Plan Review Stops For Permit 04050953 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
9 |
Status |
P |
Date |
2005-06-11 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-06-11 |
Time |
15:24 |
Rev Time |
0.50 |
Received By |
shill |
Date |
2005-06-11 |
Time |
15:24 |
Sent To |
PC |
|
Notes |
2005-06-11 00:00:00 | UNIT 6 ROOF FRAMING REVISION |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
8 |
Status |
F |
Date |
2005-03-09 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-03-08 |
Time |
17:29 |
Rev Time |
1.00 |
Received By |
shill |
Date |
2005-03-08 |
Time |
17:29 |
Sent To |
|
|
Notes |
2005-03-09 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | REVISION #4 A1 DATED 4/16/05 | | | | 1.)ONLY ONE SHEET A1 SUBMITTED. | | PLEASE SUBMIT TWO COPIES FOR ISSUANCE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
7 |
Status |
F |
Date |
2005-03-02 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-03-02 |
Time |
11:30 |
Rev Time |
0.50 |
Received By |
shill |
Date |
2005-03-02 |
Time |
11:30 |
Sent To |
PC |
|
Notes |
2005-03-02 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)REVISED SHEET A3 APPEARS TO BE A | | REVISION PRIOR TO THE ONE APPROVED.IT | | IS DATED 2/22/05; ANOTHER REVISION WAS | | APPROVED DATED 2/23/05. | | | | IF THIS IS NOT CORRECT, PLEASE SUBMIT | | THE REVISION AGAIN WITH THE CORRECT | | REVISION NUMBER (SHOULD BE #5 AS A | | REVISION #4 HAS ALREADY BEEN REVIEWED) | | WITH ALL CHANGES CLEARLY INDICATED ON | | THE PLAN. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2005-03-02 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-03-02 |
Time |
10:23 |
Rev Time |
1.00 |
Received By |
shill |
Date |
2005-03-02 |
Time |
10:23 |
Sent To |
PC |
|
Notes |
2005-03-02 00:00:00 | REVISED A3, D1 DATED 2/23/05 | | REVISION #4 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2004-11-03 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2004-11-03 |
Time |
12:56 |
Rev Time |
1.00 |
Received By |
shill |
Date |
2004-11-03 |
Time |
12:56 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2004-10-22 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-10-29 |
Time |
14:50 |
Rev Time |
1.00 |
Received By |
shill |
Date |
2004-10-22 |
Time |
17:24 |
Sent To |
PC |
|
Notes |
2004-10-22 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)IMPACT FEES MUST BE PAID TO PALM | | BEACH COUNTY.THE PLANS MUST BE | | STAMPED AND THE RECEIPT ATTACHED TO | | THE APPLICATION.233-5025 | | | | 2.)PROVIDE FLORIDA STATE PRODUCT | | APPROVALS FOR THE ARCH ALUMINUM | | NOAS PROVIDED.WWW.FLORIDABUILDING.ORG | | RULE 9B-72 FAC. | | | | 3.)A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURTS BEFORE | | A PERMIT CAN BE ISSUED. | | | | 4.)SIGN THE OWNER/AGENT LINE OF THE | | ENERGY CALC. | | | | ***NO RESUB FEE*** |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2004-10-12 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-10-18 |
Time |
17:39 |
Rev Time |
2.00 |
Received By |
shill |
Date |
2004-10-12 |
Time |
08:55 |
Sent To |
PC |
|
Notes |
