Plan Review Stops For Permit 04050933 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
F |
Date |
2005-06-30 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2005-06-30 |
Time |
11:13 |
Rev Time |
0.50 |
Received By |
alange |
Date |
2005-06-30 |
Time |
11:13 |
Sent To |
|
|
Notes |
2005-06-30 00:00:00 | DENIED | | | | 1.PLANS SUBMITTED ARE NOT ORIGONALS. | | SUBMIT PLANS WITH ORIGONAL SEAL AND | | SIGNATURE. | | FAC 61G15-23, FS 471.025 | | | | ART LANGE | | BUILDING PLANS EXAMINER | | 805-6672 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
F |
Date |
2005-06-10 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2005-06-10 |
Time |
15:30 |
Rev Time |
0.50 |
Received By |
alange |
Date |
2005-06-10 |
Time |
15:30 |
Sent To |
|
|
Notes |
2005-06-10 00:00:00 | REVISION DENIED | | | | 1.SUBMIT TWO COPIES OF PRODUCT | | APPROVALS WITH QUALITY ASSURANCE FOR | | EXTERIOR DOOR. | | PRODUCT APPROVALS SUBMITTED WITH | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | SPECIFIC FORM PER RULE 9B-72. SEE | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | 2. REVISION PLANS SUBMITTED SHALL BE | | SIGNED AND SEALED BY THE ENGINEER OF | | RECORD.FBC 104.2.2 | | | | ART LANGE | | BUILDING PLANS EXAMINER | | 805-6672 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2005-02-14 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2005-02-14 |
Time |
15:57 |
Rev Time |
0.66 |
Received By |
alange |
Date |
2005-02-14 |
Time |
15:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2004-11-08 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2004-11-08 |
Time |
09:20 |
Rev Time |
1.00 |
Received By |
alange |
Date |
2004-11-08 |
Time |
09:20 |
Sent To |
|
|
Notes |
2004-11-08 00:00:00 | DENIED | | | | PRODUCT APPROVALS FOR THERMA-TRU EXT. | | DOORS IS FOR INSWING ONLY.SUBMIT 2 | | COPIES OF PRODUCT APPROVALS FOR AN OUT | | SWING DOOR. | | | | PRODUCT APPROVALS SUBMITTED WITH | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | SPECIFIC FORM PER RULE 9B-72. SEE | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | ART LANGE | | BUILDING PLANS EXAMINER | | 805-6672 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2004-10-15 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2004-10-15 |
Time |
09:03 |
Rev Time |
1.50 |
Received By |
alange |
Date |
2004-10-15 |
Time |
09:03 |
Sent To |
|
|
Notes |
2004-10-15 00:00:00 | DENIED | | | | ITEMS FROM LAST REVIEW: | | | | 3.PRODUCT APPROVALS ARE INCOMPLETE. | | NO PRODUCT APPROVALS SUBMITTED FOR | | IMPACT PROTECTION. | | BINNINGS PAN AMERICAN PA-9 MISSING STATE | | APPROVALS | | THERMA-TRU EXT DOOR MISSING PRODUCT | | APPROVALS. | | TRACO SH WINDOW 2100 SERIES DOES NOT | | HAVE THE CORRECT STATE APPROVAL PAGES. | | SIMPSON STRAPS AND TIE-DOWNS MISSING | | PRODUCT APPROVALS. | | PRODUCT APPROVALS SUBMITTED WITH | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | SPECIFIC FORM PER RULE 9B-72. SEE | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | 4. SAFTEY GLAZING REQUIRED AT TUB AREA. | | SHOW ON PLANSFBC2405.2.1 | | | | 6. BUILDING VALUATION IS TOO LOW BASED | | ON SBCCI BUIDING VALUATION DATA. | | 1767.8 X 76.96 = 136049 | | 82 X 41.6 = 3411 | | TOTAL $139,460 ADDITIONAL PERMIT FEES | | ARE DUE. | | | | 8. A-4 ELEVATIONS SHOW 3 SOUTH | | ELEVATIONS.A-3 PAGE NOT SUBMITTED. | | | | LOOK FOR COMMENTS BY THE OTHER PLAN | | REVIEW DISCIPLINES THAT MAY BE WRITTEN | | ON THE APPLICATION, PLANS, OR ATTACHED | | SEPARATELY. WHEN RESUBMITTING PLANS | | PLEASE CLEARLY INDICATE THE REVISION AND | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH | | THE PLANS WHEN RESUBMITTING PLANS. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR | | SPECIFICATION PAGE WHERE THE CHANGES CAN | | BE FOUND, WILL HELP TO EXPEDITE YOUR | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | ART LANGE | | BUILDING PLAN REVIEW | | TEL: (561)805-6672 | | FAX: (561)659-8026 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2004-07-27 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2004-07-27 |
