Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2004-06-03 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-06-03 |
Time |
08:40 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2004-06-03 |
Time |
08:40 |
Sent To |
|
|
Notes |
2004-06-03 00:00:00 | DENIED: | | 1.PROVIDE 2 COPIES OF PLANS AND ALL | | SUBMITTAL DATA FOR REVIEW PER 2001 FBC | | 104.2.1.ONLY ONE SET PROVIDED. | | | | 2.PROVIDE ENERGY CALCULATION PER THE | | 2001 FBC CHAPTER 13 SUB-CHAPTER 4 FOR | | COMMERCIAL COMPLIANCE.LOAD | | CALCULATIONS SUBMITTED ARE FOR | | RESIDENTIAL. | | | | 3.PROVIDE OUTSIDE AIR CALCULATIONS PER | | 2001 FBC(M) 403.3. | | | | 4.PROVIDE A LETTER FROM A STRUCTURAL | | ENGINEER INDICATING THE ROOF IS | | DESIGNED FOR STRUCTURAL LOAD.LETTER | | SHALL BE SIGNED, SEALED AND DATED. | | PLEASE PROVIDE 2 COPIES. | | | | 5.HEIGHT REQUIREMENT FOR THE C.U. | | LOCATED ON THE ROOF SHALL BE PER 2001 | | FBC 1511.7. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
|