2004-10-12 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)IMPACT FEES MUST BE PAID TO PALM | | BEACH COUNTY.THE PLANS MUST BE | | STAMPED AND THE RECEIPT ATTACHED TO | | THE APPLICATION.233-5025 | | | | 2.)PROVIDE PRODUCT APPROVALS FOR | | THE FOLLOWING: | | EXTERIOR DOORS | | STOREFRONT WINDOWS AND DOORS, TRANSOM | | FIXED GLASS WINDOWS | | MULLIONS | | NOTE - ALL ARE TO BE IMPACT AS PER PLAN | | NOTE - CONTRACTOR ELECTED TO HAVE THE | | PLAN FAIL RATHER THAN PROVISO SEPARATE | | PERMITS. | | | | 3.)A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURTS BEFORE A | | PERMIT CAN BE ISSUED. | | | | 4.)SIGN THE OWNER/AGENT LINE OF THE | | ENERGY CALC. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2004-08-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2004-08-10 |
Time |
15:21 |
Rev Time |
3.00 |
Received By |
shill |
Date |
2004-08-10 |
Time |
15:21 |
Sent To |
|
|
Notes |
2004-08-10 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)THE SWING OF DOORS 1 & 2 WERE | | CHANGED, A NOTE ABOUT 4 HR BLOCK WAS | | REMOVED; THESE CHANGES WERE NOT CLOUDED. | | WHAT OTHER CHANGES WERE MADE TO THE | | PLAN WHICH WERE NOT CLEARLY INDICATED? | | | | 2.)IMPACT FEES MUST BE PAID TO PALM | | BEACH COUNTY.THE PLANS MUST BE | | STAMPED AND THE RECEIPT ATTACHED TO THE | | APPLICATION. | | | | 3.)INSULATION IS REQUIRED IN THE | | TENANT PARTITION WALLS, SEE PREVIOUS | | LIST ITEM #12.7-A10 DOES NOT SHOW | | THE REQUIRED INSULATION. | | | | 4.)PROVIDE A LINTEL SCHEDULE. | | | | 5.)SHEET E1 IS NOT SIGNED AND DATED. | | | | 6.)SEE PREVIOUS LIST, ITEM #13 IN | | PROVIDING PRODUCT APPROVALS: | | EXTERIOR DOORS | | STOREFRONT WINDOWS AND DOORS, TRANSOM | | FIXED GLASS WINDOWS | | MULLIONS | | NOTE - ALL GLAZING TO BE IMPACT AS PER | | PLAN. | | | | 7.)SEE PREVIOUS LIST, ITEM #14. | | BEFORE RESUBMITTING, HAVE THE NEW | | SHEETS APPROVED BY HISTORIC. | | | | 8.)THERE IS A NOTE FROM YOUR GLASS | | SUPPLIER STATING THAT THE HEIGHTS ARE | | TOO LARGE FOR THE STOREFRONT SYSTEM. | | AS PRODUCT APPROVALS WERE NOT SUBMITTED | | FOR THE STOREFRONT, PLEASE ADDRESS | | AS APPLICABLE. | | | | 9.)WHEN RESUBMITTING, CHANGE OUT ONLY | | REVISED SHEETS AND SUBMIT OLD SHEETS | | SEPARATELY. | | | | 10.) A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURTS BEFORE A | | PERMIT CAN BE ISSUED. | | | | 11.) THE PRINTED NAME OF THE PERSON | | SEALING THE PLAN IS TO BE ON EACH SHEET. | | FAC61G1-16.004. | | | | 12.) SIGN THE OWNER/AGENT LINE OF THE | | ENERGY CALC (PAGE 2). |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2004-06-18 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2004-06-18 |
Time |
11:40 |
Rev Time |
3.00 |
Received By |
shill |
Date |
2004-06-17 |
Time |
17:19 |
Sent To |
|
|
Notes |
2004-06-18 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)DECLARE AN OCCUPANCY CLASSIFICATION | | AND OCCUPANT LOAD. | | | | 2.)SHEET LS1 IS INCORRECTLY LABELED | | AS "PLUMBING PLAN". | | | | 3.)SEPARATE PERMITS REQUIRED FOR THE | | AWNINGS, MECHANICAL, ROOF. | | | | 4.)THE FLOOR LIVE LOAD IS TO COMPLY | | WITH FBC TABLE 1604.1, SHEET A1 (DESIGN | | PARAMETERS). | | | | 5.)THIS IMPROVEMENT IS GREATER THAN | | 50%, FBC3401.2.6. | | | | 6.)PROVIDE ENERGY CALCS, FBC400. | | | | 7.) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | ITIONS, EXIT ENCLOSURES, AND FIRE | | RATED WALLS REQUIRED TO HAVE PROTECTED | | OPENINGS SHALL BE EFFECTIVELY AND | | PERMANETLY IDENTIFIED WITH SIGNS OR | | STENCILING IN A MANNER ACCEPTABLE TO THE | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | CEILING CEILING AND IN CONCEALED SPACES. | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | PROTECT ALL OPENINGS". | | | | 8.) 