Plan Review Details - Permit 04050933
Plan Review Stops For Permit 04050933
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2005-06-30 Cont ID  
Sent By alange Date 2005-06-30 Time 11:13 Rev Time 0.50
Received By alange Date 2005-06-30 Time 11:13 Sent To  
Notes
2005-06-30 00:00:00DENIED
  
 1.PLANS SUBMITTED ARE NOT ORIGONALS.
 SUBMIT PLANS WITH ORIGONAL SEAL AND
 SIGNATURE.
 FAC 61G15-23, FS 471.025
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-06-10 Cont ID  
Sent By alange Date 2005-06-10 Time 15:30 Rev Time 0.50
Received By alange Date 2005-06-10 Time 15:30 Sent To  
Notes
2005-06-10 00:00:00REVISION DENIED
  
 1.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS WITH QUALITY ASSURANCE FOR
 EXTERIOR DOOR.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2. REVISION PLANS SUBMITTED SHALL BE
 SIGNED AND SEALED BY THE ENGINEER OF
 RECORD.FBC 104.2.2
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-02-14 Cont ID  
Sent By alange Date 2005-02-14 Time 15:57 Rev Time 0.66
Received By alange Date 2005-02-14 Time 15:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-11-08 Cont ID  
Sent By alange Date 2004-11-08 Time 09:20 Rev Time 1.00
Received By alange Date 2004-11-08 Time 09:20 Sent To  
Notes
2004-11-08 00:00:00DENIED
  
 PRODUCT APPROVALS FOR THERMA-TRU EXT.
 DOORS IS FOR INSWING ONLY.SUBMIT 2
 COPIES OF PRODUCT APPROVALS FOR AN OUT
 SWING DOOR.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-10-15 Cont ID  
Sent By alange Date 2004-10-15 Time 09:03 Rev Time 1.50
Received By alange Date 2004-10-15 Time 09:03 Sent To  
Notes
2004-10-15 00:00:00DENIED
  
 ITEMS FROM LAST REVIEW:
  
 3.PRODUCT APPROVALS ARE INCOMPLETE.
 NO PRODUCT APPROVALS SUBMITTED FOR
 IMPACT PROTECTION.
 BINNINGS PAN AMERICAN PA-9 MISSING STATE
 APPROVALS
 THERMA-TRU EXT DOOR MISSING PRODUCT
 APPROVALS.
 TRACO SH WINDOW 2100 SERIES DOES NOT
 HAVE THE CORRECT STATE APPROVAL PAGES.
 SIMPSON STRAPS AND TIE-DOWNS MISSING
 PRODUCT APPROVALS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4. SAFTEY GLAZING REQUIRED AT TUB AREA.
 SHOW ON PLANSFBC2405.2.1
  
 6. BUILDING VALUATION IS TOO LOW BASED
 ON SBCCI BUIDING VALUATION DATA.
 1767.8 X 76.96 = 136049
 82 X 41.6 = 3411
 TOTAL $139,460 ADDITIONAL PERMIT FEES
 ARE DUE.
  
 8. A-4 ELEVATIONS SHOW 3 SOUTH
 ELEVATIONS.A-3 PAGE NOT SUBMITTED.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 TEL: (561)805-6672
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-07-27 Cont ID  
Sent By alange Date 2004-07-27 Time 09:52 Rev Time 2.25
Received By alange Date 2004-07-27 Time 09:52 Sent To P
Notes
2004-07-27 00:00:00DENIED
  
 1. BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.PRODUCT APPROVAL FOR FRONT ENTRY
 DOOR MISSING. SUBMIT 2 COPIES.
  
 3.PRODUCT APPROVALS FOR STRAPS AND TIE
 DOWNS MISSING.SUBMIT 2 COPIES
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.SAFTEY GLAZING AT TUB SHALL COMPLY
 WITH FBC 2405.2.1.
  
 5.SQUARE FOOTAGE NOT CORRECT.
 UNDER ROOF 66.207 X 30 = 1986.21SQ.FT.
 COV. ENTRY 6.124 X 15.417 = 94.41 SQ.FT.
 TOTAL A/C 1891.8 SQ. FT.
  
 6. BUILDING VALUATION TO LOW BASED ON
 SBCCI BUILDING VALUATION DATA.
 A/C 1891.8 X $76.96 = $145,592
 COV. ENTRY 94.41 X $41.60 = $3,927
 REVISED VALUATION $149,519.
 ADDITIONAL PERMIT FEES OF
  
 7.SMOKE DETECTORS SHALL COMPLY WITH
 FBC 905.2.
  
