Plan Review Details - Permit 04050860
Plan Review Stops For Permit 04050860
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2005-04-07 Cont ID  
Sent By shill Date 2005-04-07 Time 15:37 Rev Time 1.00
Received By shill Date 2005-04-07 Time 15:37 Sent To PC
Notes
2005-04-07 00:00:00RESTAMP

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-01-28 Cont ID  
Sent By shill Date 2005-01-28 Time 14:59 Rev Time 1.00
Received By shill Date 2005-01-28 Time 14:59 Sent To  
Notes
2005-01-28 00:00:00IMPACT FEES PAID PR05002874

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-01-28 Cont ID  
Sent By shill Date 2005-01-28 Time 13:32 Rev Time 1.00
Received By shill Date 2005-01-28 Time 13:29 Sent To  
Notes
2005-01-28 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PROVIDE THE IMPACT FEE RECEIPT.
  
 2.)THE PRODUCT APPROVAL PROVIDED IS
 FOR SMALL MISSILE IMPACT ONLY.LARGE
 MISSILE IMPACT IS REQUIRED
 FBC1606.1.4(1).IF PRODUCT APPROVALS
 ARE NOT SUBMITTED BEFORE THE REVISION IS
 ISSUED, A SEPARATE PERMIT FOR THE
 SLIDING GLASS DOORS WILL BE REQUIRED.
  
 ***NO RESUB FEE FOR BUILDING COMMENTS -
 IMPACT FEE ONLY***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-12-03 Cont ID  
Sent By shill Date 2004-12-03 Time 10:28 Rev Time 0.00
Received By shill Date 2004-12-03 Time 10:27 Sent To PC
Notes
2004-12-03 00:00:00****CORRECTIONS****
 REVISION DATED 10/26/04
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)REVISE IMPACT FEE REVIEW; APPROVED
 FOR 2823 SF AND NEW ADDITION AREA IS NOW
 2953.233-5025
  
 2.)SHEET 2, BALCONY "HANDRAIL" IS A
 GUARDRAIL TO COMPLY WITH FBC1608.2.2.1
 THROUGH 1608.2.2.4.
  
 3.)PROVIDE DESIGN CRITERIA (LIVE LOAD)
 FOR THE BALCONY FBC TABLE 1604.1.
  
 4.)SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR THE SLIDING GLASS DOORS.
  
 5.)PROVIDE A SOILS INVESTIGATION
 REPORT.ONE WAS REQUESTED 1ST AND 2ND
 REVIEW BUT WAS WAIVED DUE TO MINIMAL
 FOUNDATION WORK.YOU ARE NOW ADDING A
 SECOND STORY AND NEW FOOTINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-08-18 Cont ID  
Sent By alange Date 2004-08-18 Time 10:44 Rev Time 0.50
Received By alange Date 2004-08-18 Time 10:44 Sent To  
Notes
2004-08-18 00:00:00OK TO ISSUE PER LM

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-07-27 Cont ID  
Sent By shill Date 2004-08-10 Time 08:35 Rev Time 3.00
Received By shill Date 2004-07-26 Time 16:52 Sent To  
Notes
2004-07-26 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST, ITEM #12, FBC
 1006.2.4 "EXTERIOR STAIRS SHALL BE
 SEPARATED FROM THE INTERIOR OF THE
 BUILDING BY WALLS WITH A FIRE RESISTANCE
 RATING OF NOT LESS THAN 1 HOUR . . ."
 FIRE RESISTANCE RATING FOR THE EXISTING
 WALLS WAS NOT CLEAR FROM THE PLAN.
 THE ENERGY CALCS SPECIFY FRAME EXTERIOR
 WALLS WITH A 24" SPACING; FBC TABLE
 709.6.2B ASSIGNS FIRE RESISTANCE TO
 FRAME WALLS WITH 16" SPACING ONLY.
 PROVIDE EITHER CALCULATED FIRE
 RESISTANCE RATING CHAPTER 7 OR ASSEMBLY
 LISTING.
  
 2.)THE INFILL DETAIL ALSO DOES NOT
 DEMONSTRATE COMPLIANCE.1 HR REQUIRED.
  