1503.4.4 PROTECTION AGAINST DECAY & | | TERMITES. CONDENSATE LINES & ROOF DOWN | | SPOUTS SHALL DISCHARGE AT LEAST 1 FT. | | AWAY FROM THE STRUCTURE SIDEWALL, | | WHETHER BY UNDERGROUND PIPING, TAIL EX- | | TENSIONS, OR SPLASH BLOCKS. | | | | 9.)TENANT SEPARATION REQUIRED FBC | | 704.3.PROVIDE ASSEMBLY NUMBER OR | | CALCULATED FIRE RESISTANCE FBC709. SHEET | | A1 APPEARS TO INDICATE THE PARTITION | | WALLS AS CONCRETE BLOCK 4HR, BUT REFERS | | TO DETAIL 7-A10 WHICH IS METAL FRAME. | | DETAIL 7-A10 REFERS TO UL U1165; I WAS | | UNABLE TO FIND THIS IN THE UL BOOK OR | | THE WEBSITE. | | | | 10.) SHEET A7 HAS BEEN CROSSED OFF WITH | | A NOTE TO SEE REVISED A7.INCLUDE THIS | | REVISED A7, APPROVED BY HISTORIC, WHEN | | RESUBMITTING. | | | | 11.)DOORS 1 AND 2 ARE TO COMPLY WITH | | FBC FIGURE 25, MANEUVERING CLEARANCES | | AT DOORS, FOR BOTH PUSH AND PULL SIDES. | | | | 12.)INSULATION REQUIRED FOR COMMON | | WALLS, FBC402. | | | | 13.)SUBMIT PRODUCT APPROVALS FOR THE | | FOLLOWING: | | EXTERIOR DOORS | | STOREFRONT WINDOWS AND DOORS, TRANSOM | | FIXED GLASS WINDOWS | | MULLIONS | | NOTE - ALL GLAZING TO BE IMPACT AS PER | | PLAN | | | | 14.)BEFORE RESUBMITTING, HAVE THE | | NEW SHEETS APPROVED BY HISTORIC. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2005-05-02 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-05-02 |
Time |
13:16 |
Rev Time |
0.30 |
Received By |
dpalmer |
Date |
2005-05-02 |
Time |
13:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2005-02-23 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-02-23 |
Time |
05:40 |
Rev Time |
0.30 |
Received By |
dpalmer |
Date |
2005-02-23 |
Time |
05:27 |
Sent To |
|
|
Notes |
2005-02-23 00:00:00 | ****** UNSAT ****** | | | | 1)NOTE: PLEASE CORRELATE RTU OCP WITH | | RTU'S NOTED ON BOTTOM OF E-3. | | PLEASE CLARIFY A/C SYSTEM. PANEL | | SCHEDULE INDICATES RTU'S AND AHU'S? ARE | | THE RTU'S COND UNITS? | | PLEASE ALSO CORRELATE WITH PLANS. | | | | 2)NOTE: PLEASE SHOW SERVICE ENTRANCE | | CONDCUTORS PER 310.16,240.4. | | 215.5 | | | | 3)NOTE: PLEASE SEE ANY HAND DRAWN | | CHANGES TO PLANS: EACH MUST BE SIGNED | | AND DATED BY THE ENGINEER OF RECORD. OR | | PLEASE REPRINT SHEETS WITH CHANGES AND | | SIGN, DATE AND SEAL SHEET. | | FS 471.025 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2004-09-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-09-21 |
Time |
16:36 |
Rev Time |
1.00 |
Received By |
dpalmer |
Date |
2004-09-21 |
Time |
16:21 |
Sent To |
|
|
Notes |
2004-09-21 00:00:00 | ALL NEW ELECTRICAL SHEETS/SETS. | | STAMPED NEW AND VOIDED OLD. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2004-07-28 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-07-28 |
Time |
14:25 |
Rev Time |
0.33 |
Received By |
dpalmer |
Date |
2004-07-28 |
Time |
13:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2004-06-02 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-06-02 |
Time |
14:13 |
Rev Time |
1.50 |
Received By |
dpalmer |
Date |
2004-06-02 |
Time |
14:13 |
Sent To |
|
|
Notes |