 8.PAGE A/3 ELEVATIONS DON'T MATCH
 FLOOR PLAN.ALSO THERE ARE TO
 ELEVATIONS FOR THE SOUTH VIEW AND NO
 NORTH ELEVATION.
  
 9.SUBMIT 2 COPIES OF ENERGY CALCS.
  
 10.SHOW BUCK DETAIL COPLYING WITH
 FBC 1707.4.4.2 BUCKS SHALL EXTEND BEYOND
 THE INTERIOR OF FACE OF THE WINDOW OR
 DOOR FRAME SUCH THAT FULL SUPPORT OF
 THEFRAME IS PROVIDED.
  
 11.SUBMIT 2 COPIES OF SOILS REPORT.
  
 12.SEPERATE DEMO PERMIT OF EXISTING
 DWELLING REQUIRED.
  
 13.FBC 11-11 A MINIMUM OF ONE BATHROOM
 DOOR SHALL HAVE A CLEAR OPENING OF
 29" SHOW ON PLAN.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 TEL: (561)805-6672
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-07-06 Cont ID  
Sent By dpalmer Date 2005-07-06 Time 08:43 Rev Time 0.25
Received By dpalmer Date 2005-07-06 Time 08:43 Sent To P
Notes
2005-07-06 00:00:00REV TO RELOCATE ELECT PANEL.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2005-06-21 Cont ID  
Sent By dpalmer Date 2005-06-21 Time 09:07 Rev Time 0.25
Received By dpalmer Date 2005-06-21 Time 09:07 Sent To M
Notes
2005-06-21 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE SEE PLANS SUBMITTED ARE
 SEALED PHOTOCOPIES OF SIGNED, SEALED
 PLANS.
 PLEASE SEE ALL PLANS BY ENGINEER OF
 RECORD ARE TO BE ORIGINAL. PLEASE SEE
 FAC 61G15-23, FS 471.025.
 PLEASE SEE ONE SET OF PLANS HAS BEEN
 RETAINED AND MAY BE TURNED OVER TO THE
 FBPE'S.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-12-13 Cont ID  
Sent By dpalmer Date 2004-12-13 Time 07:32 Rev Time 0.25
Received By dpalmer Date 2004-12-13 Time 07:32 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-11-03 Cont ID  
Sent By csiegber Date 2004-11-03 Time 10:42 Rev Time 1.25
Received By dpalmer Date 2004-11-03 Time 10:01 Sent To P
Notes
2004-11-03 00:00:00********** UNSAT 3RD TIME ************
  
 *** PLEASE SEE THE FOLLOWING COMMENTS
 PLANS STILL CONTAIN CORRECTIONS THAT
 NEED TO BE MADE THAT WERE ON PREVIOUS
 TWO REVIEWS.
  
 1)NOTE: PLEASE SEE PANEL IS SHOWN IN
 KITCHEN ABOVE KITCHEN COUNTERSPACE. THIS
 IS NOT PERMITTED. PLEASE SEE 110.26 FOR
 MIN CLEARENCE REQUIREMENTS.
 PREVIOUS REVIEW**
  
 2)NOTE: PLEASE SEE RECEPT/GFI SPACING
 ALONG KITCHEN COUNTERSPACE PER 210.52C1
 *PREVIOUS TWO REVIEWS**
  
 3)NOTE: PLEASE SEE DINING RM/LIVING ROOM
 STILL SHOWS #14 FOR REQUIRED 20A
 CIRCUIT(S) FOR DINING RM.210.52B1
 **PREVIOUS TWO REVIEWS **
  
 4)NOTE:PLEASE SEE MISSING INFORMATION ON
 TITLE BLOCK AS REQUIRED UNDER FAC
 61G15-23.002, FS 471
 **PREVIOUS REVIEW **
  
 5)NOTE: PLEASE SEE A NEW RISER DIAGRAM
 IS NOW SUBMITTED AND IS NOW MISSING THE
 REQUIRED FOOTER STEEL AS PART OF THE
 G.E. SYSTEM. 250.50
  