Time |
09:52 |
Rev Time |
2.25 |
Received By |
alange |
Date |
2004-07-27 |
Time |
09:52 |
Sent To |
P |
|
Notes |
2004-07-27 00:00:00 | DENIED | | | | 1. BEFORE A PERMIT TO CONSTRUCT, MAY | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | SET OF PLANS MUST BE STAMPED BY THAT | | OFFICE, AND A COPY OF THE PAID RECEIPT | | ATTACHED TO THE PERMIT APPLICATION. | | PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | 2.PRODUCT APPROVAL FOR FRONT ENTRY | | DOOR MISSING. SUBMIT 2 COPIES. | | | | 3.PRODUCT APPROVALS FOR STRAPS AND TIE | | DOWNS MISSING.SUBMIT 2 COPIES | | PRODUCT APPROVALS SUBMITTED WITH | | PERMIT APPLICATION AFTER OCTOBER 1, | | 2003ARE REQUIRED TO COMPLY WITH THE | | FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | INFORMATIONPLEASE SEE THE STATE WEBSITE | | AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | SPECIFIC FORM PER RULE 9B-72. SEE | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | 4.SAFTEY GLAZING AT TUB SHALL COMPLY | | WITH FBC 2405.2.1. | | | | 5.SQUARE FOOTAGE NOT CORRECT. | | UNDER ROOF 66.207 X 30 = 1986.21SQ.FT. | | COV. ENTRY 6.124 X 15.417 = 94.41 SQ.FT. | | TOTAL A/C 1891.8 SQ. FT. | | | | 6. BUILDING VALUATION TO LOW BASED ON | | SBCCI BUILDING VALUATION DATA. | | A/C 1891.8 X $76.96 = $145,592 | | COV. ENTRY 94.41 X $41.60 = $3,927 | | REVISED VALUATION $149,519. | | ADDITIONAL PERMIT FEES OF | | | | 7.SMOKE DETECTORS SHALL COMPLY WITH | | FBC 905.2. | | | | 8.PAGE A/3 ELEVATIONS DON'T MATCH | | FLOOR PLAN.ALSO THERE ARE TO | | ELEVATIONS FOR THE SOUTH VIEW AND NO | | NORTH ELEVATION. | | | | 9.SUBMIT 2 COPIES OF ENERGY CALCS. | | | | 10.SHOW BUCK DETAIL COPLYING WITH | | FBC 1707.4.4.2 BUCKS SHALL EXTEND BEYOND | | THE INTERIOR OF FACE OF THE WINDOW OR | | DOOR FRAME SUCH THAT FULL SUPPORT OF | | THEFRAME IS PROVIDED. | | | | 11.SUBMIT 2 COPIES OF SOILS REPORT. | | | | 12.SEPERATE DEMO PERMIT OF EXISTING | | DWELLING REQUIRED. | | | | 13.FBC 11-11 A MINIMUM OF ONE BATHROOM | | DOOR SHALL HAVE A CLEAR OPENING OF | | 29" SHOW ON PLAN. | | | | LOOK FOR COMMENTS BY THE OTHER PLAN | | REVIEW DISCIPLINES THAT MAY BE WRITTEN | | ON THE APPLICATION, PLANS, OR ATTACHED | | SEPARATELY. WHEN RESUBMITTING PLANS | | PLEASE CLEARLY INDICATE THE REVISION AND | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH | | THE PLANS WHEN RESUBMITTING PLANS. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR | | SPECIFICATION PAGE WHERE THE CHANGES CAN | | BE FOUND, WILL HELP TO EXPEDITE YOUR | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | ART LANGE | | BUILDING PLAN REVIEW | | TEL: (561)805-6672 | | FAX: (561)659-8026 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
P |
Date |
2005-07-06 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-07-06 |
Time |
08:43 |
Rev Time |
0.25 |
Received By |
dpalmer |
Date |
2005-07-06 |
Time |
08:43 |
Sent To |
P |
|
Notes |
2005-07-06 00:00:00 | REV TO RELOCATE ELECT PANEL. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
F |
Date |
2005-06-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-06-21 |
Time |
09:07 |
Rev Time |
0.25 |
Received By |
dpalmer |
Date |
2005-06-21 |
Time |
09:07 |
Sent To |
M |
|
Notes |
