Plan Review Details - Permit 04051244
Plan Review Stops For Permit 04051244
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2005-03-02 Cont ID  
Sent By jwitmer Date 2005-03-02 Time 09:58 Rev Time 0.77
Received By jwitmer Date 2005-03-02 Time 09:58 Sent To  
Notes
2005-03-02 00:00:00REVISIONS DATED:
 1-11-05
 1-21-05
 2-15-05OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2004-12-16 Cont ID  
Sent By jwitmer Date 2004-12-16 Time 07:29 Rev Time 0.55
Received By jwitmer Date 2004-12-16 Time 07:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-11-23 Cont ID  
Sent By jwitmer Date 2004-11-23 Time 07:53 Rev Time 0.55
Received By jwitmer Date 2004-11-23 Time 07:53 Sent To PC
Notes
2004-11-23 00:00:0011-23-04 REVISION# 2. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-11-10 Cont ID  
Sent By jwitmer Date 2004-11-10 Time 13:19 Rev Time 2.22
Received By jwitmer Date 2004-11-10 Time 13:19 Sent To  
Notes
2004-11-10 00:00:0011-10-04 REVISIONSOK JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-10-05 Cont ID  
Sent By jwitmer Date 2004-10-05 Time 12:34 Rev Time 0.77
Received By jwitmer Date 2004-10-05 Time 10:48 Sent To PC
Notes
2004-10-05 00:00:00REVISION # 1, OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-08-17 Cont ID  
Sent By csiegber Date 2004-10-04 Time 13:10 Rev Time 4.44
Received By jwitmer Date 2004-08-17 Time 10:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-07-19 Cont ID  
Sent By jwitmer Date 2004-07-19 Time 09:45 Rev Time 2.22
Received By jwitmer Date 2004-07-19 Time 09:45 Sent To  
Notes
2004-07-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04051244
 ADD: 3021 OKEECHOBEE BLVD
 CONT: POPPER AND ASSOCIATES
 TEL: (561)719-7133
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PROVISO: NO SOILS REPORT TO BE
 SUBMITTED, CONTRACTOR/ DESIGN PROFESSION
 ALS WILL BE CONTINUING WORK AT OWN RISK.
 WILL BE STATED ON PERMIT CARD!!!!
  
 3) SUBMITTED ENERGY CALCULATIONS:
 FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 4) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EFIS-(PAREXEIFS)
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 NOTE***** PROVIDE NOC FOR BOTH
 HORIZONTAL AND VERTICAL APPLICATIONS.
  
 5) PROVIDE THE FIRE RATING REPORT FOR
 THE EFIS SYSTEM, SINCE THIS STRUCTURE IS
 IN A FIRE ZONE EXTERIOR WALLS ARE TO BE
 NON-COMBUSTIBLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-24 Cont ID  
Sent By jwitmer Date 2004-06-24 Time 12:03 Rev Time 2.55
Received By jwitmer Date 2004-06-24 Time 12:03 Sent To PC
Notes
2004-06-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04051244
 ADD: 3021 OKEECHOBEE BLVD
 CONT: POPPER & ASSOC
 TEL: (561)719-7133
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS/ W MANUAL "J"
  
 4) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 5) FIRE DISTRICT NO TYPE VI CONSTRUCTION
 F102.1 WEST PALM BEACH AMENDMENT
  
 6) A-108 DETAILS INDICATE PLYWOOD SUB-
 SHEATHING- NO TYPE VI CONSTRUCTION
 ALLOWED IN FIRE DISTRICT!
  
 7) SITE PLAN INDICATES THE ACCESSIBLE
 ROUTE BETWEEN THE HUMMER SHOWROOM AND
 THE VW SHOWROOM AND THE PUBLIC WAY. THE
 PLAN ALSO INDICATES THE DROP WALK FOR AC
 CESSIBILITY, BUT NOT FOR THE ACCESSIBLE
 PARKING SPACESAND ACCESS ISLE AT THE
 HUMMER DEALERSHIP.
  
 8) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) SWING SERVICE DOOR,
 B) FIXED WINDOWS, STOREFRONT
 C) ROOFING STEELMASTER
 D) WALL LOUVERS
 E) STORM SHUTTERS- OVER LOUVERS A-112
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9) THE A-112 SHEET INDICATES STOREFRONT
 WINDOW OPENINGS LARGER THAN THE SUBMIT-
 TED REPORT. EITHER MULLION REPORTS WITH
 THE REQUIRED LENGTH WILL BE REQUIRED OR
 DIFFERENT WINDOW REPORTS.
  