 *** PLEASE SEE ATTACHED COPY OF FS
 553.80(2)(B).***
 THIS REQUIRES ANY PLANS REVIEWED 3 OR
 MORE TIMES WITH ANY OF THE SAME
 COMMENTS
 SHALL HAVE A 4X FEE ACCESSED TO THE
 DESIGN PROFESSIONAL FOR THE PORTION OF
 PERMIT FEE ATTRIBUTED TO PLAN REVIEW.
 PLEASE SEE ATTACHED BZ #247610
 $2,273.80
 WHICH HAS NOW BEEN ADDED. PLEASE SEE
 THIS MUST BE PAID BEFORE PLANS ARE
 ALLOWED TO BE RE-SUBMITTED FOR NEXT
 REVIEW.
 **PLEASE ALSO SEE THAT ONE COPY OF EACH
 OF THE 3 SETS OF ELECTRICAL PLANS ARE
 NOW BEING REATINED FOR POSSIBLE REVIEW
 BY THE FBPE'S.*****
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-09-21 Cont ID  
Sent By dpalmer Date 2004-09-21 Time 11:14 Rev Time 0.50
Received By dpalmer Date 2004-09-21 Time 11:05 Sent To P
Notes
2004-09-21 00:00:00********* UNSAT 2ND REVIEW ********
  
 1)NOTE: PLEASE SEE PANEL IS BEING SHOWN
 AS 150 MLO? NO MAIN SHOWN? 225.31 ETC.
  
 2)NOTE: PLEASE SEE LOCATION OF PANEL IS
 SHOWN IN KITCHEN WHERE COUNTERSPACE IS?
 MUST MEET 110.26
  
 3)NOTE: PLEASE SEE NFPA-72 8-1.4.2 FOR
 LOCATION AND TYOE OF SD NEAR KITCHEN.
  
 4 )NOTE: PLEASE SHOWS REQ'D DISC'S FOR
 A/C EQUIPMENT. PER 440.11
  
 5 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 210.12 2002 NEC
 PLEASE ALSO SEE ELECTRICAL NOTES:
 MENTIONS SD'S TO BE ON WITH KIT LIGHTING
 CIRCUIT? SEE ABOVE.
  
 6)NOTE: PLEASE SEE 210.52C1 FOR RECEPTS
 ALONG KITCHEN COUNTERSPACE.
  
 7)NOTE: PLEASE SEE DINING RM RECEPT
 NOW SHOWN ON A 20A BRKR, YET STILL SHOWN
 W/ #14 AWG WHICH IS ONL RATED FOR 15A'S.
 PLEASE SEE 210.52B1
  
 8)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANEL. ONE SHOWS PANEL BEING A
 30 CIRCUIT, THE OTHER 40 CIRCUITS??
  
 9)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 ALL INFORMATION REQUIRED ON TITLE BLOCK.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW REVISED SHEETS INTO SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-07-26 Cont ID  
Sent By csiegber Date 2004-09-17 Time 09:10 Rev Time 0.75
Received By btrobaug Date 2004-07-26 Time 12:54 Sent To M
Notes
2004-07-26 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE AIC RATING MARKED IN THE PANEL IS
 10000, AND 22000 NOTED ON PLAN, PLEASE
 CORRELATE.
  
 2} PLEASE SHOW THE LOCATION OF THE
 SERVICE EQUIPMENT ON THE PLAN.
  
 3} THE PANEL SCHEDULE CONTAINS THE
 FOLLOWING VIOLATIONS:
 A) DINING ROOM CIRCUIT ON 15 AMP CKT.
 MUST COMPLY WITH 210.52(B)(1).
 B) THE 15 AMP SMALL APPLIANCE (KITCHEN)
 MUST COMPLY WITH 210.11(C)(1), 20 AMP.
 C) THE BATH CIRCUITS MUST COMPLY WITH
 210.11(C)(3).
 D) THE WASHER/DRYER IS LISTED AS A
 SINGLE UNIT BUT SHOWN AS SEPARATE
 UNITS. PLEASE CORRELATE AND ADJUST
 LOAD CALCULATIONS ACCORDINGLY.
  
 4} THE BACK BATHROOM (WHICH DOES NOT
 APPEAR ON THE ARCHITECTURAL PLAN A-1)
 MUST HAVE A RECEPTACLE TO COMPLY WITH
 210.52(D)., ALSO CORRELATE PLANS TO
 INDICATE IF THAT ROOM IS TO BE PART OF
 THIS PLAN.
  
 5} THE RECEPTACLE SPACING IN THE
 DINING,AND BACK BEDROOM IS IN VIOLATION
 OF 210.52(A)(1).
  
 6} THE KITCHEN RECEPTACLES MUST COMPLY
 WITH 210.52(C)(1) SPACING AND
 210.8(A)(6) GFI.
  
