Plan Review Details - Permit 04050953
Plan Review Stops For Permit 04050953
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2005-06-11 Cont ID  
Sent By shill Date 2005-06-11 Time 15:24 Rev Time 0.50
Received By shill Date 2005-06-11 Time 15:24 Sent To PC
Notes
2005-06-11 00:00:00UNIT 6 ROOF FRAMING REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2005-03-09 Cont ID  
Sent By shill Date 2005-03-08 Time 17:29 Rev Time 1.00
Received By shill Date 2005-03-08 Time 17:29 Sent To  
Notes
2005-03-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 REVISION #4 A1 DATED 4/16/05
  
 1.)ONLY ONE SHEET A1 SUBMITTED.
 PLEASE SUBMIT TWO COPIES FOR ISSUANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2005-03-02 Cont ID  
Sent By shill Date 2005-03-02 Time 11:30 Rev Time 0.50
Received By shill Date 2005-03-02 Time 11:30 Sent To PC
Notes
2005-03-02 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)REVISED SHEET A3 APPEARS TO BE A
 REVISION PRIOR TO THE ONE APPROVED.IT
 IS DATED 2/22/05; ANOTHER REVISION WAS
 APPROVED DATED 2/23/05.
  
 IF THIS IS NOT CORRECT, PLEASE SUBMIT
 THE REVISION AGAIN WITH THE CORRECT
 REVISION NUMBER (SHOULD BE #5 AS A
 REVISION #4 HAS ALREADY BEEN REVIEWED)
 WITH ALL CHANGES CLEARLY INDICATED ON
 THE PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-03-02 Cont ID  
Sent By shill Date 2005-03-02 Time 10:23 Rev Time 1.00
Received By shill Date 2005-03-02 Time 10:23 Sent To PC
Notes
2005-03-02 00:00:00REVISED A3, D1 DATED 2/23/05
 REVISION #4

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-11-03 Cont ID  
Sent By shill Date 2004-11-03 Time 12:56 Rev Time 1.00
Received By shill Date 2004-11-03 Time 12:56 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-10-22 Cont ID  
Sent By csiegber Date 2004-10-29 Time 14:50 Rev Time 1.00
Received By shill Date 2004-10-22 Time 17:24 Sent To PC
Notes
2004-10-22 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO
 THE APPLICATION.233-5025
  
 2.)PROVIDE FLORIDA STATE PRODUCT
 APPROVALS FOR THE ARCH ALUMINUM
 NOAS PROVIDED.WWW.FLORIDABUILDING.ORG
 RULE 9B-72 FAC.
  
 3.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE
 A PERMIT CAN BE ISSUED.
  
 4.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 ***NO RESUB FEE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-10-12 Cont ID  
Sent By csiegber Date 2004-10-18 Time 17:39 Rev Time 2.00
Received By shill Date 2004-10-12 Time 08:55 Sent To PC
Notes
2004-10-12 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO
 THE APPLICATION.233-5025
  
 2.)PROVIDE PRODUCT APPROVALS FOR
 THE FOLLOWING:
 EXTERIOR DOORS
 STOREFRONT WINDOWS AND DOORS, TRANSOM
 FIXED GLASS WINDOWS
 MULLIONS
 NOTE - ALL ARE TO BE IMPACT AS PER PLAN
 NOTE - CONTRACTOR ELECTED TO HAVE THE
 PLAN FAIL RATHER THAN PROVISO SEPARATE
 PERMITS.
  
 3.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 4.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-08-27 Cont ID  
Sent By shill Date 2004-08-10 Time 15:21 Rev Time 3.00
Received By shill Date 2004-08-10 Time 15:21 Sent To  
Notes
2004-08-10 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE SWING OF DOORS 1 & 2 WERE
 CHANGED, A NOTE ABOUT 4 HR BLOCK WAS
 REMOVED; THESE CHANGES WERE NOT CLOUDED.
 WHAT OTHER CHANGES WERE MADE TO THE
 PLAN WHICH WERE NOT CLEARLY INDICATED?
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 3.)INSULATION IS REQUIRED IN THE
 TENANT PARTITION WALLS, SEE PREVIOUS
 LIST ITEM #12.7-A10 DOES NOT SHOW
 THE REQUIRED INSULATION.
  
 4.)PROVIDE A LINTEL SCHEDULE.
  
