Plan Review Details - Permit 04050853
Plan Review Stops For Permit 04050853
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-07-12 Cont ID  
Sent By lsmith Date 2004-07-12 Time 09:40 Rev Time 1.00
Received By lsmith Date 2004-07-08 Time 09:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-17 Cont ID  
Sent By mjacobs Date 2004-06-17 Time 14:08 Rev Time 1.00
Received By mjacobs Date 2004-06-17 Time 14:08 Sent To PC
Notes
2004-06-17 00:00:00BUILDING PLAN REVIEW
 PERMIT:04050853
 ADD:1450 CENTREPARK BLVD SUITE 325
 CONT:BURKARDT CONSTRUCTION, INC
 TEL: (561)659-1400
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 1ST REVIEW
 ACTION: DENIED
  
 1)1004.1.4 WHERE 2 OR MORE EXITS OR
 EXIT ACCESS DOORS ARE REQUIED, AT LEAST
 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL
 BE PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN 1/2 OF THE LENGTH OF THE MAX-
 IMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED.
  
 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3)11-4.24.2 HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER OR RIM NO
 HIGHER THAN 34" ABOVE THE FINISH FLOOR.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 MYRON JACOBS
 TEL: (561)805-6726

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-06-23 Cont ID  
Sent By dpalmer Date 2004-06-23 Time 07:31 Rev Time 0.50
Received By dpalmer Date 2004-06-22 Time 21:15 Sent To  
Notes
2004-06-23 00:00:00****************************************
  
 CONTRACTOR IS TO COME DOWN AND REMOVE
 ALL OLD/VOIDED SHEETS AND INSERT NEW
 SHEETS INTO COMPLETE SETS FOR REVIEW
 AND STAMPING.
 NEW SHEETS NOT IN SETS.
 ****************************************

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-25 Cont ID  
Sent By mjacobs Date 2004-06-21 Time 15:07 Rev Time 1.00
Received By dpalmer Date 2004-05-25 Time 13:07 Sent To  
Notes
2004-05-25 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SEE CERTIFICATE OF AUTHO-
 -RIZATION # PRINTTED ON TITLE BLOCK
 BELONGS TO ROY F JOHNS & ASSOCIATES.
 PLEASE SEE COPY OF PRINT OUT FROM DBPR.
 THIS IS REQUIRED TO BE CORRECTED ON
 ALL SHEETS WHEATHER OR NOT COMMENT IS
 MADE FROM OTHER REVIEWERS.
  
 2)NOTE: PLEASE SEE FS 471.025/ FAC 61G15
 -23.002. PLEASE PROVIDE A FULL SIGNATURE
 CONTAINING A MIN OF FIRST AND LAST NAME.
 INITIALS ARE NOT PERMITTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-06-23 Cont ID  
Sent By mcarsill Date 2004-06-23 Time 13:49 Rev Time 0.00
Received By mcarsill Date 2004-06-23 Time 13:49 Sent To  
Notes
2004-06-23 00:00:00ELECTRONIC LOCKS TO COMPLY WITH FIRE
 CODE REQUIREMENTS.
  
 MIKE CARSILLO, ASSSTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-05-20 Cont ID  
Sent By mcarsill Date 2004-05-20 Time 10:49 Rev Time 0.00
Received By mcarsill Date 2004-05-20 Time 10:49 Sent To  
Notes
2004-05-20 00:00:001) HOW DOES THE ELECTRIC STRIKES ON
 DOORS 305 AND 312 AFFECT EXITING.
 ANY LOCKING DEVICES INSTALLED ON
 EGRESS DOORS SHALL COMPLY WITH
 ALL OF THE REQUIREMENTS OF THE LIFE
 SAFETY CODE, 2000 EDITION, CHAPTER 7.
  
 2) SEPARATE PERMITS REQUIRED FOR ANY
 REQUIRED REMODEL OF THE FIRE SPRINKLER
 OR FIRE ALARM SYSTEM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-21 Cont ID  
Sent By mjacobs Date 2004-06-21 Time 15:07 Rev Time 0.00
Received By mjacobs Date 2004-06-21 Time 15:07 Sent To  
Notes
2004-06-21 00:00:00TO COMM BD#13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-20 Cont ID  
Sent By csiegber Date 2004-05-20 Time 08:37 Rev Time 0.00
Received By csiegber Date 2004-05-20 Time 08:37 Sent To  
Notes
2004-05-20 00:00:00TO COMM BD#34

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-07-02 Cont ID  
Sent By pkrauss Date 2004-07-02 Time 09:02 Rev Time 0.40
Received By pkrauss Date 2004-07-02 Time 09:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-06-09 Cont ID  
Sent By pkrauss Date 2004-06-09 Time 07:04 Rev Time 0.50
Received By pkrauss Date 2004-06-09 Time 07:02 Sent To  
Notes
2004-06-09 00:00:00DENIED:
 1.CERTIFICATE OF AUTHORIZATION # ON
 THE TITLE BLOCK IS NOT CORRECT ACCORDING
 TO DBPR.PLEASE CORRECT.
  
 2.PLAN SHEET M2.1 INDICATES EXHAUST
 AIR FROM EF-1 DISCHARGING INTO THE
 PLENUM.PER 2001 FBC(M) 501.3, EVERY
 MECHANICAL EXHAUST SYSTEM SHALL BE
 DISCHARGED TO THE OUTDOORS WHERE IT
 CANNOT BE DRAWN IN BY A VENTILATING
 SYSTEM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-07-09 Cont ID  
Sent By kstevens Date 2004-07-09 Time 17:48 Rev Time 1.00
Received By kstevens Date 2004-07-09 Time 17:48 Sent To  
Notes
2004-07-09 00:00:00 
  
  
  
  
 PASSED/PROVISO
  
 SECTION 608.3 ALL DEVICES INTENDED TO
 SERVE SOME SPECIAL FUNCTION SUCH AS
 COOLING, AND THAT CONNECT TO THE WATER
 SUPPLY SYSTEM, SHALL BE PROVIDED WITH
 PROTECTION AGAINST BACKFLOW AND CONTAM-
 INATION OF THE WATER SUPPLY. COMMERCIAL
 DRINKING WATER DISPENSERS SHALL BE PRO-
 TECTED AGAINST CONTAMINATION.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 Z

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-12 Cont ID  
Sent By kstevens Date 2004-06-12 Time 15:58 Rev Time 0.50
Received By kstevens Date 2004-06-12 Time 15:58 Sent To  
Notes
2004-06-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT A-2 SHOW KNEE CLEARANCE 11-4.24.3
 DEPTH 11-4.24.4. CLEAR FLOOR SPACE 11-4.
 24.5, EXPOSED PIPES AND SURFACES 11-4.24
 .6 ON DETAIL FOR LOUNGE SINK.
 2) SUBMIT MANUFACTURE SPECIFICATION FOR
 WATER COOLER. FIXTURE, DEVISE OR APPLI-
 ANCE USING WATER FOR ITS PROPER OPERAT-
 ION SHALL BE DIRECTLY OR INDIRECTLY CON-
 NECTED TO THE WATER SUPPLY. SEE SECTIONS
 301.2, 301.3 & 301.4.
 3) SEE ELECTRICAL REVIEW CONCERNING THE
 CERTIFICAT OF AUTHROIZATION REQUIRED ON
 TITLE BLOCK OF SIGNED/SEALED PLANS.
 61G15-23.002 FAC & FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]