 3.)SEE PREVIOUS LIST, ITEM #13.
 ALTHOUGH IT IS CLEAR THAT THE STAIR IS
 OPEN, THE USABLE STILL UNDER THE STAIR
 STILL MUST COMPLY (1 HR). NONCOMBUSTIBLE
 MATERIALS DOES NOT COMPLY; USE OF
 NONCOMBUSTIBLE MATERIALS DO NOT
 CONSTITUTE A 1 HR ASSEMBLY.ALSO, YOU
 ARE STATING THAT THIS IS NONCOMBUSTIBLE;
 ISN'T THE ROOF FRAMING WOOD?SHEATHING?
  
 4.)THE FILE ROOM DOOR APPEARS TO ALSO
 BE WITHIN 10' OF THE STAIR.SHOW AS
 A PROTECTED OPENING ON THE PLAN, SUBMIT
 PRODUCT APPROVAL AND FIRE RATING
 INFORMATION FOR THIS EXTERIOR OPENING.
  
 5.)THE PREVIOUS LIST INCLUDED
 CORRECTIONS IN REGARDS TO THE RAMP
 (ITEMS 8 AND 9).THIS INDICATES THAT
 IT WAS NOT CODE COMPLIANT ON THE
 ORIGINAL SET OF PLANS, AND ARE CODE
 COMPLIANT ON THE REVISED SET OF PLANS,
 BUT IS NOT CLOUDED.PLEASE ALWAYS
 CLEARLY INDICATE ALL CHANGES AND SUBMIT
 OLD SHEETS.
  
 6.)REVISE THE SITE PLAN TO REFLECT
 CHANGES MADE TO THE RAMP.
  
 7.)SEPARATE PERMITS REQUIRED.
  
 8.)LOUNGE SINK DOES NOT SHOW
 COMPLIANCE WITH FBC11-4.24.3, 11-4.24.4.
  
 9.)IN REGARDS TO THE AFFIDAVIT FOR THE
 FLOORS, PLEASE REVISE TO CLEARLY
 INDICATE THAT BOTH OF THE FLOORS (1ST
 AND 2ND FLOOR) ARE INCLUDED IN THIS
 AFFIDAVIT (STATES "FLOOR SYSTEM"; WHICH
 ONE?BOTH MUST BE CERTIFIED.)ALSO
 BE ADVISED THAT YOU ARE CERTIFYING THE
 FLOORS BASED ON AN INSPECTION PERFORMED
 BY A PERSON NOT LICENSED TO DO DESIGN
 OR TO MAKE STRUCTURAL DETERMINATIONS.
 PLEASE STATE THE LOADS WHICH IN THE
 LETTER ARE REFERRED TO BY CODE SECTION.
 SUBMIT TWO COPIES; REQUIRED TO BE
 SEALED AND INCLUDE A TITLE BLOCK.
  
 10.) SEE PREVIOUS LIST, ITEM 19, THE
 INTERIOR STAIRS ALSO ARE REQUIRED TO
 HAVE A HANDRAIL ON BOTH SIDES.
  
 11.) IN REGARDS TO THE PREVIOUS LIST,
 ITEM #22 WAS A TYPO; SHOULD READ "TO
 COMPLY WITH FBC1804.6.3.1."PLEASE
 ADDRESS AT THIS TIME.
  
 12.)SEE PREVIOUS LIST, ITEM #20.
 THIS IS AN AREA WHERE SOILS ARE
 REQUIRED.ALTHOUGH YOU STATE THAT THE
 FOUNDATION WORK IS MINIMAL, SOILS ARE
 STILL REQUIRED AS FOUNDATION WORK IS
 BEING PERFORMED.
  
 13.)TEST REPORTS FOR THE GAF RUBBEROID
 WERE NOT SUBMITTED, BUT FLORIDA STATE
 PRODUCT APPROVALS WERE SUBMITTED. PLEASE
 PROVIDE TWO COPIES OF THE TEST REPORT.
  
 14.) PROVIDE STATE PAS AND TEST REPORTS
 FOR THE PGT FIXED GLASS WINDOW.
  
 15.) SEE ATTACHED NOTICE IN REGARDS TO
 FS553.80(2)(B).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-10 Cont ID  
Sent By csiegber Date 2004-07-22 Time 16:30 Rev Time 3.00
Received By shill Date 2004-06-09 Time 12:27 Sent To  
Notes
2004-06-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE NOTICE OF COMMENCEMENT IS
 EXPIRED (OVER 90 DAYS WITHOUT
 COMMENCING WORK), FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY (CHANGE OF USE).THE
 PLANS MUST BE STAMPED AND THE RECEIPT
 ATTACHED TO THE APPLICATION.233-5025
  
 3.)PROVIDE A COPY OF THE SURVEY FOR
 THIS PROPERTY.
  