2005-06-21 00:00:00 | ********** UNSAT ************* | | | | 1)NOTE: PLEASE SEE PLANS SUBMITTED ARE | | SEALED PHOTOCOPIES OF SIGNED, SEALED | | PLANS. | | PLEASE SEE ALL PLANS BY ENGINEER OF | | RECORD ARE TO BE ORIGINAL. PLEASE SEE | | FAC 61G15-23, FS 471.025. | | PLEASE SEE ONE SET OF PLANS HAS BEEN | | RETAINED AND MAY BE TURNED OVER TO THE | | FBPE'S. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2004-12-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-12-13 |
Time |
07:32 |
Rev Time |
0.25 |
Received By |
dpalmer |
Date |
2004-12-13 |
Time |
07:32 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2004-11-03 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-11-03 |
Time |
10:42 |
Rev Time |
1.25 |
Received By |
dpalmer |
Date |
2004-11-03 |
Time |
10:01 |
Sent To |
P |
|
Notes |
2004-11-03 00:00:00 | ********** UNSAT 3RD TIME ************ | | | | *** PLEASE SEE THE FOLLOWING COMMENTS | | PLANS STILL CONTAIN CORRECTIONS THAT | | NEED TO BE MADE THAT WERE ON PREVIOUS | | TWO REVIEWS. | | | | 1)NOTE: PLEASE SEE PANEL IS SHOWN IN | | KITCHEN ABOVE KITCHEN COUNTERSPACE. THIS | | IS NOT PERMITTED. PLEASE SEE 110.26 FOR | | MIN CLEARENCE REQUIREMENTS. | | PREVIOUS REVIEW** | | | | 2)NOTE: PLEASE SEE RECEPT/GFI SPACING | | ALONG KITCHEN COUNTERSPACE PER 210.52C1 | | *PREVIOUS TWO REVIEWS** | | | | 3)NOTE: PLEASE SEE DINING RM/LIVING ROOM | | STILL SHOWS #14 FOR REQUIRED 20A | | CIRCUIT(S) FOR DINING RM.210.52B1 | | **PREVIOUS TWO REVIEWS ** | | | | 4)NOTE:PLEASE SEE MISSING INFORMATION ON | | TITLE BLOCK AS REQUIRED UNDER FAC | | 61G15-23.002, FS 471 | | **PREVIOUS REVIEW ** | | | | 5)NOTE: PLEASE SEE A NEW RISER DIAGRAM | | IS NOW SUBMITTED AND IS NOW MISSING THE | | REQUIRED FOOTER STEEL AS PART OF THE | | G.E. SYSTEM. 250.50 | | | | *** PLEASE SEE ATTACHED COPY OF FS | | 553.80(2)(B).*** | | THIS REQUIRES ANY PLANS REVIEWED 3 OR | | MORE TIMES WITH ANY OF THE SAME | | COMMENTS | | SHALL HAVE A 4X FEE ACCESSED TO THE | | DESIGN PROFESSIONAL FOR THE PORTION OF | | PERMIT FEE ATTRIBUTED TO PLAN REVIEW. | | PLEASE SEE ATTACHED BZ #247610 | | $2,273.80 | | WHICH HAS NOW BEEN ADDED. PLEASE SEE | | THIS MUST BE PAID BEFORE PLANS ARE | | ALLOWED TO BE RE-SUBMITTED FOR NEXT | | REVIEW. | | **PLEASE ALSO SEE THAT ONE COPY OF EACH | | OF THE 3 SETS OF ELECTRICAL PLANS ARE | | NOW BEING REATINED FOR POSSIBLE REVIEW | | BY THE FBPE'S.***** | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2004-09-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-09-21 |
Time |
11:14 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2004-09-21 |
Time |
11:05 |
Sent To |
P |
|
Notes |
2004-09-21 00:00:00 | ********* UNSAT 2ND REVIEW ******** | | | | 1)NOTE: PLEASE SEE PANEL IS BEING SHOWN | | AS 150 MLO? NO MAIN SHOWN? 225.31 ETC. | | | | 2)NOTE: PLEASE SEE LOCATION OF PANEL IS | | SHOWN IN KITCHEN WHERE COUNTERSPACE IS? | | MUST MEET 110.26 | | | | 3)NOTE: PLEASE SEE NFPA-72 8-1.4.2 FOR | | LOCATION AND TYOE OF SD NEAR KITCHEN. | | | | 4 )NOTE: PLEASE SHOWS REQ'D DISC'S FOR | | A/C EQUIPMENT. PER 440.11 | | | | 5 )NOTE: PLEASE LIST THE REQ'D ARC | | FAULT PROTECTED CURCUIT(S) ON PANEL | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | IN BEDROOMS ARE TO BE PROTECTED , | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | 210.12 2002 NEC | | PLEASE ALSO SEE ELECTRICAL NOTES: | | MENTIONS SD'S TO BE ON WITH KIT LIGHTING | | CIRCUIT? SEE ABOVE. | | | | 6)NOTE: PLEASE SEE 210.52C1 FOR RECEPTS | | ALONG KITCHEN COUNTERSPACE. | | | | 7)NOTE: PLEASE SEE DINING RM RECEPT | | NOW SHOWN ON A 20A BRKR, YET STILL SHOWN | | W/ #14 AWG WHICH IS ONL RATED FOR 15A'S. | | PLEASE SEE 210.52B1 | | | | 8)NOTE: PLEASE CORRELATE RISER DIAGRAM | | AND PANEL. ONE SHOWS PANEL BEING A | | 30 CIRCUIT, THE OTHER 40 CIRCUITS?? | | | | 9)NOTE: PLEASE SEE FAC 61G15-23.002 FOR | | ALL INFORMATION REQUIRED ON TITLE BLOCK. | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | INSERT NEW REVISED SHEETS INTO SETS FOR | | REVIEW AND STAMPING. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2004-07-26 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-09-17 |