 10) THE ROOFING SYSTEM STEELMASTER
 BUILDINGS WILL REQUIRE EITHER PRODUCT
 TESTING REPORTS, (FLORIDA) OR APPROVAL
 THROUGH FLORIDA COMMUNITY AFFAIRS.
  
 11) A-111 INDICATES THE USE OF "STO
 SYSTEM" FIRE DISTRICT NO COMBUSTIBLE
 ON THE EXTERIOR OF BUILDING, F102.2.7.
  
 12) SHEET S-104 INDICATES ADDITIONAL
 INFORMATION TO BE SUPPLIED BY STEELMAS-
 TER, DECK TO BEAM CONNENCTIONS. PROVIDE
 ADDITIONAL INFORMATION.
  
 13)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-03-25 Cont ID  
Sent By dpalmer Date 2005-03-25 Time 11:43 Rev Time 0.30
Received By dpalmer Date 2005-03-25 Time 11:43 Sent To  
Notes
2005-03-25 00:00:00REDLINED,
  
 MDP, SHOWN AS MLO, OK PER JAKE LEAHY.
 MDP SHALL CONTAIN NO 1-POLE OR 2-POLE
 BRKRS PER 230.71.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-02-25 Cont ID  
Sent By dpalmer Date 2005-02-25 Time 08:17 Rev Time 0.50
Received By dpalmer Date 2005-02-25 Time 05:56 Sent To  
Notes
2005-02-25 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE SEE ORIG REDLINES FROM
 REIVEW 6/04 BY JAKE LEAHY, PLEASE SEE
 NOTE #7 ON RISER IS MISSING FROM "NOTES
 LEGEND".
  
 2)NOTE: PLEASE CLARIFY METHOD OF
 EQUIPMENT GROUNDING BETWEEN MDP TO
 PANELS.
 250.110,250.122
  
 3)NOTE: PLEASE SEE ORIG PLANS CALLED FOR
 A MCB IN MDP AND NOW MDP IS SHOWN AS MLO
 AND IS SHOWING MORE THAN 6-SPACES.
 PLEASE SEE 230.71A
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-11-02 Cont ID  
Sent By dpalmer Date 2004-11-02 Time 15:04 Rev Time 0.50
Received By dpalmer Date 2004-11-02 Time 14:51 Sent To  
Notes
2004-11-02 00:00:00REVIEWED REVISED SHEETS E-101, E102
 ONLY.
 REDLINED ALL FIXTURES & FAN ON PLANS TO
 BE LISTED BY A NRTL.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-06-09 Cont ID  
Sent By jleahy Date 2004-06-09 Time 08:29 Rev Time 1.00
Received By jleahy Date 2004-06-09 Time 08:29 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2004-07-07 Cont ID  
Sent By mamini Date 2004-07-07 Time 14:45 Rev Time 0.50
Received By mamini Date 2004-07-07 Time 14:45 Sent To  
Notes
2004-07-07 00:00:00PASSED WITH PROVISOS:
 1. ANY WORK WITHIN PUBLIC R.O.W WILL
 REQUIRES A SEPARATE PERMIT FROM THE
 PUBLIC UTILITIES & ENGINEERING 494-1083
 DEAN LAUDERMILK.
 2. EROSION & SEDIMENTATION CONTROL
 DEVICES SHALL BE IN PLACE PRIOR TO
 BEGINNING CLEARING THE SITE, DEMOLITION,
 OR OTHER SUCH CONSRTUCTION ACTIVITIES.
 THE DEVICES SHALL BE INSTALLED,
 MONOTORED, AND MAINTAINED IN ACCORDANCE
 WITH ALL APPLICABLE FEDERAL, STATE, AND
 LOCAL REQUIREMENTS.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-05-28 Cont ID  
Sent By mamini Date 2004-05-28 Time 15:52 Rev Time 1.00
Received By mamini Date 2004-05-28 Time 15:51 Sent To  
Notes
2004-05-28 00:00:00FAILED:
 1. PLEASE INCLUDE CIVIL PLAN SHOWING
 CONNECTION FOR THE PROPOSED WATER AND
 SEWER, ARE THESE NEW CONNECTIONS TO THE
 CITY MAIN OR TO EXISTING ON SITE?
 2. DO PROPOSED STRUCTURES HAVE ANY
 IMPACT ON DRAINAGE ON SITE?
 3. ANY WORK WITHIN PUBLIC R.O.W REQUIRES
 A SEPARATE PERMIT FROM PUBLIC UTILITIES
 AND ENGINEERING 494-1040/1041
 DEAN LAUDERMILK.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-03-17 Cont ID  
Sent By mwennerg Date 2005-03-17 Time 15:44 Rev Time 0.00
Received By mwennerg Date 2005-03-17 Time 15:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-11-24 Cont ID  
Sent By nmccray Date 2004-11-24 Time 13:49 Rev Time 0.00
Received By nmccray Date 2004-11-24 Time 13:48 Sent To  
Notes
2004-11-24 00:00:00REVISION DATED 10-13-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-07-12 Cont ID  
Sent By nmccray Date 2004-07-12 Time 14:54 Rev Time 0.00
Received By nmccray Date 2004-07-12 Time 14:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-06-02 Cont ID  
Sent By mcarsill Date 2004-06-02 Time 14:07 Rev Time 0.00
Received By mcarsill Date 2004-06-02 Time 14:07 Sent To  
Notes
2004-06-02 00:00:001) A KNOX-BOX WILL BE REQUIRED.
  