 4.)SEPARATE PERMITS REQUIRED.
  
 5.)RENOVATED BUILDINGS ARE REQUIRED
 TO COMPLY WITH FBC12-101.1.3, FORM
 400D OR WITH METHOD B SUBCHAPTER 4.
  
 6.)PROVIDE TEST REPORTS AND FLORIDA
 STATEWIDE, LOCAL OR SITE SPECIFIC
 PRODUCT APPROVALS FOR THE FOLLOWING:
 FIXED GLASS WINDOW
 SINGLE HUNG WINDOW
 IMPACT PROTECTION
 DOOR
 ROOF
 ANY OTHER PRODUCT APPROVALS AS REQUIRED.
  
 7.)SHEET 2, WIND DESIGN INFORMATION
 INDICATES A HEIGHT OF 15' WHICH
 CONFLICTS WITH THE PLAN.
  
 8.)11-4.8.4.(2) LANDINGS. ALL LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARANCE.
  
 9.)11-4.8.4(3) IF RAMPS CHANGE DIREC-
 TION AT LANDINGS, THE MINIMUM LANDING
 SIZE SHALL BE 60" X 60".
  
 10.) THE FIRST FLOOR TOILET DOOR
 ENCROACHES UPON THE CLEAR FLOOR SPACE
 REQUIRED BY FBC11-4.19.3, FBC11-4.23.2.
 THIS DOOR US TO COMPLY WITH FBC1012.1.4.
 SHOW THE REQUIRED FLOOR SPACE, TO SCALE,
 ON THE FLOOR PLAN.
  
 11.)THE 2ND FLOOR TOILET DOOR DOES NOT
 COMPLY WITH FBC1012.1.4.
  
 12.)IT APPEARS THAT THE NEW STAIRS
 IS THE MAIN EGRESS FOR THE 2ND FLOOR.
 THIS STAIR IS TO COMPLY WITH FBC1006.
 2.4.SHOW HOW THIS 1 HR PROTECTION IS
 OBTAINED.INDICATE ALL OPENINGS
 REQUIRED TO BE PROTECTED ON THE PLAN.
  
 13.)FBC1006.1.4, THERE IS TO BE NO
 USABLE SPACE UNDER THE STAIR UNLESS
 PROTECTED BY THE SAME FIRE RESISTANCE AS
 THE EXIT ENCLOSURE (MIN. 1 HR).
  
 14.)THE LOUNGE DOOR LACKS THE
 MANUEVERING CLEARANCE REQUIRED BY
 FBC11-4.13-6 AND FBC 11-FIGURE 25(A).
  
 15.)THE LOUNGE SINK IS TO COMPLY WITH
 FBC11-4.24.
  
 16.)PROVIDE AN AFFIDAVIT CERTIFYING
 THE FLOOR LOADING, CITY OF WEST PALM
 BEACH AMENDMENTS TO THE FBC104.3.2,
 FBC TABLE 1604.1.
  
 17.)THE EXTERIOR STAIR RAILING SERVES
 AS A GUARDRAIL AS WELL AS A HANDRAIL,
 TO COMPLY WITH FBC1608.2.2, FBC1608.2.1,
 FBC1007.5, FBC1015.ALL HANDRAILS TO
 COMPLY WITH FBC1608.2.1.
  
 18.)EDGE PROTECTION REQUIRED FOR THE
 RAMP, FBC1013.8.
  
 19.)HANDRAILS REQUIRED ON BOTH SIDES
 OF THE STAIRS, FBC1007.5.2.
  
 20.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 21.)HANDRAIL FOR THE STAIRS ARE TO
 COMPLY WITH FBC11-4.9.4(2), FBC FIGURE
 19(C).
  