Time |
09:10 |
Rev Time |
0.75 |
Received By |
btrobaug |
Date |
2004-07-26 |
Time |
12:54 |
Sent To |
M |
|
Notes |
2004-07-26 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE AIC RATING MARKED IN THE PANEL IS | | 10000, AND 22000 NOTED ON PLAN, PLEASE | | CORRELATE. | | | | 2} PLEASE SHOW THE LOCATION OF THE | | SERVICE EQUIPMENT ON THE PLAN. | | | | 3} THE PANEL SCHEDULE CONTAINS THE | | FOLLOWING VIOLATIONS: | | A) DINING ROOM CIRCUIT ON 15 AMP CKT. | | MUST COMPLY WITH 210.52(B)(1). | | B) THE 15 AMP SMALL APPLIANCE (KITCHEN) | | MUST COMPLY WITH 210.11(C)(1), 20 AMP. | | C) THE BATH CIRCUITS MUST COMPLY WITH | | 210.11(C)(3). | | D) THE WASHER/DRYER IS LISTED AS A | | SINGLE UNIT BUT SHOWN AS SEPARATE | | UNITS. PLEASE CORRELATE AND ADJUST | | LOAD CALCULATIONS ACCORDINGLY. | | | | 4} THE BACK BATHROOM (WHICH DOES NOT | | APPEAR ON THE ARCHITECTURAL PLAN A-1) | | MUST HAVE A RECEPTACLE TO COMPLY WITH | | 210.52(D)., ALSO CORRELATE PLANS TO | | INDICATE IF THAT ROOM IS TO BE PART OF | | THIS PLAN. | | | | 5} THE RECEPTACLE SPACING IN THE | | DINING,AND BACK BEDROOM IS IN VIOLATION | | OF 210.52(A)(1). | | | | 6} THE KITCHEN RECEPTACLES MUST COMPLY | | WITH 210.52(C)(1) SPACING AND | | 210.8(A)(6) GFI. | | | | 7} SMOKE DETECTORS ARE REQUIRED PER 8-1. | | 4.1.6.2 NFPA-72. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
12 |
Status |
N |
Date |
2005-07-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-07-01 |
Time |
17:34 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-07-01 |
Time |
17:34 |
Sent To |
E |
|
Notes |
2005-07-01 00:00:00 | TO "DPALMER" DESK/REVISION |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
11 |
Status |
N |
Date |
2005-06-14 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2005-06-14 |
Time |
07:09 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2005-06-14 |
Time |
07:09 |
Sent To |
E |
|
Notes |
2005-06-14 00:00:00 | TO 'DP' DESK/REV. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
10 |
Status |
N |
Date |
2005-05-26 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-05-26 |
Time |
15:52 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-05-26 |
Time |
15:52 |
Sent To |
M |
|
Notes |
2005-05-26 00:00:00 | TO "PKRAUSS" BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
9 |
Status |
N |
Date |
2005-02-02 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-02-02 |
Time |
13:10 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-02-02 |
Time |
13:10 |
Sent To |
M |
|
Notes |
2005-02-02 00:00:00 | TO "M" BOX/RESUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
8 |
Status |
N |
Date |
2004-12-07 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2004-12-07 |
Time |
13:55 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2004-12-07 |
Time |
13:55 |
Sent To |
E |
|
Notes |
2004-12-07 00:00:00 | SESNT TO "DP" DESK. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2004-11-23 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2004-11-23 |
Time |
13:16 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2004-11-23 |
Time |
13:16 |
Sent To |
E |
|
Notes |
