12E, THESE ARE NOT ON A SEPARATE
 CIRCUIT AS NOTED ON PLANS.
  
 2)NOTE: PLEASE SEE A PANEL SCHEDULE WAS
 SUBMITTED SIGNED AND SEALED BY THE
 ENGINEER. PLANS WHICH ARE SIGNED AND
 SEALED ARE REQUIRED TO HAVE A TITLE
 BLOCK PER FAC 61G15-23.002.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-11-18 Cont ID  
Sent By dpalmer Date 2004-11-18 Time 19:52 Rev Time 0.25
Received By dpalmer Date 2004-11-18 Time 19:52 Sent To  
Notes
2004-11-18 00:00:00********* UNSAT 2ND REVIEW **********
  
 1)NOTE: PLEASE SEE NOTES FROM PREVIOUS
 HAS NOT BEEN ADDRESSED.
 THE SAME PLANS HAVE COME BACK IN W/OUT
 ANY CHANGES OR CORRECTIONS.??
  
 2)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WHICH IS NOW ATTACHED WITH
 RESPECT TO DESIGN PROFESSIONAL.
 PLEASE SEE THIS ONLY A NOTICE GIVEN AT
 THIS TIME.
  
 DUE TO PLANS NOT BEING COMPLETE, A
 COMPLETE REVIEW FOR CODE COMPLIANCE CAN
 NOT BE DONE AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-09 Cont ID  
Sent By dpalmer Date 2004-06-09 Time 18:06 Rev Time 0.33
Received By dpalmer Date 2004-06-09 Time 18:06 Sent To  
Notes
2004-06-09 00:00:00********* UNSAT ************
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002,
 AND FS 471.025. PLEASE INCLUDE ALL
 INFORMATION ON TITLE BLOCK AS SET FORTH
 PER ABOVE.
  
 2)NOTE: PLEASE INCLUDE ALL NEW CIRCUIT-
 -ING ON PLANS AND CORRELATE WITH A
 PANEL SCHEDULE TO BE SUBMITTED.
  
 3)NOTE: PLEASE SEE 2002 NEC 210.8B3
 FOR REQUIRED GFI PROTECTION.
  
 PLEASE NOTE: DUE TO MISSING INFORMATION
 A COMPLETE REVIEW FOR ELECTRICAL MAY NOT
 BE DONE AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-07-01 Cont ID  
Sent By mwennerg Date 2005-07-01 Time 15:53 Rev Time 0.00
Received By mwennerg Date 2005-07-01 Time 15:53 Sent To  
Notes
2005-07-01 00:00:00REVISION DATED 6-23-05

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-01-03 Cont ID  
Sent By nmccray Date 2005-01-03 Time 15:44 Rev Time 0.00
Received By nmccray Date 2005-01-03 Time 15:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-06-10 Cont ID  
Sent By mcarsill Date 2004-06-10 Time 16:18 Rev Time 0.00
Received By mcarsill Date 2004-06-10 Time 16:18 Sent To  
Notes
2004-06-10 00:00:001) PLEASE PROVIDE A FURNITURE PLAN.
  
 2) PLEASE PROVIDE AN OCCUPANT LOAD
 COUNT FOR THE LOCATION.
  
 3) THE NEW BATHROOM DOOR NEARLY
 BLOCKS THE HALLWAY. THE SAME
 CONDITION EXISTS ELSEWHERE ON THE
 PLAN. PLEASE ADVISE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-06-24 Cont ID  
Sent By adarroug Date 2005-06-24 Time 10:21 Rev Time 0.00
Received By adarroug Date 2005-06-24 Time 10:21 Sent To  
Notes
2005-06-30 00:00:00TO "COMM" BD#23
2005-06-24 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-03-15 Cont ID  
Sent By adarroug Date 2005-03-15 Time 13:38 Rev Time 0.00
Received By adarroug Date 2005-03-15 Time 13:38 Sent To E
Notes
2005-03-15 00:00:00TO "JLEAHY" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-01-18 Cont ID  
Sent By mjacobs Date 2005-01-18 Time 10:53 Rev Time 0.00
Received By mjacobs Date 2005-01-18 Time 10:53 Sent To E
Notes
2005-01-18 00:00:00TO "DP" DESK/REV.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-01-12 Cont ID  
Sent By mjacobs Date 2005-01-12 Time 15:50 Rev Time 0.00
Received By mjacobs Date 2005-01-12 Time 15:50 Sent To M
Notes
2005-01-12 00:00:00TO "M/AC" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-12-17 Cont ID  
Sent By mjacobs Date 2004-12-17 Time 08:31 Rev Time 0.00
Received By mjacobs Date 2004-12-17 Time 08:31 Sent To  
Notes
2004-12-17 00:00:00SENT TO "COMM BD#52"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-11-17 Cont ID  
Sent By mjacobs Date 2004-11-17 Time 07:18 Rev Time 0.00
Received By mjacobs Date 2004-11-17 Time 15:33 Sent To  
Notes
2004-11-17 00:00:00SENT TO COMM BD#47

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-12 Cont ID  
Sent By csiegber Date 2004-11-12 Time 16:54 Rev Time 0.00
Received By csiegber Date 2004-11-12 Time 16:54 Sent To  
Notes
2004-11-12 00:00:00TO COMM BD#

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-15 Cont ID  
Sent By csiegber Date 2004-07-06 Time 09:07 Rev Time 0.00
Received By csiegber Date 2004-06-08 Time 15:56 Sent To  
Notes
2004-06-08 00:00:00TO COMM BD#64