2004-06-02 00:00:00 | ********* UNSAT ************** | | | | 1)NOTE: PLEASE SEE PLANS CONTAIN A TITLE | | BLOCK FOR AN ENGINEER ON ELECTRICAL | | PLANS. IF THIS PERSON(ENG) IS RESPON- | | -SIBLE FOR PLANS, PLANS MUST BE SIGNED | | AND SEALED BY THAT PERSON. FS 471/481 | | PLANS MUST ALSO CONTAIN A CLEAR AND | | RAISED SEAL. | | PLEASE SEE FS 471.025 AND FS 481.221 | | WHICH REQUIRES A 'SIGNATURE'. | | PLEASE PROVIDE A SIGNED, SEAL NOTARIZED | | LETTER FOR PROOF OF LEGAL SIGNATURE. | | | | 2)NOTE: PLEASE CORRELATE PERMIT APPL- | | -CATION AND PLANS. APPL MENTIONS 5 UNITS | | AND PLANS SHOW 6 UNITS? | | | | 3)NOTE: PLEASE COMPLETE RISER DIAGRAM. | | MISSING INFORMATION FOR MAIN(S). | | 230.72,230.76,230.79 ETC | | MISSING CONDUITS/CONDUCTORS ETC. | | 215.5/310.16 ETC | | | | 4)NOTE: PLEASE SHOW GROUNDING ELECTRODE | | SYSTEM PER 250.50. | | EQUIPMENT GROUNDING CONDUCTORS PER 250. | | 122. | | | | 5)NOTE: PLEASE SEE OCP SHOWN FOR RECEPTS | | ON PANEL SCHEDULE. 80A?? | | | | 6)NOTE: PLEASE CORRELATE OCP SHOWN FOR | | A/C UNITS WITH MECH PLANS. | | | | 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | RATED FOR THE AVAILABLE FAULT CURRENT. | | PER 110.9/215.5 | | | | 8 )NOTE: PLEASE SHOW LOAD CALCULATIONS, | | PLEASE SHOW PER | | 220.3,220.10,220.11,220.13 ETC. | | PLEASE ALSO SHOW ALL CONTINOUS LOADS | | AT 125% PER 215.3,230.42 | | | | 9)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- | | -ING OF EM/EXT LTS. | | | | PLANS NOT COMPLETE AT THIS TIME FOR A | | FULL AND COMPLETE REVIEW. | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | INSERT ONLY NEW SHEETS INTO COMPLETE | | SETS FOR REVIEW AND STAMPING. | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | AS THEY MAY HAVE AN AFFECT ON ELECTRICAL | | PLANS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2005-03-17 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2005-03-17 |
Time |
13:58 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2005-03-17 |
Time |
13:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2004-10-12 |
|
|
Cont ID |
|
Sent By |
nmccray |
Date |
2004-10-12 |
Time |
11:11 |
Rev Time |
0.00 |
Received By |
nmccray |
Date |
2004-10-12 |
Time |
11:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2004-05-25 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2004-05-25 |
Time |
13:11 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2004-05-25 |
Time |
13:11 |
Sent To |
|
|
Notes |
2004-05-25 00:00:00 | 1) DEMOLITION, RENOVATION, AND | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | 2) IF FUEL POWERED EQUIPMENT ARE USED | | FOR CUTTING PURPOSES, ADEQUATE | | VENTILATION IS TO BE PROVIDED TO | | PREVENT THE ACCUMULATION OF CARBON | | MONOXIDE FUMES. | | | | 3) CANVAS AWNING IS TO BE FIRE | | RETARDANT SINCE LOCATION IS WITHIN | | THE CITY FIRE LIMITS. | | | | 4) BUILDING ADDRESS REQUIRED ON PROPER | | ELEVATION. A MINIMUM OF AT LEAST 6" | | HIGH NUMBERS ARE REQUIRED. | | | | 5) PORTABLE FIRE EXTINGUISHERS ARE | | REQUIRED. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
11 |
Status |
N |
Date |
2005-06-09 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-06-09 |
Time |
09:15 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2005-06-09 |
Time |
09:15 |
Sent To |
B |
|
Notes |
2005-06-09 00:00:00 | TO SH DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
10 |
Status |
N |
Date |
2005-05-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-05-06 |
Time |
16:22 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-05-06 |
Time |
16:22 |
Sent To |
B |
|
Notes |
2005-05-06 00:00:00 | TO "SHILL" DESK/REVISION |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
9 |
Status |
N |
Date |
2005-04-25 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-04-25 |