 22.)CRAWL SPACE IS TO COMPLY WITH
 FBC1804.6.1
  
 22.)WHEN RESUBMITTING, PLEASE SUBMIT
 A TRANSMITTAL LETTER EXPLAINING HOW
 EACH ITEM WAS ADDRESSED.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-03-21 Cont ID  
Sent By dpalmer Date 2006-03-21 Time 18:12 Rev Time 0.00
Received By dpalmer Date 2006-03-21 Time 18:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-03-17 Cont ID  
Sent By dpalmer Date 2006-03-17 Time 08:01 Rev Time 0.00
Received By dpalmer Date 2006-03-17 Time 07:14 Sent To  
Notes
2006-03-17 00:00:00*********** UNSAT ****************
  
 1)NOTE: PLEASE SEE SEC'S AND FEEDERS
 AHVE NOW BEEN DECREASED WHICH ARE NOT
 RATED FOR THE OCP AS SHOWNA OR THE SIZE
 OF SERVICE. ORIG PLANS INDICATED A 200A
 SERVICE, THEN THE REVISED PLANS IN JAN
 05 INDICATED A 225A SERVICE WHICH THE
 SEC'S AND FEEDER WERE INCREASED.
 PLEASE SEE 310.16 FOR COMMERCIAL USE
 WHICH REQUIRES THESE CONDUCTORS TO BE
 INCREASED.
 310.16,240.4, ETC
  
 2) NOTE: DUE TO THE INCREASEOF SERVICE
 ENTRANCE CONDUCTORS, THE PLANS WERE
 REDLINED ON JAN 24,2005 TO INCREASE THE
 GROUNDING ELECTRODE CONDUCTOR. THISWAS
 NOT DONE AND STILL SHOWS A GROUNDING
 ELECTRODE TOO SMALL.
 #2 MIN).250.66, 250.50,250.52
  
 3)NOTE: PLEASE COMPLETE ALL CIRCUTING ON
 PLANS AND CORRELATE W/ THE SUBMITTED
 PANEL SCHEDULE.
 PLEASE SEE 700.12E FOR EM/EXT.
  
 4)NOTE: PLEASEBE SURE TO GO OVER PLANS
 AND MAKE SURE ALL CIRCUITS CORRELATE.
 PLEASE SEE RECEPT IN BATH ON LT CIRCUIT.
 PLEASE SEE RECEPT ON LT CIRCUIT ON A
 DIFFERENT FLR.
  
 MOST OF THE ABOVE AREAS HAVEBEEN
 REDLINED, HOWEVER THIS IN NO WAY
 INCLUDES ALL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-01-24 Cont ID  
Sent By dpalmer Date 2005-01-24 Time 13:45 Rev Time 0.30
Received By dpalmer Date 2005-01-24 Time 13:45 Sent To  
Notes
2005-01-24 00:00:00NOTE REDLINED.
  
 SEC'S HAVE NOW INCREASED DUE TO SIZE OF
 SERVICE INCREASING.
 PLEASE SEE 250.66 FOR MIN GEC. (#2 MIN).

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-11-17 Cont ID  
Sent By dpalmer Date 2004-11-17 Time 15:17 Rev Time 0.60
Received By dpalmer Date 2004-11-17 Time 15:17 Sent To  
Notes
2004-11-17 00:00:00******* UNSAT **********
  
 1)NOTE: PLEASE SEE THERE ARE NUMEROUS
 ITEMS ON PANEL SCHEDULE WHICH HAVE BEEN
 ADDED OR LOADS INCREASE YET, LOAD HAS
 GONE DOWN FROM PREVIOUS PLANS?? HOW IS
 THIS POSSIBLE?
 PLEASE SEE INCREASED A/C LOAD.
 PLEASE SEE ADDED RECEPT LOAD/LT, GARBAGE
 DISP ETC.
  
 2)NOTE: PLEASE ALSO SEE LOADING OF SOME
 RECEPT CIRCUITS. 1920 W MAX ON A 20A
 BRANCH CIRCUIT.
 PLEASE SEE 220.13 FOR 180VA FOR EACH
 RECEPT.
 SEE #22,24,,,
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
  
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-07-19 Cont ID  
Sent By dpalmer Date 2004-07-19 Time 08:53 Rev Time 0.33
Received By dpalmer Date 2004-07-19 Time 08:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-28 Cont ID  
Sent By dpalmer Date 2004-05-28 Time 14:35 Rev Time 1.00
Received By dpalmer Date 2004-05-28 Time 14:34 Sent To  
Notes
2004-05-28 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SEE BLDG IS SHOWN AS A
 CHANGE OF OCCUPANCY FROM RESIDENCE TO
 COMMERCIAL OFFICE BLDG.
 PLEASE ADJUST PLANS ACCORD.
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE.
  