2004-11-23 00:00:00 | SENT TO "DP" DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2004-11-10 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-11-10 |
Time |
14:50 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-11-10 |
Time |
14:50 |
Sent To |
E |
|
Notes |
2004-11-10 00:00:00 | TO DP DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2004-11-01 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-11-01 |
Time |
|
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-11-01 |
Time |
08:58 |
Sent To |
E |
|
Notes |
2004-11-01 00:00:00 | TO DP DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2004-09-17 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-09-17 |
Time |
09:10 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-09-17 |
Time |
09:10 |
Sent To |
E |
|
Notes |
2004-09-17 00:00:00 | TO DP DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2004-07-26 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-07-26 |
Time |
09:27 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-07-26 |
Time |
09:26 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2004-07-21 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2004-07-23 |
Time |
13:03 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-07-21 |
Time |
09:30 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2004-05-20 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-05-20 |
Time |
14:11 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-05-20 |
Time |
14:11 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
7 |
Status |
P |
Date |
2005-07-18 |
|
|
Cont ID |
|
Sent By |
prafter |
Date |
2005-07-18 |
Time |
10:21 |
Rev Time |
0.75 |
Received By |
prafter |
Date |
2005-07-18 |
Time |
10:21 |
Sent To |
B |
|
Notes |
2005-07-18 00:00:00 | MECH. PLAN REVIEW. | | | | REF. HMOSER #6 REV. REFEARED TO ELECT. | | REV. PLANS NOT SIGNED AND SEALED,PLANS. | | PLANS NOW S/S 7/1/05. | | PAT RAFTER 561/805/6728. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
6 |
Status |
F |
Date |
2005-06-21 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2005-06-21 |
Time |
16:47 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2005-06-21 |
Time |
16:44 |
Sent To |
P |
|
Notes |
2005-06-21 00:00:00 | PLAN DENIED | | REFER TO ELECTRICAL PLAN REVIEW NOTES | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2005-05-28 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2005-05-28 |
Time |
11:22 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2005-05-28 |
Time |
10:59 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2005-02-08 |
|
|
Cont ID |
|
Sent By |
prafter |
Date |
2005-02-08 |
Time |
09:02 |
Rev Time |
1.00 |
Received By |
prafter |
Date |
2005-02-08 |
Time |
09:01 |
Sent To |
B |
|
Notes |
2005-02-08 00:00:00 | FOURTH RESUB. | | | | MANUAL (J) OK ,AND R/A OUT OF BEDROOMS | | REFLECTED ON PLANS. | | PAT RAFTER 2/8/05 561/805/6728. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2004-12-15 |
Time |
|
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2004-12-15 |
Time |
15:21 |
Sent To |
|
|
Notes |
2004-12-15 00:00:00 | PLAN DENIED | | REFER TO SECTION 601.4 BALANCED RETURN | | AIR,NEED ENERGY CALCULATIONS,AND MANUAL | | (J) | | PLAN REVIEW BY HAROLD MOSER | | (561)805-6732 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2004-10-08 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-10-08 |
Time |
09:59 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2004-10-08 |
Time |
08:32 |
Sent To |
|
|
Notes |