 5.)SHEET E1 IS NOT SIGNED AND DATED.
  
 6.)SEE PREVIOUS LIST, ITEM #13 IN
 PROVIDING PRODUCT APPROVALS:
 EXTERIOR DOORS
 STOREFRONT WINDOWS AND DOORS, TRANSOM
 FIXED GLASS WINDOWS
 MULLIONS
 NOTE - ALL GLAZING TO BE IMPACT AS PER
 PLAN.
  
 7.)SEE PREVIOUS LIST, ITEM #14.
 BEFORE RESUBMITTING, HAVE THE NEW
 SHEETS APPROVED BY HISTORIC.
  
 8.)THERE IS A NOTE FROM YOUR GLASS
 SUPPLIER STATING THAT THE HEIGHTS ARE
 TOO LARGE FOR THE STOREFRONT SYSTEM.
 AS PRODUCT APPROVALS WERE NOT SUBMITTED
 FOR THE STOREFRONT, PLEASE ADDRESS
 AS APPLICABLE.
  
 9.)WHEN RESUBMITTING, CHANGE OUT ONLY
 REVISED SHEETS AND SUBMIT OLD SHEETS
 SEPARATELY.
  
 10.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 11.) THE PRINTED NAME OF THE PERSON
 SEALING THE PLAN IS TO BE ON EACH SHEET.
 FAC61G1-16.004.
  
 12.) SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC (PAGE 2).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-18 Cont ID  
Sent By shill Date 2004-06-18 Time 11:40 Rev Time 3.00
Received By shill Date 2004-06-17 Time 17:19 Sent To  
Notes
2004-06-18 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)DECLARE AN OCCUPANCY CLASSIFICATION
 AND OCCUPANT LOAD.
  
 2.)SHEET LS1 IS INCORRECTLY LABELED
 AS "PLUMBING PLAN".
  
 3.)SEPARATE PERMITS REQUIRED FOR THE
 AWNINGS, MECHANICAL, ROOF.
  
 4.)THE FLOOR LIVE LOAD IS TO COMPLY
 WITH FBC TABLE 1604.1, SHEET A1 (DESIGN
 PARAMETERS).
  
 5.)THIS IMPROVEMENT IS GREATER THAN
 50%, FBC3401.2.6.
  
 6.)PROVIDE ENERGY CALCS, FBC400.
  
 7.) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 8.) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 9.)TENANT SEPARATION REQUIRED FBC
 704.3.PROVIDE ASSEMBLY NUMBER OR
 CALCULATED FIRE RESISTANCE FBC709. SHEET
 A1 APPEARS TO INDICATE THE PARTITION
 WALLS AS CONCRETE BLOCK 4HR, BUT REFERS
 TO DETAIL 7-A10 WHICH IS METAL FRAME.
 DETAIL 7-A10 REFERS TO UL U1165; I WAS
 UNABLE TO FIND THIS IN THE UL BOOK OR
 THE WEBSITE.
  
 10.) SHEET A7 HAS BEEN CROSSED OFF WITH
 A NOTE TO SEE REVISED A7.INCLUDE THIS
 REVISED A7, APPROVED BY HISTORIC, WHEN
 RESUBMITTING.
  
 11.)DOORS 1 AND 2 ARE TO COMPLY WITH
 FBC FIGURE 25, MANEUVERING CLEARANCES
 AT DOORS, FOR BOTH PUSH AND PULL SIDES.
  
 12.)INSULATION REQUIRED FOR COMMON
 WALLS, FBC402.
  
 13.)SUBMIT PRODUCT APPROVALS FOR THE
 FOLLOWING:
 EXTERIOR DOORS
 STOREFRONT WINDOWS AND DOORS, TRANSOM
 FIXED GLASS WINDOWS
 MULLIONS
 NOTE - ALL GLAZING TO BE IMPACT AS PER
 PLAN
  
 14.)BEFORE RESUBMITTING, HAVE THE
 NEW SHEETS APPROVED BY HISTORIC.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-05-02 Cont ID  
Sent By dpalmer Date 2005-05-02 Time 13:16 Rev Time 0.30
Received By dpalmer Date 2005-05-02 Time 13:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-02-23 Cont ID  
Sent By dpalmer Date 2005-02-23 Time 05:40 Rev Time 0.30
Received By dpalmer Date 2005-02-23 Time 05:27 Sent To  
Notes
2005-02-23 00:00:00****** UNSAT ******
  
 1)NOTE: PLEASE CORRELATE RTU OCP WITH
 RTU'S NOTED ON BOTTOM OF E-3.
 PLEASE CLARIFY A/C SYSTEM. PANEL
 SCHEDULE INDICATES RTU'S AND AHU'S? ARE
 THE RTU'S COND UNITS?
 PLEASE ALSO CORRELATE WITH PLANS.
  