 3)NOTE: PLEASE SEE NEC 220 FOR LOAD
 PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 4)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM/ EXT LTS.
 PLEASE SEE FIRE REVIEW COMMENTS FOR
 EM/EXT LTS.
  
 5)NOTE: PLEASE SEE OCP SHOWN FOR AHU'S
 DO NOT SEEM TO CORRELATE TO NEC 424.3B
 PLEASE VERIFY KW LOAD AND OCP.
  
 6)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO PANEL.
 250.110,250.122,250.24
  
 7)NOTE: PLEASE CORRELATE RISER WITH
 PANEL, ONE SHOWS PANEL BEING MCB, OTHER
 SHOWS MLO??
  
 8)NOTE: PLEASE SEE SEC'S SHOWN AS 1/0'S
 PLEASE SEE 310.16 FOR MIN SEC'S FOR A
 200A SERVICE.
  
 9)NOTE: PLEASE SEE 210.70/210.63 FOR
 AHU WHICH APPEARS TO BE IN AN ATTIC??
  
 10)NOTE: PLEASE SEE FS 481.221 WHICH
 REQUIRES A SIGNATURE FOR ARCH.
 PLEASE SEE THAT PLANS APPEAR TO AN
 INITIAL FOR FIRST NAME.
 IF THIS IS LEGAL "SIGNATURE", PLEASE
 PROVIDE A SIGNED, DATED AND SEALED
 NOTARIZED LETTER STATING THIS IS LEGAL
 SIGNATURE. WE CAN THEN PLACE THIS IN
 A SIGNATURE FILE FOR FUTURE REFERENCE
 DUE TO ISSUES WE HAVE ENCOUNTERED WITH
 MORE THAN ONE "SIGNATURE" FOR INDIVIDUAL
 'S ON PLANS BEING SUBMITTED TO CITY OF
 WEST PALM BEACH. WE ARE REQUIRING
 "SIGNATURE" VERIFICATION FOR FILE.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 INCLUDING IMPACT FEES FOR PALM BEACH
 COUNTY.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO SETS FOR
 REVIEW AND STAMPING. ONE SET OF OLD
 SHEETS MAY BE SUBMITTED FOR REFERENCE
 FOR SOME REVIEWS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-02-16 Cont ID  
Sent By nmccray Date 2005-02-16 Time 16:18 Rev Time 0.00
Received By nmccray Date 2005-02-16 Time 16:18 Sent To  
Notes
2005-02-16 00:00:00REVISION DATED 12-27-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-12-02 Cont ID  
Sent By nmccray Date 2004-12-02 Time 14:41 Rev Time 0.00
Received By nmccray Date 2004-12-02 Time 14:41 Sent To  
Notes
2004-12-02 00:00:00REVISION DATED 10-26-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-07-13 Cont ID  
Sent By nmccray Date 2004-07-13 Time 15:25 Rev Time 0.00
Received By nmccray Date 2004-07-13 Time 15:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-05-20 Cont ID  
Sent By mcarsill Date 2004-05-20 Time 10:18 Rev Time 0.00
Received By mcarsill Date 2004-05-20 Time 10:18 Sent To  
Notes
2004-05-20 00:00:001) ALL NEW STAIRS AND RAMPS SHALL HAVE
 HANDRAILS ON BOTH SIDES.
  
 2) BUILDING ADDRESS IS REQUIRED. A
 MINIMUM OF 6" HIGH NUMBERS ARE
 REQUIRED.
  
 3) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 4) NO INFORMATION PROVIDED ABOUT
 PORTABLE FIRE EXTINGUISHERS.
  
 5) PLEASE EXPLAIN EXITING RATIONALE
 FROM SECOND FLOOR. ALSO PLEASE IDENTIFY
 ALL OPENINGS WITHIN 10 FEET OF THE
 STAIRS BOTH VERTICALLY AND HORIZONTALLY.
  
 6) PLEASE INDICATE TOTAL OCCUPANT LOAD
 FOR BOTH THE FIRST AND SECOND FLOOR.
  
 7) HOW WILL THE NEW PRE-FAB STAIRS BE
 SLIP RESISTANT.
  
 8) PLEASE INDICATE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR HANDRAILS
 AND GUARDRAILS.
  