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE FIRE ALARM SYSTEM. FIRE ALARM
 CIRCUITS SHALL BE CLASS A STYLE D, OR
 FULLY ADDRESSABLE.
  
 3) THE SITE PLAN DISPLAYS ONLY ONE FIRE
 HYDRANT. SURELY, THERE ARE OTHER FIRE
 HYDRANTS IN THE VICINITY.
  
 4) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 5) SUITABLE ROADS ARE TO BE PROVIDED
 DURING CONSTRUCTION FOR FIRE AND
 PARAMEDICAL EQUIPMENT.
  
 6) PLEASE INDICATE HOW VEHICLES ARE
 GOING TO BE DISPLAYED WITHIN THE
 BUILDING. TYPICALLY,WHEN VEHICLES ARE
 STORED, THEY CONTAIN VERY LITTLE FUEL
 HAVE AT LEAST ONE BATTERY TERMINAL
 DISCONNECTED AND TAPED. ALSO THE GAS CAP
 IS TO BE LOCKED.
  
 7) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-06-03 Cont ID  
Sent By shill Date 2005-06-03 Time 16:03 Rev Time 0.00
Received By shill Date 2005-06-03 Time 16:03 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-05-20 Cont ID  
Sent By adarroug Date 2005-05-20 Time 08:31 Rev Time 0.00
Received By adarroug Date 2005-05-20 Time 08:30 Sent To M
Notes
2005-05-20 00:00:00TO "PKRAUSS" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-03-22 Cont ID  
Sent By adarroug Date 2005-03-22 Time 13:37 Rev Time 0.00
Received By adarroug Date 2005-03-22 Time 13:37 Sent To E
Notes
2005-03-22 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-02-17 Cont ID  
Sent By adarroug Date 2005-02-17 Time 10:52 Rev Time 0.00
Received By adarroug Date 2005-02-17 Time 10:52 Sent To  
Notes
2005-02-17 00:00:00TO "COMM" BD#46/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-02-14 Cont ID  
Sent By adarroug Date 2005-02-14 Time 15:51 Rev Time 0.00
Received By adarroug Date 2005-02-14 Time 15:50 Sent To P
Notes
2005-02-14 00:00:00TO KSTEVENS DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-12-08 Cont ID  
Sent By mjacobs Date 2004-12-08 Time 15:29 Rev Time 0.00
Received By mjacobs Date 2004-12-08 Time 15:29 Sent To B
Notes
2004-12-08 00:00:00SENT TO "JW" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-11-18 Cont ID  
Sent By mjacobs Date 2004-11-18 Time 13:44 Rev Time 0.00
Received By mjacobs Date 2004-11-18 Time 13:44 Sent To B
Notes
2004-11-18 00:00:00SENT TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-10-27 Cont ID  
Sent By csiegber Date 2004-10-27 Time 11:16 Rev Time 0.00
Received By csiegber Date 2004-10-27 Time 11:16 Sent To  
Notes
2004-10-27 00:00:00TO COMM BD#54