 2)NOTE: PLEASE SHOW SERVICE ENTRANCE
 CONDCUTORS PER 310.16,240.4.
 215.5
  
 3)NOTE: PLEASE SEE ANY HAND DRAWN
 CHANGES TO PLANS: EACH MUST BE SIGNED
 AND DATED BY THE ENGINEER OF RECORD. OR
 PLEASE REPRINT SHEETS WITH CHANGES AND
 SIGN, DATE AND SEAL SHEET.
 FS 471.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-09-21 Cont ID  
Sent By dpalmer Date 2004-09-21 Time 16:36 Rev Time 1.00
Received By dpalmer Date 2004-09-21 Time 16:21 Sent To  
Notes
2004-09-21 00:00:00ALL NEW ELECTRICAL SHEETS/SETS.
 STAMPED NEW AND VOIDED OLD.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-07-28 Cont ID  
Sent By dpalmer Date 2004-07-28 Time 14:25 Rev Time 0.33
Received By dpalmer Date 2004-07-28 Time 13:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-06-02 Cont ID  
Sent By dpalmer Date 2004-06-02 Time 14:13 Rev Time 1.50
Received By dpalmer Date 2004-06-02 Time 14:13 Sent To  
Notes
2004-06-02 00:00:00********* UNSAT **************
  
 1)NOTE: PLEASE SEE PLANS CONTAIN A TITLE
 BLOCK FOR AN ENGINEER ON ELECTRICAL
 PLANS. IF THIS PERSON(ENG) IS RESPON-
 -SIBLE FOR PLANS, PLANS MUST BE SIGNED
 AND SEALED BY THAT PERSON. FS 471/481
 PLANS MUST ALSO CONTAIN A CLEAR AND
 RAISED SEAL.
 PLEASE SEE FS 471.025 AND FS 481.221
 WHICH REQUIRES A 'SIGNATURE'.
 PLEASE PROVIDE A SIGNED, SEAL NOTARIZED
 LETTER FOR PROOF OF LEGAL SIGNATURE.
  
 2)NOTE: PLEASE CORRELATE PERMIT APPL-
 -CATION AND PLANS. APPL MENTIONS 5 UNITS
 AND PLANS SHOW 6 UNITS?
  
 3)NOTE: PLEASE COMPLETE RISER DIAGRAM.
 MISSING INFORMATION FOR MAIN(S).
 230.72,230.76,230.79 ETC
 MISSING CONDUITS/CONDUCTORS ETC.
 215.5/310.16 ETC
  
 4)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 SYSTEM PER 250.50.
 EQUIPMENT GROUNDING CONDUCTORS PER 250.
 122.
  
 5)NOTE: PLEASE SEE OCP SHOWN FOR RECEPTS
 ON PANEL SCHEDULE. 80A??
  
 6)NOTE: PLEASE CORRELATE OCP SHOWN FOR
 A/C UNITS WITH MECH PLANS.
  
 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 8 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 9)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM/EXT LTS.
  
 PLANS NOT COMPLETE AT THIS TIME FOR A
 FULL AND COMPLETE REVIEW.
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT ONLY NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 AS THEY MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-03-17 Cont ID  
Sent By mwennerg Date 2005-03-17 Time 13:58 Rev Time 0.00
Received By mwennerg Date 2005-03-17 Time 13:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-10-12 Cont ID  
Sent By nmccray Date 2004-10-12 Time 11:11 Rev Time 0.00
Received By nmccray Date 2004-10-12 Time 11:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-05-25 Cont ID  
Sent By mcarsill Date 2004-05-25 Time 13:11 Rev Time 0.00
Received By mcarsill Date 2004-05-25 Time 13:11 Sent To  
Notes
2004-05-25 00:00:001) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) IF FUEL POWERED EQUIPMENT ARE USED
 FOR CUTTING PURPOSES, ADEQUATE
 VENTILATION IS TO BE PROVIDED TO
 PREVENT THE ACCUMULATION OF CARBON
 MONOXIDE FUMES.
  