Time |
16:19 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-04-25 |
Time |
16:19 |
Sent To |
E |
|
Notes |
2005-04-25 00:00:00 | TO "DPALMER" DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
8 |
Status |
N |
Date |
2005-03-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-03-01 |
Time |
14:30 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-03-01 |
Time |
14:15 |
Sent To |
B |
|
Notes |
2005-03-01 00:00:00 | TO SHILL DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2005-02-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-02-24 |
Time |
10:05 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-02-24 |
Time |
10:05 |
Sent To |
B |
|
Notes |
2005-02-24 00:00:00 | TO SHILL DESK/REVISION |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2005-02-18 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-02-18 |
Time |
11:29 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-02-18 |
Time |
11:29 |
Sent To |
|
|
Notes |
2005-02-18 00:00:00 | TO "COMM" BD#21 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2004-10-29 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-10-29 |
Time |
14:50 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-10-29 |
Time |
14:51 |
Sent To |
B |
|
Notes |
2004-10-29 00:00:00 | TO SH DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2004-10-18 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-10-18 |
Time |
17:39 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-10-18 |
Time |
17:39 |
Sent To |
B |
|
Notes |
2004-10-18 00:00:00 | TO SH DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2004-08-30 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-08-30 |
Time |
10:50 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-08-30 |
Time |
10:50 |
Sent To |
|
|
Notes |
2004-08-30 00:00:00 | TO COMM BD#45 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2004-07-22 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-07-22 |
Time |
15:15 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-07-22 |
Time |
15:15 |
Sent To |
|
|
Notes |
2004-07-22 00:00:00 | TO COMM BD#43 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2004-06-18 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2004-06-18 |
Time |
13:08 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2004-05-20 |
Time |
16:15 |
Sent To |
|
|
Notes |
2004-05-20 00:00:00 | TO COMM BD#53 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2005-07-22 |
|
|
Cont ID |
|
Sent By |
prafter |
Date |
2005-07-22 |
Time |
09:17 |
Rev Time |
1.00 |
Received By |
prafter |
Date |
2005-07-22 |
Time |
09:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2004-11-01 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-11-01 |
Time |
12:46 |
Rev Time |
0.55 |
Received By |
pkrauss |
Date |
2004-09-16 |
Time |
10:52 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2004-08-05 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-08-05 |
Time |
09:43 |
Rev Time |
0.55 |
Received By |
pkrauss |
Date |
2004-08-05 |
Time |
07:44 |
Sent To |
|
|
Notes |