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-04 Cont ID  
Sent By csiegber Date 2004-10-04 Time 13:10 Rev Time 0.00
Received By csiegber Date 2004-10-04 Time 13:10 Sent To B
Notes
2004-10-04 00:00:00TO JW DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-03 Cont ID  
Sent By csiegber Date 2004-08-03 Time 14:25 Rev Time 0.00
Received By csiegber Date 2004-08-03 Time 14:25 Sent To  
Notes
2004-08-03 00:00:00TO COMM BD#39

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-06 Cont ID  
Sent By csiegber Date 2004-07-06 Time 16:53 Rev Time 0.00
Received By csiegber Date 2004-07-06 Time 16:53 Sent To  
Notes
2004-07-06 00:00:00TO COMM BD#53

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-24 Cont ID  
Sent By lmartine Date 2004-06-24 Time 11:00 Rev Time 0.00
Received By lmartine Date 2004-05-28 Time 10:53 Sent To  
Notes
2004-05-28 00:00:00TO COMM BD#56

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2005-06-06 Cont ID  
Sent By pkrauss Date 2005-06-06 Time 16:17 Rev Time 0.25
Received By pkrauss Date 2005-06-06 Time 16:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-05-23 Cont ID  
Sent By pkrauss Date 2005-05-23 Time 07:13 Rev Time 0.45
Received By pkrauss Date 2005-05-23 Time 07:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2005-03-12 Time   Rev Time 0.00
Received By hmoser Date 2005-03-12 Time 09:33 Sent To  
Notes
2005-03-12 00:00:001) REFER TO SECTION 606.2.1 SUPPLY AIR
 SYSTEMS FOR FAN SHUTDOWN.
 2) REFER TO SECTION 606.4.1 SUPERVISON
 FOR FAN SHUTDOWN .FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-11-17 Cont ID  
Sent By pkrauss Date 2004-11-17 Time 08:43 Rev Time 0.55
Received By pkrauss Date 2004-11-17 Time 07:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-06-24 Cont ID  
Sent By pkrauss Date 2004-06-24 Time 15:04 Rev Time 0.40
Received By pkrauss Date 2004-06-24 Time 15:04 Sent To  
Notes
2004-06-24 00:00:00APPROVED 6-10-04

Review Stop P PLUMBING
Rev No 7 Status P Date 2005-03-11 Cont ID  
Sent By kstevens Date 2005-03-11 Time 18:16 Rev Time 0.96
Received By kstevens Date 2005-03-11 Time 18:16 Sent To  
Notes
2005-03-11 00:00:00REVISION OK - CHANGED RD'S 5, 6, & 7 TO
 TWO INCH RD AND CHANGED PIPING TO TWO
 INCH. ADDED CONDENSATE FROM NEW ROOF A/C
 UNIT. SHTS P-101, P-201 & MP-101

Review Stop P PLUMBING
Rev No 6 Status F Date 2005-03-11 Cont ID  
Sent By kstevens Date 2005-03-11 Time 09:15 Rev Time 0.50
Received By kstevens Date 2005-03-11 Time 09:15 Sent To  
Notes
2005-03-11 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL DRAWINGS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE
 FOLLOWING INFORMATION.
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (2) FIRM LICENSE NUMBER/CERTIFICATE OF
 AUTHROIZATION.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status F Date 2005-03-01 Cont ID  
Sent By kstevens Date 2005-03-01 Time 17:58 Rev Time 0.45
Received By kstevens Date 2005-03-01 Time 17:58 Sent To  
Notes
2005-03-01 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1) DRAWINGS SHALL BE DRAWN TO SCALE WITH
 SUFFICIENT CLARITY AND DETAIL TO
 INDICATE THE NATURE AND CHARACTER OF THE
 WORK. SECTION 104.2.1. INFORMATION HARD
 TO READ AND SOME INFORMATION APPEARS TO
 BE CUT OFF FROM SHEET. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8-INCH
 SCALE. REVISION STATES 1/8", BUT ARE NOT
 1/8" SCALE. SECTION 104.2.1.3.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-11-24 Cont ID  
Sent By kstevens Date 2004-11-24 Time 15:46 Rev Time 1.33
Received By kstevens Date 2004-11-24 Time 15:46 Sent To  
Notes
2004-11-24 00:00:00REVISION OK - SHTS MP-101, P-101 & P-201

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-08-19 Cont ID  
Sent By kstevens Date 2004-08-19 Time 18:29 Rev Time 1.00
Received By kstevens Date 2004-08-19 Time 18:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-07-24 Cont ID  
Sent By kstevens Date 2004-07-24 Time 11:40 Rev Time 1.25
Received By kstevens Date 2004-07-24 Time 11:40 Sent To  
Notes
2004-07-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
  