 3) CANVAS AWNING IS TO BE FIRE
 RETARDANT SINCE LOCATION IS WITHIN
 THE CITY FIRE LIMITS.
  
 4) BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION. A MINIMUM OF AT LEAST 6"
 HIGH NUMBERS ARE REQUIRED.
  
 5) PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-06-09 Cont ID  
Sent By shill Date 2005-06-09 Time 09:15 Rev Time 0.00
Received By shill Date 2005-06-09 Time 09:15 Sent To B
Notes
2005-06-09 00:00:00TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-05-06 Cont ID  
Sent By adarroug Date 2005-05-06 Time 16:22 Rev Time 0.00
Received By adarroug Date 2005-05-06 Time 16:22 Sent To B
Notes
2005-05-06 00:00:00TO "SHILL" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-04-25 Cont ID  
Sent By adarroug Date 2005-04-25 Time 16:19 Rev Time 0.00
Received By adarroug Date 2005-04-25 Time 16:19 Sent To E
Notes
2005-04-25 00:00:00TO "DPALMER" DESK

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-03-01 Cont ID  
Sent By adarroug Date 2005-03-01 Time 14:30 Rev Time 0.00
Received By adarroug Date 2005-03-01 Time 14:15 Sent To B
Notes
2005-03-01 00:00:00TO SHILL DESK

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-02-24 Cont ID  
Sent By adarroug Date 2005-02-24 Time 10:05 Rev Time 0.00
Received By adarroug Date 2005-02-24 Time 10:05 Sent To B
Notes
2005-02-24 00:00:00TO SHILL DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-02-18 Cont ID  
Sent By adarroug Date 2005-02-18 Time 11:29 Rev Time 0.00
Received By adarroug Date 2005-02-18 Time 11:29 Sent To  
Notes
2005-02-18 00:00:00TO "COMM" BD#21

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-10-29 Cont ID  
Sent By csiegber Date 2004-10-29 Time 14:50 Rev Time 0.00
Received By csiegber Date 2004-10-29 Time 14:51 Sent To B
Notes
2004-10-29 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-18 Cont ID  
Sent By csiegber Date 2004-10-18 Time 17:39 Rev Time 0.00
Received By csiegber Date 2004-10-18 Time 17:39 Sent To B
Notes
2004-10-18 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-30 Cont ID  
Sent By csiegber Date 2004-08-30 Time 10:50 Rev Time 0.00
Received By csiegber Date 2004-08-30 Time 10:50 Sent To  
Notes
2004-08-30 00:00:00TO COMM BD#45

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-22 Cont ID  
Sent By csiegber Date 2004-07-22 Time 15:15 Rev Time 0.00
Received By csiegber Date 2004-07-22 Time 15:15 Sent To  
Notes
2004-07-22 00:00:00TO COMM BD#43

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-18 Cont ID  
Sent By shill Date 2004-06-18 Time 13:08 Rev Time 0.00
Received By shill Date 2004-05-20 Time 16:15 Sent To  
Notes
2004-05-20 00:00:00TO COMM BD#53

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-07-22 Cont ID  
Sent By prafter Date 2005-07-22 Time 09:17 Rev Time 1.00
Received By prafter Date 2005-07-22 Time 09:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-11-01 Cont ID  
Sent By pkrauss Date 2004-11-01 Time 12:46 Rev Time 0.55
Received By pkrauss Date 2004-09-16 Time 10:52 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-08-05 Cont ID  
Sent By pkrauss Date 2004-08-05 Time 09:43 Rev Time 0.55
Received By pkrauss Date 2004-08-05 Time 07:44 Sent To  
Notes
2004-08-05 00:00:00DENIED:
 1.TITLE BLOCK REQUIRED FOR THE
 ENGINEER.PROVIDE LICENCE NUMBER. PLANS
 ARE TO BE SIGNED NOT INITIALED BY THE
 ENGINEER.ENGINEERING FIRMS ARE
 REQUIRED TO HAVE A CERTIFICATE OF
 AUTHORIZATION NUMBER INDICATED ON THE
 TITLE BLOCK. FS 471.025 & 481.221
 FAC 61G15-23.002
  
 2.PLAN SHEET M-2 IS NOT WITH THE
 NEW SET OF RE-SUBMITTED PLANS.PLANS
 THAT WERE NOT REVISED BUT ARE STILL PART
 OF THE A SUBMITTAL NEEED TO BE COMBINED
 WITH THE REVISED SHEETS FOR A COMPLETE
 SET OF PLANS FOR CONSTRUCTION.
  