 9) NO EMERGENCY LIGHTS OR EXIT SIGNS
 SHOWN ON SECOND FLOOR POWER PLAN.
 PLEASE REVISE AS NECESSARY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-02-19 Cont ID  
Sent By adarroug Date 2006-02-19 Time 12:17 Rev Time 0.00
Received By adarroug Date 2006-02-19 Time 12:17 Sent To  
Notes
2006-02-19 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-01-20 Cont ID  
Sent By mjacobs Date 2005-01-20 Time 10:35 Rev Time 0.00
Received By mjacobs Date 2005-01-20 Time 10:35 Sent To  
Notes
2005-01-20 00:00:00TO "COMM BD#21"/REV.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-11-04 Cont ID  
Sent By csiegber Date 2004-11-04 Time 13:59 Rev Time 0.00
Received By csiegber Date 2004-11-04 Time 13:59 Sent To  
Notes
2004-11-04 00:00:00TO COMM BD#51/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-08-10 Cont ID  
Sent By shill Date 2004-08-10 Time 08:35 Rev Time 0.00
Received By shill Date 2004-08-10 Time 08:35 Sent To B
Notes
2004-08-10 00:00:00TO LM DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-08-05 Cont ID  
Sent By csiegber Date 2004-08-05 Time 16:12 Rev Time 0.00
Received By csiegber Date 2004-08-05 Time 16:12 Sent To  
Notes
2004-08-05 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-22 Cont ID  
Sent By csiegber Date 2004-07-22 Time 16:30 Rev Time 0.00
Received By csiegber Date 2004-07-22 Time 16:30 Sent To B
Notes
2004-07-22 00:00:00TO SH DESK/PA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-12 Cont ID  
Sent By csiegber Date 2004-07-12 Time 16:21 Rev Time 0.00
Received By csiegber Date 2004-07-12 Time 16:21 Sent To  
Notes
2004-07-12 00:00:00TO COMM BD#27

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-20 Cont ID  
Sent By csiegber Date 2004-05-20 Time 09:27 Rev Time 0.00
Received By csiegber Date 2004-05-20 Time 09:27 Sent To  
Notes
2004-05-20 00:00:00TO COMM BD#7

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-01-24 Cont ID  
Sent By pkrauss Date 2005-01-24 Time 07:06 Rev Time 0.40
Received By pkrauss Date 2005-01-24 Time 06:53 Sent To  
Notes
2005-01-24 00:00:00PROVISO:
 PLAN SHEET 5 OF 6 GROUND FLOOR, A/C
 CLOSET INDICATES LOUVERED DOOR, PLEASE
 NOTE, IF THE MECHANICAL CLOSET IS A FREE
 RETURN, THE LOUVERED DOOR SHALL BE NON
 COMBUSTIBLE.2001 FBC(M)602.2.1 AND
 603.9.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2004-11-30 Cont ID  
Sent By pkrauss Date 2004-11-30 Time 14:24 Rev Time 0.40
Received By pkrauss Date 2004-11-30 Time 14:03 Sent To  
Notes
2004-11-30 00:00:00DENIED:
 1.RETURN AIR FROM THE CONFERENCE ROOM
 AREA IS NOT SIZED PROPERLY.R/A JUMPER
 SHALL BE A MINIMUM OF 1 1/2 TIMES THE
 SQUARE INCHES OF THE SUPPLY AIR INTO
 THAT SPACE.PLEASE INCREASE SIZE OF
 R/A
 JUMPER OR PROVIDE AN ADDITIONAL 10" R/A
 JUMPER.
  
 2.NO DUCT SIZE INDICATED ON THE
 FOLLOWING:
 R/A JUMPER INTO THE CONFERENCE RM
 R/A JUMPER FROM THE OFFICE AREAS ON
 THE GROUND FLOOR.
 R/A DUCT FROM A/C 1
 R/A JUMPER FROM 2ND FL PRIVATE OFFICE
  
  
 3.RETURN AIR REQUIRED FROM THE
 SECRETARY'S OFFICE ON THE 2ND FLOOR
 ALONG WITH THE 1" DOOR UNDERCUT PER THE
  
 2001 FBC(M)601.4 EXCEPTION 1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-07-21 Cont ID  
Sent By pkrauss Date 2004-07-21 Time 06:39 Rev Time 0.35
Received By pkrauss Date 2004-07-21 Time 06:20 Sent To  
Notes
2004-07-21 00:00:00PROVISO:
 1.DUCT SMOKE DETECTORS TO BE INSTALLED
 IN THE SUPPLY AIR DUCT & NOT THE RETURN
 AS INDICATED.2001 FBC(M) 606.2.1.
  