  
 FROM PREVIOUS REVIEW:
 3) SHT A-114 DETAIL 1 SHOW MEASUREMENT
 FROM THE CENTER OF W/C TO WALL. FIG 28
 REVISION SHOWS 1'10". 1'6" REQUIRED.
 9) SUBMIT STORM RISERS FOR SECONDARY
 ROOF DRAINS. SHOW PIPE SIZES AND SLOPE.
 INDICATE TERMINATION POINT. SECTION
 104.3.1.1
  
 NEW COMMENTS:
 1B) SHT MP-101 4" HORIZONTAL LEADER AT
 1/4" PER FT. NOT SUFFICIENT FOR 2,470 SF
 PER TABLE 1106.3- ALSO IF HORIZONTAL
 LEADER ON SECONDARY DRAIN, THEN MINIMUM
 5" REQUIRED FOR AREAS AT ROOF DRAINS
 #'S 1 & 4 AND 8" REQUIRED FOR AREAS AT
 ROOF DRAINS #'S 2 & 3.
 2B) SHOW SIZE AND LOCATION OF SECONDARY
 ROOF DRAINS FOR THE LOWER ROOFS. SECTION
 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-18 Cont ID  
Sent By kstevens Date 2004-06-18 Time 10:48 Rev Time 2.25
Received By kstevens Date 2004-06-18 Time 10:48 Sent To  
Notes
2004-06-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) ALL ARCHITECTURAL SHEET SHALL BE SEA-
 LED AND DATED PER FAC 61G1-16.003 AND
 FS 481.2055.
 2) SHT A-114 SHOW CLEAR FLOOR SPACE FOR
 SINK IN BREAK ROOM. SECTION 11-4.24.5
 3) SHT A-114 DETAILS 1 AND 15 SHOW THE
 MEASURMENT FROM THE CENTER OF THE LAVS &
 WATER CLOSETS TO THE WALL. FIG 28. 18"
 FOR W/C AND 15" FOR LAV.
 4) SHT A-114 HANDICAP SINK AT COUNTER
 DETAIL SHALL BE MAXIMUM 34" PER SECTION
 11-4.24.2. DETAIL SHOWS 68"
 5) SHTS A-103 & MP-101 SHOW SECONDARY
 ROOF DRAINS IN DIFFERENT LOCATIONS.
 CORRELATE PLANS. SECTION 104.2.1
 6) SHT MP-100 SUBMIT CALCULATIONS FOR
 UPPER AND LOWER ROOFS. SHOW SF FOR EACH
 AREA AND SHOW 1/2 AREA OF VERTICAL WALLS
 INCLUDING PARAPETS ADDED TO CALCULATIONS
 FOR EACH AREA. THEN SHOW TOTAL ROOF AREA
 DRAINING TO EACH ROOF DRAIN. SECTIONS
 1106, 1107 AND ALL SUBSECTIONS.
 7) SHT P-201 URINAL SHALL CONNECT DOWN-
 STREAM OF THE LAV ON THE STACK IN THE
 MEN'S TOILET ROOM. SECTION 1104.2.1
 8) SHT P-201 BREAK ROOM SINK SHALL DIS-
 CHARGE DOWNSTREAM OF THE FIXTURES IN THE
 WOMENS TOILET ROOM. SECTION 909.1
 9) SUBMIT STORM RISERS FOR THE PRIMARY
 AND SECONDARY ROOF DRAINS, AND SUBMIT
 BLDG STORM ISOMETRICS. SHOW ALL PIPE
 SIZES AND SLOPE. INDICATE TERMINATION
 POINT FOR EACH SYSTEM.
 10) SHT P-201 PLUMBING SPECIFICATIONS,
 MATERIALS, (F) AIR CHAMBERS ARE NOT
 APPROVED. DELETE FROM REFERENCE. SECTION
 604.9
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-08-05 Cont ID  
Sent By gjoyce Date 2004-08-05 Time 09:35 Rev Time 0.25
Received By gjoyce Date 2004-08-05 Time 09:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-07-26 Cont ID  
Sent By gjoyce Date 2004-07-26 Time 09:20 Rev Time 0.25
Received By gjoyce Date 2004-07-26 Time 09:20 Sent To  
Notes
2004-07-26 00:00:00PLEASE PROVIDE A LANDSCAPE PLAN FOR THE
 HUMMER SITE GMJ