 3.EQUIPMENT SCHEDULE ARE NOT INCLUDED
 WITH THE RE-SUBMITTED DRAWINGS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-06-09 Cont ID  
Sent By pkrauss Date 2004-06-09 Time 11:07 Rev Time 0.40
Received By pkrauss Date 2004-06-09 Time 11:07 Sent To  
Notes
2004-06-09 00:00:00DENIED:
 1.PLAN SHEET M-2, THE EQUIPMENT
 SCHEDULE INDICATES 3 SYSTEMS.PLAN M-1
 INDICATES 6 PACKAGE UNITS.PLEASE
 CORRECT THE EQUIPMENT SCHEDULE.
  
 2.PROVIDE OUTSIDE AIR CALCULATIONS.
 INDICATE OUTSIDE AIR REQUIREMENT ON THE
 PLAN IN ACCORDANCE WITH 2001 FBC(M)
 TABLE 403.3.
  
 3.INDICATE ON THE PLAN, TERMINATION
 OF THE CONDENSATE DRAIN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-10-09 Cont ID  
Sent By kstevens Date 2004-10-09 Time 06:16 Rev Time 1.00
Received By kstevens Date 2004-10-09 Time 06:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2004-07-31 00:00:002ND PLUMBING PLAN REVIEW DENIED FBC 2001
 (1) NO RESPONSE LETTER FROM ARCHITECT
 RE: PREVIOUS COMMENTS DATED 06-15-04
 NUMBER 1, 2, AND COMMENT #4 TAB 403.1
 REQUIRES A DRINKING FOUNTAIN FOR EACH
 SPACE.
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-15 Cont ID  
Sent By kstevens Date 2004-06-15 Time 13:30 Rev Time 1.00
Received By kstevens Date 2004-06-15 Time 13:30 Sent To  
Notes
2004-06-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) PERMIT APPLICATION STATES 5 BAYS, THE
 PLANS SHOW 6 BAYS. CORRELATE APPLICATION
 WITH PLANS.
 2) THE PERSNOAL SIGNATURE OF THE ARCHIT-
 ECT SHALL APPEAR ON THE DOCUMENTS TO BE
 FILED FOR PUBLIC RECORD. INITIALS ARE
 NOT ACCEPTABLE. FAC 61G1-16.003 & FS
 481.2055.
 3) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SECTIONS 1106 &
 1107. SHOW SQUARE FOOTAGE OF ROOF AND
 SHOW 1/2 AREA OF ALL VERTICAL WALLS IN-
 CLUDING PARAPETS ADDED TO AREA OF ROOF.
 INDICATE SLOPE OF GUTTERS PER TABLE
 1106.6 AND SHOW HIGH POINTS OF GUTTER.
 4) INDICATE THE OCCUPANCIES OF THE BAYS.
 TABLE 403.1 WILL DETERMINE WHICH FIXTUR-
 ES WILL BE REQUIRED ACCORDING TO THE
 OCCUPANCY OF EACH SPACE. DRINKING FOUNT-
 AINS SHALL BE REQUIRED FOR EACH SPACE.
 SEE SECTION 410.1.
 5) SHT P-1 PLUMBING NOTES:
 #4 DIELECTRIC UNIONS ARE NOT APPROVED
 FOR WATER DISTRIBUTION. DELETE REFERENCE
 OR MODIFY TO READ DIELECTRIC COUPLING.
 #6 AIR CHAMBERS ARE NOT APPROVED. DE-
 LETE FROM REFERENCE. SECTION 604.9
 6) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2
 7) A WATER RISER DIAGRAM ISOMETRIC IS
 REQUIRED. SECTION 104.3.1.1.
 8) OTHER COMMENTS MAY FOLLOW WHEN THE
 OCCUPANCY IS ESTABLISHED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-06-11 Cont ID  
Sent By aaponte Date 2004-06-11 Time 08:30 Rev Time 0.00
Received By aaponte Date 2004-06-11 Time 08:30 Sent To  
Notes
***NONE***