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2005-01-03 Cont ID  
Sent By pkrauss Date 2005-01-03 Time 14:43 Rev Time 0.25
Received By pkrauss Date 2005-01-03 Time 14:35 Sent To  
Notes
2005-01-03 00:00:00PROVISO:
 NO MECHANICAL PLANS OR CONTRACTOR
 INDICATED WITH THE PERMIT APPLICATION.
 PLAN SHEET 1 OF 3 INDICATES RELOCATED
 PIZZA OVEN, HOOD TO VENT TO THE
 EXTERIOR.PLEASE INDICATE TERMINATION
 OF THE EXHUAST HOOD AND ALL PERTINENT
 INFORMATION WITH MECHANICAL PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-06-21 Cont ID  
Sent By pkrauss Date 2004-06-21 Time 08:21 Rev Time 0.35
Received By pkrauss Date 2004-06-21 Time 08:14 Sent To  
Notes
2004-06-21 00:00:00DENIED:
 PLEASE CLARIFY RELOCATED PIZZA OVEN.
 THE PERMIT APPLICATION INDICATES "REMOVE
 EXISTING PIZZA ROOM WALL @ EQUIP".
 IS THE LOCATION OF THE PIZZA OVEN ON
 THE PLAN WHERE IT WAS RELOCATED TO?
 DOES THE HOOD EXTEND OVER THE OVEN?
 HOW WILL THE HEAT BE REMOVED?
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-07-09 Cont ID  
Sent By kstevens Date 2005-07-01 Time 15:55 Rev Time 0.50
Received By kstevens Date 2005-07-09 Time 15:55 Sent To  
Notes
2005-07-09 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-01-04 Cont ID  
Sent By pschmitz Date 2005-01-04 Time 11:01 Rev Time 0.00
Received By pschmitz Date 2005-01-04 Time 10:12 Sent To  
Notes
2005-01-04 00:00:00PLUMBING PLAN REVIEW PROVISO:
  
 PREVIOUS COMMENTS DATED 12-29-04 BY KEN
 MEETING WITH LOUIS MARTENIZ, GEO CEARS.
 NOTE (1)
 WATER PIPING AND WATER HAMMER ARRESTOR
 SIZE, LOCATION SUBJECT TO FIELD
 INSPECTOR APPROVAL AS WELL THE DRAIN
 WASTE VENT SYSTE, INCLUDING FLOOR SINKS
  
 AS BUILT DRAWING RERQUIRED FOR FINAL.
 NOTE (4)
 FOOD PREP SINK SHALL DRAIN INDIRECTLY
 TO
 A FLOOR SINK.
 DISH WASHER WASTE, DRAIN TO SANITARY
 SEWER.
 NOTE (5)
 GREASE TRAP EXISTING, SUBJECT TO
 APPROVAL FROM WPB ENVIROMENTAL
 COMPLIANCE.
 SEPERATE PLANS AND PERMIT FOR GAS BEFORE
 STARTING WORK.
 END OF COMMENTS, QUESTIONS CONTACT
 PAUL SCHMITZ561-805-6692

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-12-29 Cont ID  
Sent By kstevens Date 2004-12-29 Time 16:11 Rev Time 1.25
Received By kstevens Date 2004-12-29 Time 16:11 Sent To  
Notes
2004-12-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
  
 1) FROM PREVIOUS REVIEW:
 SUBMIT A WATER RISER DIAGRAM FOR ALL
 NEW WORK. SHOW ALL PIPE SIZES AND WATER
 HAMMER ARRESTORS REQUIRED BY SECTION
 604.9, LOCATED NEAR THE FIXTURES AS
 REQUIRED BY PDI-WH 201.
 2) FROM PREVIOUS REVIEW:
 ATTACH WORKSHEETS, (2 SHEETS), TO EACH
 SET OF PLANS FOR REVIEW.
 ***NEW COMMENTS***
 3) SHT 1 OF 3 PLUMBING RISER BAY 529. NO
 SANT. DRAINAGE SHOWN FOR NEW HAND SINK.
 THE THREE COMPARTMENT SINK SHALL DRAIN
 INTO A FLOOR SINK, AS REQUIRED IN
 SECTION 802.3. PLEASE INDICATE ON
 PLANS.
 SECTION 104.2.1.
 4) SHT 1 OF 3. PLUMBING RISER KITCHEN
 BAY 533, FOOD PREP SINK SHALL DRAIN
 INDIRECTLY PER SECTION 802.1.1. DISH
 MACHINE SHALL DRAIN INTO THE SANITARY
 SYSTEM, NOT THE GREASE WASTE SYSTEM PER
 CITY CODE.
 5) SUBMIT RESPONSE SHEET FROM RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE FOR THE
 SIZING OF THE GREASE INTECEPTOR. WASTE
 ORD. #2938-96
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-07-06 Cont ID  
Sent By kstevens Date 2004-07-06 Time 08:39 Rev Time 0.75
Received By kstevens Date 2004-07-06 Time 08:39 Sent To  
Notes
2004-07-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SUBMIT A SANITARY AND WATER RISER
 DIAGRAM FOR ALL NEW WORK. SHOW ALL PIPE
 SIZES AND IF WATER HAMMER ARE USED PER
 SECTION 604.9 THEY SHALL BE LOCATED NEAR
 THE FIXTURE IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING. PDI-WH 201
 2) SEPARATE GAS PLANS/PERMIT REQUIRED.
 SEE ATTACHED SHEET FOR GAS PERMIT REQ-
 UIREMENTS.
 3) ROUTE PLANS TO DBPR, HOTEL AND REST-
 URANT DIVISION FOR REVIEW. 2 SETS OF
 PLANS SHALL BE STAMPED BY DBPR AND THE
 WORKSHEETS ATTACHED TO EACH PLAN FOR RE-
 VIEW BY CITY WPB.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]