2004-10-08 00:00:00 | DENIED: | | 1.LOAD CALCULATIONS ARE TO BE IN | | ACCORDANCE WITH 2001 FBC CHAPTER 13 | | SUB-CHAPTER 600 METHOD A.CALCULATIONS | | SUBMITTED INDICATE FULL COMMERCIAL.PER | | FS 553.907, THE BUILDINGS OWNER, THE | | OWNERS ARCHITECT, OR OTHER AUTHORIZED | | AGENT LEGALLY DESIGNATED BY THE OWNER | | SHALL CERTIFY THAT THE BUILDING IS IN | | COMPLIANCE WITH THE CODE. | | | | 2.RETURN AIR TRANSFERS ARE NOT SIZED | | IN ACCORDANCE WITH 2001 FBC(M) 601.4, | | EXCEPTION 1 THROUGH 3.PLEASE SIZE THE | | FOLLOWING RETURN TRANSFERS AS FOLLOWS: | | 8" SUPPLY = 10" RETURN AIR JUMPER | | MASTER BEDROOM ALL AIR INTO THE SUITE | | SHALL BE INCLUDED. A MINIMUM OF 16" | | RETURN IS REQUIRED. | | | | 3. NON HABITABLE ROOMS LIKE THE LAUNDRY | | ROOM, ARE NOT REQUIRED TO HAVE A RETURN. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2004-08-02 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2004-10-06 |
Time |
07:51 |
Rev Time |
0.10 |
Received By |
pkrauss |
Date |
2004-08-02 |
Time |
14:32 |
Sent To |
|
|
Notes |
2004-08-02 00:00:00 | NO MECHANICAL PLANS OR CONTRACTOR | | INDICATED WITH PERMIT APPLICATION. | | PLEASE PROVIDE PLANS, ENERGY AND MANUAL | | J CALCULATIONS, AND EQUIPMENT SCHEDULE | | WITH MECHANICAL PERMIT APPLICATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
6 |
Status |
P |
Date |
2005-07-16 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2005-07-16 |
Time |
11:48 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2005-07-16 |
Time |
11:48 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
F |
Date |
2005-06-29 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2005-06-29 |
Time |
10:02 |
Rev Time |
0.25 |
Received By |
jleech |
Date |
2005-06-29 |
Time |
10:02 |
Sent To |
B |
|
Notes |
2005-06-29 00:00:00 | DENIED; | | SEE ELECTRICAL PLAN REVIEW NOTES. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2004-12-15 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2004-12-15 |
Time |
11:35 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2004-12-15 |
Time |
11:35 |
Sent To |
B1 |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2004-11-04 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2004-11-04 |
Time |
07:52 |
Rev Time |
0.33 |
Received By |
kstevens |
Date |
2004-11-04 |
Time |
07:52 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2004-10-06 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2004-10-06 |
Time |
07:50 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2004-10-06 |
Time |
07:50 |
Sent To |
M |
|
Notes |
2004-10-06 00:00:00 | SECTION 706.3 FITTINGS TO DIRECT THE | | SEWAGE & WASTE IN DIRECTION OF FLOW |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2004-07-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-09-21 |
Time |
11:14 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2004-07-27 |
Time |
16:47 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2004-12-15 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2004-12-15 |
Time |
16:33 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2004-12-15 |
Time |
16:33 |
Sent To |
B |
|
Notes |
2004-12-15 00:00:00 | PLANS GIVEN TO LUIS M |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2004-07-23 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2004-07-23 |
Time |
13:03 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2004-07-23 |
Time |
13:03 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2004-05-24 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-07-21 |
Time |
09:30 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2004-05-24 |
Time |
11:04 |
Sent To |
|
|
Notes |
2004-05-24 00:00:00 | DENIED, NO ACCESSARY DWELLING ALLOWED | | IN SF7.CALLED CONTR FILE S FOR P/U. | | CALLED OFFICE TWICE VOICE MAIL IS FULL, | | CALLED CELL # AND CANNOT BE CONNCECTED | | TO PHONE LINE. |
|
|