 2.RETURN AIR REQUIRED FROM THE 2ND
 FLOOR SECRETARY'S OFFICE & THE 1ST FLOOR
 CONFERENCE ROOM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-06-08 Cont ID  
Sent By pkrauss Date 2004-06-08 Time 07:48 Rev Time 0.40
Received By pkrauss Date 2004-06-08 Time 07:31 Sent To  
Notes
2004-06-08 00:00:00DENIED:
 1.PLAN SHEET 5 OF 5 NOTE #17, OUTSIDE
 AIR CALCS BASED ON ASHRAE 62-89.PLEASE
 PROVIDE THE CALCULATIONS.
  
 2.INDICATE OUTSIDE AIR DUCT, SIZE,
 MATERIAL, LAYOUT & INTAKE LOCATION.
  
 3.THE GROUND FLOOR MECHANICAL PLAN
 SOME OF THE DUCTS ARE NOT SIZED.
  
 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUUPIED AREAS PER NFPA 90A
 6.4.4.3 (1).
  
 5.DETAIL FOR THE REFRIGERANT LINES
 DOES NOT INDICATE INSULATION ON THE
 PIPING PER 2001 FBC CHAPTER 13 SUB-
 CHAPTER 611.1.ABC.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-11-29 Cont ID  
Sent By kstevens Date 2004-11-29 Time 11:26 Rev Time 0.50
Received By kstevens Date 2004-11-29 Time 11:26 Sent To  
Notes
2004-11-29 00:00:00REVISION OK - CHANGED LOCATION OF BREAK
 ROOM SINK.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-08-18 Cont ID  
Sent By lmartine Date 2004-08-18 Time 10:12 Rev Time 0.50
Received By lmartine Date   Time   Sent To  
Notes
2004-08-18 00:00:00 
 SEE PLANS FOR PLUMBING REVIEW APPROVAL

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-05 Cont ID  
Sent By kstevens Date 2004-06-05 Time 16:05 Rev Time 1.00
Received By kstevens Date 2004-06-05 Time 16:05 Sent To  
Notes
2004-06-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
  
  
 1) SHT 1 OF 5 GROUND FLOOR PLAN. LOUNGE
 SINK SHALL COMPLY WITH 11-4.24 AND ALL
 SUBSECTIONS. SHOW TURNING AREA SEE FIGS
 3A & 3B. SECTION 11-4.2.3 & 11-4.2.4.2
 2) SHT 1 OF 5 GROUND FLOOR PLAN. TOILET
 ROOM - SHOW CLEAR FLOOR SPACE FOR LAV &
 W/C. SHOW TURNING AREA PER SECTION 11-4.
 22.3.
 3) SHT 1 OF 5 DOORS SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE FOR ANY FIXTURE.
 SEE TOILET ROOM DOOR. SECTION 11-4.22.2
 4) PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED. ALSO SEE SECTION 410.1.
 5) SHOW LOCATION OF WATER HEATER ON THE
 FLOOR PLAN. SECTION 104.2.1
 6) SUBMIT A WATER RISER DIAGRAM. SECTION
 104.3.1.1 - SHOW LOCATION OF WATER HAMM-
 ER ARRESTORS PER PDI-WH 201.
 7) SHT 5 OF 5 UNDER PLUMBING NOTES THERE
 ARE GAS NOTES. A SEPARATE GAS PERMIT IS
 REQUIRED IF THERE IS GAS BEING INSTALLED
 SEPARATE GAS PLANS REQUIRED ALSO. SECT-
 ION 104.3.1.1
 8) SEE ELECTRICAL REVIEW CONCERNING THE
 SIGNATURE OF THE ARCHITECT, AND REMOVAL
 OF OLD SHEETS WHEN RESUBMITTING PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-12-02 Cont ID  
Sent By mmclean Date 2004-12-02 Time 11:08 Rev Time 0.00
Received By mmclean Date 2004-12-02 Time 11:08 Sent To  
Notes
2004-12-02 00:00:00RETURNED TO COMM BOARD #51

Review Stop Z ZONING
Rev No 1 Status P Date 2004-05-28 Cont ID  
Sent By mmclean Date 2004-05-28 Time 16:08 Rev Time 0.00
Received By mmclean Date 2004-05-28 Time 16:08 Sent To  
Notes
***NONE***