2004-08-05 00:00:00 | DENIED: | | 1.TITLE BLOCK REQUIRED FOR THE | | ENGINEER.PROVIDE LICENCE NUMBER. PLANS | | ARE TO BE SIGNED NOT INITIALED BY THE | | ENGINEER.ENGINEERING FIRMS ARE | | REQUIRED TO HAVE A CERTIFICATE OF | | AUTHORIZATION NUMBER INDICATED ON THE | | TITLE BLOCK. FS 471.025 & 481.221 | | FAC 61G15-23.002 | | | | 2.PLAN SHEET M-2 IS NOT WITH THE | | NEW SET OF RE-SUBMITTED PLANS.PLANS | | THAT WERE NOT REVISED BUT ARE STILL PART | | OF THE A SUBMITTAL NEEED TO BE COMBINED | | WITH THE REVISED SHEETS FOR A COMPLETE | | SET OF PLANS FOR CONSTRUCTION. | | | | 3.EQUIPMENT SCHEDULE ARE NOT INCLUDED | | WITH THE RE-SUBMITTED DRAWINGS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2004-06-09 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-06-09 |
Time |
11:07 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2004-06-09 |
Time |
11:07 |
Sent To |
|
|
Notes |
2004-06-09 00:00:00 | DENIED: | | 1.PLAN SHEET M-2, THE EQUIPMENT | | SCHEDULE INDICATES 3 SYSTEMS.PLAN M-1 | | INDICATES 6 PACKAGE UNITS.PLEASE | | CORRECT THE EQUIPMENT SCHEDULE. | | | | 2.PROVIDE OUTSIDE AIR CALCULATIONS. | | INDICATE OUTSIDE AIR REQUIREMENT ON THE | | PLAN IN ACCORDANCE WITH 2001 FBC(M) | | TABLE 403.3. | | | | 3.INDICATE ON THE PLAN, TERMINATION | | OF THE CONDENSATE DRAIN. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2004-10-09 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2004-10-09 |
Time |
06:16 |
Rev Time |
1.00 |
Received By |
kstevens |
Date |
2004-10-09 |
Time |
06:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
2004-07-31 00:00:00 | 2ND PLUMBING PLAN REVIEW DENIED FBC 2001 | | (1) NO RESPONSE LETTER FROM ARCHITECT | | RE: PREVIOUS COMMENTS DATED 06-15-04 | | NUMBER 1, 2, AND COMMENT #4 TAB 403.1 | | REQUIRES A DRINKING FOUNTAIN FOR EACH | | SPACE. | | END OF COMMENTS, QUESTIONS 561-805-6692 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2004-06-15 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2004-06-15 |
Time |
13:30 |
Rev Time |
1.00 |
Received By |
kstevens |
Date |
2004-06-15 |
Time |
13:30 |
Sent To |
|
|
Notes |
2004-06-15 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1) PERMIT APPLICATION STATES 5 BAYS, THE | | PLANS SHOW 6 BAYS. CORRELATE APPLICATION | | WITH PLANS. | | 2) THE PERSNOAL SIGNATURE OF THE ARCHIT- | | ECT SHALL APPEAR ON THE DOCUMENTS TO BE | | FILED FOR PUBLIC RECORD. INITIALS ARE | | NOT ACCEPTABLE. FAC 61G1-16.003 & FS | | 481.2055. | | 3) SUBMIT CALCULATIONS FOR PRIMARY AND | | SECONDARY ROOF DRAINS. SECTIONS 1106 & | | 1107. SHOW SQUARE FOOTAGE OF ROOF AND | | SHOW 1/2 AREA OF ALL VERTICAL WALLS IN- | | CLUDING PARAPETS ADDED TO AREA OF ROOF. | | INDICATE SLOPE OF GUTTERS PER TABLE | | 1106.6 AND SHOW HIGH POINTS OF GUTTER. | | 4) INDICATE THE OCCUPANCIES OF THE BAYS. | | TABLE 403.1 WILL DETERMINE WHICH FIXTUR- | | ES WILL BE REQUIRED ACCORDING TO THE | | OCCUPANCY OF EACH SPACE. DRINKING FOUNT- | | AINS SHALL BE REQUIRED FOR EACH SPACE. | | SEE SECTION 410.1. | | 5) SHT P-1 PLUMBING NOTES: | | #4 DIELECTRIC UNIONS ARE NOT APPROVED | | FOR WATER DISTRIBUTION. DELETE REFERENCE | | OR MODIFY TO READ DIELECTRIC COUPLING. | | #6 AIR CHAMBERS ARE NOT APPROVED. DE- | | LETE FROM REFERENCE. SECTION 604.9 | | 6) AN RPZ BACKFLOW IS REQUIRED ON THE | | WATER SERVICE. SECTION 608.13.2 | | 7) A WATER RISER DIAGRAM ISOMETRIC IS | | REQUIRED. SECTION 104.3.1.1. | | 8) OTHER COMMENTS MAY FOLLOW WHEN THE | | OCCUPANCY IS ESTABLISHED. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2004-06-11 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2004-06-11 |
Time |
08:30 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2004-06-11 |
Time |
08:30 |
Sent To |
|
|
Notes |
|
|