 7} SMOKE DETECTORS ARE REQUIRED PER 8-1.
 4.1.6.2 NFPA-72.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-07-01 Cont ID  
Sent By adarroug Date 2005-07-01 Time 17:34 Rev Time 0.00
Received By adarroug Date 2005-07-01 Time 17:34 Sent To E
Notes
2005-07-01 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-06-14 Cont ID  
Sent By mjacobs Date 2005-06-14 Time 07:09 Rev Time 0.00
Received By mjacobs Date 2005-06-14 Time 07:09 Sent To E
Notes
2005-06-14 00:00:00TO 'DP' DESK/REV.

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-05-26 Cont ID  
Sent By adarroug Date 2005-05-26 Time 15:52 Rev Time 0.00
Received By adarroug Date 2005-05-26 Time 15:52 Sent To M
Notes
2005-05-26 00:00:00TO "PKRAUSS" BOX

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-02-02 Cont ID  
Sent By adarroug Date 2005-02-02 Time 13:10 Rev Time 0.00
Received By adarroug Date 2005-02-02 Time 13:10 Sent To M
Notes
2005-02-02 00:00:00TO "M" BOX/RESUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-12-07 Cont ID  
Sent By mjacobs Date 2004-12-07 Time 13:55 Rev Time 0.00
Received By mjacobs Date 2004-12-07 Time 13:55 Sent To E
Notes
2004-12-07 00:00:00SESNT TO "DP" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-11-23 Cont ID  
Sent By mjacobs Date 2004-11-23 Time 13:16 Rev Time 0.00
Received By mjacobs Date 2004-11-23 Time 13:16 Sent To E
Notes
2004-11-23 00:00:00SENT TO "DP" DESK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-11-10 Cont ID  
Sent By csiegber Date 2004-11-10 Time 14:50 Rev Time 0.00
Received By csiegber Date 2004-11-10 Time 14:50 Sent To E
Notes
2004-11-10 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-11-01 Cont ID  
Sent By csiegber Date 2004-11-01 Time   Rev Time 0.00
Received By csiegber Date 2004-11-01 Time 08:58 Sent To E
Notes
2004-11-01 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-09-17 Cont ID  
Sent By csiegber Date 2004-09-17 Time 09:10 Rev Time 0.00
Received By csiegber Date 2004-09-17 Time 09:10 Sent To E
Notes
2004-09-17 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-26 Cont ID  
Sent By csiegber Date 2004-07-26 Time 09:27 Rev Time 0.00
Received By csiegber Date 2004-07-26 Time 09:26 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-21 Cont ID  
Sent By mmclean Date 2004-07-23 Time 13:03 Rev Time 0.00
Received By csiegber Date 2004-07-21 Time 09:30 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-20 Cont ID  
Sent By csiegber Date 2004-05-20 Time 14:11 Rev Time 0.00
Received By csiegber Date 2004-05-20 Time 14:11 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2005-07-18 Cont ID  
Sent By prafter Date 2005-07-18 Time 10:21 Rev Time 0.75
Received By prafter Date 2005-07-18 Time 10:21 Sent To B
Notes
2005-07-18 00:00:00MECH. PLAN REVIEW.
  
 REF. HMOSER #6 REV. REFEARED TO ELECT.
 REV. PLANS NOT SIGNED AND SEALED,PLANS.
 PLANS NOW S/S 7/1/05.
 PAT RAFTER 561/805/6728.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2005-06-21 Cont ID  
Sent By hmoser Date 2005-06-21 Time 16:47 Rev Time 0.00
Received By hmoser Date 2005-06-21 Time 16:44 Sent To P
Notes
2005-06-21 00:00:00PLAN DENIED
 REFER TO ELECTRICAL PLAN REVIEW NOTES
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2005-05-28 Cont ID  
Sent By hmoser Date 2005-05-28 Time 11:22 Rev Time 0.00
Received By hmoser Date 2005-05-28 Time 10:59 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-02-08 Cont ID  
Sent By prafter Date 2005-02-08 Time 09:02 Rev Time 1.00
Received By prafter Date 2005-02-08 Time 09:01 Sent To B
Notes
2005-02-08 00:00:00FOURTH RESUB.
  
 MANUAL (J) OK ,AND R/A OUT OF BEDROOMS
 REFLECTED ON PLANS.
 PAT RAFTER 2/8/05 561/805/6728.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2004-12-15 Time   Rev Time 0.00
Received By hmoser Date 2004-12-15 Time 15:21 Sent To  
Notes
2004-12-15 00:00:00PLAN DENIED
 REFER TO SECTION 601.4 BALANCED RETURN
 AIR,NEED ENERGY CALCULATIONS,AND MANUAL
 (J)
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-10-08 Cont ID  
Sent By pkrauss Date 2004-10-08 Time 09:59 Rev Time 0.00
Received By pkrauss Date 2004-10-08 Time 08:32 Sent To  
Notes
2004-10-08 00:00:00DENIED:
 1.LOAD CALCULATIONS ARE TO BE IN
 ACCORDANCE WITH 2001 FBC CHAPTER 13
 SUB-CHAPTER 600 METHOD A.CALCULATIONS
 SUBMITTED INDICATE FULL COMMERCIAL.PER
 FS 553.907, THE BUILDINGS OWNER, THE
 OWNERS ARCHITECT, OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER
 SHALL CERTIFY THAT THE BUILDING IS IN
 COMPLIANCE WITH THE CODE.
  
 2.RETURN AIR TRANSFERS ARE NOT SIZED
 IN ACCORDANCE WITH 2001 FBC(M) 601.4,
 EXCEPTION 1 THROUGH 3.PLEASE SIZE THE
 FOLLOWING RETURN TRANSFERS AS FOLLOWS:
 8" SUPPLY = 10" RETURN AIR JUMPER
 MASTER BEDROOM ALL AIR INTO THE SUITE
 SHALL BE INCLUDED. A MINIMUM OF 16"
 RETURN IS REQUIRED.
  
 3. NON HABITABLE ROOMS LIKE THE LAUNDRY
 ROOM, ARE NOT REQUIRED TO HAVE A RETURN.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-08-02 Cont ID  
Sent By kstevens Date 2004-10-06 Time 07:51 Rev Time 0.10
Received By pkrauss Date 2004-08-02 Time 14:32 Sent To  
Notes
2004-08-02 00:00:00NO MECHANICAL PLANS OR CONTRACTOR
 INDICATED WITH PERMIT APPLICATION.
 PLEASE PROVIDE PLANS, ENERGY AND MANUAL
 J CALCULATIONS, AND EQUIPMENT SCHEDULE
 WITH MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 6 Status P Date 2005-07-16 Cont ID  
Sent By pschmitz Date 2005-07-16 Time 11:48 Rev Time 0.00
Received By pschmitz Date 2005-07-16 Time 11:48 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2005-06-29 Cont ID  
Sent By jleech Date 2005-06-29 Time 10:02 Rev Time 0.25
Received By jleech Date 2005-06-29 Time 10:02 Sent To B
Notes
2005-06-29 00:00:00DENIED;
 SEE ELECTRICAL PLAN REVIEW NOTES.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-12-15 Cont ID  
Sent By kstevens Date 2004-12-15 Time 11:35 Rev Time 0.50
Received By kstevens Date 2004-12-15 Time 11:35 Sent To B1
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-11-04 Cont ID  
Sent By kstevens Date 2004-11-04 Time 07:52 Rev Time 0.33
Received By kstevens Date 2004-11-04 Time 07:52 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-10-06 Cont ID  
Sent By kstevens Date 2004-10-06 Time 07:50 Rev Time 0.50
Received By kstevens Date 2004-10-06 Time 07:50 Sent To M
Notes
2004-10-06 00:00:00SECTION 706.3 FITTINGS TO DIRECT THE
 SEWAGE & WASTE IN DIRECTION OF FLOW

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-07-27 Cont ID  
Sent By dpalmer Date 2004-09-21 Time 11:14 Rev Time 0.33
Received By jleech Date 2004-07-27 Time 16:47 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2004-12-15 Cont ID  
Sent By mmclean Date 2004-12-15 Time 16:33 Rev Time 0.00
Received By mmclean Date 2004-12-15 Time 16:33 Sent To B
Notes
2004-12-15 00:00:00PLANS GIVEN TO LUIS M

Review Stop Z ZONING
Rev No 2 Status P Date 2004-07-23 Cont ID  
Sent By mmclean Date 2004-07-23 Time 13:03 Rev Time 0.00
Received By mmclean Date 2004-07-23 Time 13:03 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-05-24 Cont ID  
Sent By csiegber Date 2004-07-21 Time 09:30 Rev Time 0.00
Received By mmclean Date 2004-05-24 Time 11:04 Sent To  
Notes
2004-05-24 00:00:00DENIED, NO ACCESSARY DWELLING ALLOWED
 IN SF7.CALLED CONTR FILE S FOR P/U.
 CALLED OFFICE TWICE VOICE MAIL IS FULL,
 CALLED CELL # AND CANNOT BE CONNCECTED
 TO PHONE LINE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved